Plan Review Details - Permit 05010713
Plan Review Stops For Permit 05010713
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-31 Cont ID  
Sent By btrobaug Date 2005-01-31 Time 10:31 Rev Time 0.33
Received By btrobaug Date 2005-01-31 Time 10:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By btrobaug Date 2005-01-24 Time 14:42 Rev Time 0.50
Received By btrobaug Date 2005-01-18 Time 09:01 Sent To  
Notes
2005-01-24 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE FLOOR PLANS INDICATING
 LOCATION OF THE EMERGENCY AND EXIT
 LIGHTS. ALSO SHOW LIGHTING AND CIRCUITS
 SO COMPLIANCE WITH 700.18 CAN BE
 DETERMINED.
  
 2} THE LOAD CALCULATION SHOULD BE
 DETERMINED PER 220.3 NOT 220.30.
  
 3} THE 100 AMP. ELEVATER EQUIPMENT
 PANEL
 SHOWN AS MUST BE FED WITH #3 CU PER
 310.16.*
  
 4} THE 100 AMP PANELS ON THE 1ST FLOOR
 MUST BE FED WITH #3 CU PER 310.16.*
  
 * IF FEEDERS ARE PROTECTED BY
 APPROPRIATE OCP PROVIDE PANEL SCHEDULE
 INDICATING SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-14 Cont ID  
Sent By mjacobs Date 2005-01-14 Time 15:28 Rev Time 0.00
Received By mjacobs Date 2005-01-14 Time 15:28 Sent To E
Notes
2005-01-14 00:00:00TO "E' BOX.