Plan Review Details - Permit 05010528
Plan Review Stops For Permit 05010528
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-25 Cont ID  
Sent By shill Date 2005-03-25 Time 10:36 Rev Time 0.50
Received By shill Date 2005-03-25 Time 10:36 Sent To PC
Notes
2005-03-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, INDICATE METHOD
 OF INSTALLATION AND WHICH PRODUCT IS
 BEING INSTALLED.A RESPONSE WAS
 PROVIDED - "WITH A DRILL".THIS DOES
 NOT SHOW CODE COMPLIANCE.THERE ARE TWO
 ACCORDIAN SHUTTERS WITH VARIOUS METHODS
 OF ATTACHMENT ON YOUR PRODUCT APPROVAL.
 PLEASE CIRCLE WHICH PRODUCT YOU ARE
 USING AND CIRCLE THE DRAWING WHICH SHOWS
 METHOD OF INSTALLATION (INSIDE MOUNT,
 WALL MOUNT, ETC).SHEET 6 HAS THE
 TAPCON FASTENERS FOR THE 6.8 ACCORDIAN
 SHUTTER HIGHLIGHTED, BUT BOTH THE 2"
 EDGE DISTANCE AND 3" EDGE DISTANCE ARE
 HIGHLIGHTED.IS THIS CORRECT?
  
 2.)IN RESPONSE TO THE PREVIOUS REQUEST
 TO FILL OUT THE SCHEDULE FOR
 INSTALLATION, A WALL PRESSURE WAS
 PROVIDED OF -30/-175.OPENINGS HAVE A
 POSITIVE AND NEGATIVE PRESSURE; HOW HAVE
 YOU ARRIVED AT TWO NEGATIVE NUMBERS?
 PLEASE PROVIDE CORRECT DP.IF THIS IS A
 ONE STORY SINGLE FAMILY DWELLING, THE
 -30 IS TOO LOW AND THE -175 IS TOO HIGH.
 SEE FBC TABLE1606.2B AND D, AND FIGURE
 1606.2(C).
  
 3.)SEE PREVIOUS LIST, ITEM #3, FLORIDA
 STATE PRODUCT APPROVAL OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO TEST
 REPORT, WWW.FLORIDABUILDING.ORG.
  
 4.)SHOW EMERGENCY MEANS OF ESCAPE
 FBC1005.4.4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By shill Date 2005-01-25 Time 15:50 Rev Time 0.50
Received By shill Date 2005-01-25 Time 15:26 Sent To PC
Notes
2005-01-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.) INDICATE METHOD OF INSTALLATION,
 WHICH PRODUCT IS BEING INSTALLED, ETC.
 TO SHOW CODE COMPLIANCE FBC CHAPTER 16.
  
 2.)COMPLETE THE ATTACHED SCHEDULE FOR
 INSTALLATION.
  
 3.)FLORIDA STATE PRODUCT APPROVAL OR
 LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO TEST REPORT.
 WWW.FLORIDABUILDING.ORG

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-25 Cont ID  
Sent By adarroug Date 2005-03-25 Time 10:01 Rev Time 0.00
Received By adarroug Date 2005-03-25 Time 10:01 Sent To B
Notes
2005-03-25 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-12 Cont ID  
Sent By mjacobs Date 2005-01-12 Time 15:34 Rev Time 0.00
Received By mjacobs Date 2005-01-12 Time 15:34 Sent To B
Notes
2005-01-12 00:00:00TO "MISC" BOX.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved