Plan Review Details - Permit 05010913
Plan Review Stops For Permit 05010913
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-15 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 10:49 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2005-02-15 00:00:00DID NOT DO ELECTRICAL REVIEW ON PLANS.
 VALUE INCREASED BY CONT TO $9300.00

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-01 Cont ID  
Sent By btrobaug Date 2005-02-01 Time 12:44 Rev Time 0.25
Received By btrobaug Date 2005-02-01 Time 12:44 Sent To M
Notes
2005-02-01 00:00:00 
  
  
 PLEASE INCREASE THE VALUE OF THE PERMIT
 APPLICATION TO INCLUDE ALL LABOR AND
 MATERIAL. THIS INCLUDES THE COST OF THE
 GENERATOR AND ALL RELATED EQUIPMENT, NO
 MATTER WHO FURNISHES SAME.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-01-31 Cont ID  
Sent By btrobaug Date 2005-01-31 Time 15:19 Rev Time 0.50
Received By btrobaug Date 2005-01-31 Time 13:21 Sent To Z
Notes
2005-01-25 00:00:00 
  
  
 PROVISO
  
 1} THE TRANSFER SWITCH MUST BE LISTED AS
 SERVICE EQUIPMENT TO COMPLY WITH 230.72
 AND 225.31,225.32.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 16:20 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 16:20 Sent To E
Notes
2005-01-20 00:00:00TO "E' BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-02-07 Cont ID  
Sent By btrobaug Date 2005-02-07 Time 16:52 Rev Time 0.30
Received By pkrauss Date 2005-02-07 Time 16:47 Sent To P
Notes
2005-02-07 00:00:00PLANS DO NOT INDICATE DISTANCE FROM THE
 MUFFLER TERMINATION TO THE PROPERTY
 LINES.PLEASE NOTE EXHAUST TERMINATION
 SHALL BE DONE IN SUCH A MANNER THAT
 NOXIOUS FUME CANNOT BE DRAWN IN BY FRESH
 AIR INTAKES, WINDOWS OR DOORS PER 2001
 FBC(M)501.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT(561)805-6719.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-01 Cont ID  
Sent By mmclean Date 2005-02-01 Time 12:42 Rev Time 0.00
Received By mmclean Date 2005-02-01 Time 12:42 Sent To E
Notes
2005-02-01 00:00:00GIVEN TO BILL T MM