Plan Review Details - Permit 05010869
Plan Review Stops For Permit 05010869
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-16 Cont ID  
Sent By shill Date 2005-03-16 Time 14:11 Rev Time 1.00
Received By shill Date 2005-03-16 Time 13:59 Sent To PC
Notes
2005-03-16 00:00:00PROVISO - ARCHITECT TO SUBMIT DATED
 SHEETS A2 AND A4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-28 Cont ID  
Sent By shill Date 2005-01-28 Time 09:05 Rev Time 2.00
Received By shill Date 2005-01-28 Time 09:05 Sent To  
Notes
2005-01-28 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)DETAIL 10-A3, LOUNGE SINK IS TO
 COMPLY WITH FBC11-4.24.3 (KNEE
 CLEARANCE), SINK DEPTH A MAX OF 6 1/2"
 DEEP (11-4.24.4), MOUNTED WITH THE RIM
 NO HIGHER THAN 34" (11-4.24.2).A KNEE
 CLEARANCE IS SHOWN BUT THAT CLEARANCE
 IS
 BLOCKED BY THE CABINETRY.NOTE THAT
 DETAILS 8-A3 AND 10-A3 CONFLICT IN SINK
 HEIGHT.
  
 2.)A1, BUILDING CODE CLASSIFICATION,
 LOAD DECLARES 39.PLEASE CLARIFY.
  
 3.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC 13-103.1.2.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-01-25 Cont ID  
Sent By dpalmer Date 2005-01-25 Time 14:55 Rev Time 0.50
Received By dpalmer Date 2005-01-25 Time 14:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-02-09 Cont ID  
Sent By mcarsill Date 2005-02-09 Time 16:32 Rev Time 0.00
Received By mcarsill Date 2005-02-09 Time 16:32 Sent To  
Notes
2005-02-09 00:00:001. SEPARATE PLANS AND PERMITS
 FOR ANY FIRE SPRINKLER OR FIRE ALARM
 REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-23 Cont ID  
Sent By adarroug Date 2005-02-23 Time 14:54 Rev Time 0.00
Received By adarroug Date 2005-02-23 Time 14:54 Sent To  
Notes
2005-02-23 00:00:00TO "COMM" BD#64

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-19 Cont ID  
Sent By mjacobs Date 2005-01-19 Time 16:15 Rev Time 0.00
Received By mjacobs Date 2005-01-19 Time 16:15 Sent To  
Notes
2005-01-19 00:00:00TO "COMM BD#58"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-06-01 Cont ID  
Sent By hmoser Date 2005-06-01 Time 13:45 Rev Time 0.00
Received By hmoser Date 2005-06-01 Time 13:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-03-15 Cont ID  
Sent By pkrauss Date 2005-03-15 Time 07:07 Rev Time 0.40
Received By pkrauss Date 2005-03-14 Time 16:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-02-03 Cont ID  
Sent By pkrauss Date 2005-02-03 Time 13:30 Rev Time 0.55
Received By pkrauss Date 2005-02-03 Time 09:03 Sent To  
Notes
2005-02-03 00:00:00DENIED:
 1.PLAN SHEET M2.1, ERU-1 INDICATED IN
 THE RESTROOM AREAS.IS THIS AN EXHAUST
 UNIT?PLANS APPEAR TO HAVE THE DUCTWORK
 FROM ERU-1 TAPPING INTO THE RETURN
 DUCTWORK FROM AHU-4 & 8.PER 2001
 FBC(M) TABLE 403.3, EXHAUST FROM
 BATHROOM AREAS SHALL NOT BE
 RECIRCULATED.EXHAUST DUCT SHALL
 TERMINATE TO THE OUTDOORS PER
 2001FBC(M)501.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-15 Cont ID  
Sent By kstevens Date 2005-03-15 Time 13:39 Rev Time 1.25
Received By kstevens Date 2005-03-15 Time 13:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-08 Cont ID  
Sent By kstevens Date 2005-02-08 Time 09:51 Rev Time 1.92
Received By kstevens Date 2005-02-08 Time 09:51 Sent To  
Notes
2005-02-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 SHOW TURNING AREA IN EACH
 TOILET ROOMS DETAIL #2. SECTION
 11-4.22.3.
 2) SHT A-1 SHOW CLEAR FLOOR SPACE FOR
 THE LOUNGE SINK. SECTION 11-4.24.5.
 (FORWARD APPROACH REQUIRED, MAXIMUM 19"
 UNDERNEATH THE SINK).
 3) SHT A-3 DETAIL #7 FLUSH CONTROLS TO
 BE MOUNTED ON THE WIDE SIDE OF THE
 TOILET AREA. SECTION 11-4.16.5. - DETAIL
 #10 MAXIMUM SINK DEPTH TO BE 6-1/2".
 SECTION 11-4.24.4. (MAX. 7" SHOWN).
 4) SUBMIT A DETAIL FOR THE DRINKING
 SHOWING COMPLIANCE WITH 11-4.15 AND ALL
 SUBSECTIONS.
 5) SHT P0.1 PLUMBING FIXTURE SCHEDULE.
 SUBMIT MANUF. SPECIFICATION SHEETS FOR
 THE POWERSTREAM RP-1 TANKLESS WATER
 HEATER. SHEETS SHALL SHOW LISTING, AND
 INSTALLATION INSTRUCTIONS. SECTION
 303.4
 6) SHT P5.1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED IN AN
 "EFFECTIVE RANGE" NEXT TO THE FIXTURES,
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF INSTALL. INSTRUCTIONS.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]