 |
Plan Review Details - Permit 05010378
Plan Review Stops For Permit 05010378 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2006-02-08 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-02-08 |
Time |
13:18 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-02-08 |
Time |
13:17 |
Sent To |
|
|
Notes |
2006-02-08 00:00:00 | UNITY OF TITLE ,NEW PCN = | | 74434321060230120 HAS THE SAME ADDRESS: | | 909 3RD ST . |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2006-02-07 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2006-02-07 |
Time |
14:43 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2006-02-07 |
Time |
14:16 |
Sent To |
|
|
Notes |
2006-02-07 00:00:00 | ADD: 909 3RD ST | | CONT: NEWBOLD CONSTRUCTION | | TEL: (561)644-5764 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 2ND REVIEW | | ACTION: DENIED | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | THE NOC FILED WILL HAVE THE WRONG | | PROPERTY CONTROL NUMBER ONCE THE UNITY | | OF TITLE OCCURS.WILL HAVE TO BE REFILED. | | THE UNITITY OF TITLE WILL MAKE LOT # 12 | | THE PCN TO USE TO IDENTIFY THE PROPERTY. | | | | ALSO CORRECT THE PCN ON THE PERMIT | | APPLICATION TO LOT 12. | | 74-43-43-21-06-023-0120 | | | | | | | | 2) OK! | | | | 3OK! | | 4) OK! | | | | 5)PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 6)FL BLD CODE 1606.1.5: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORTS,MISSING REPORTS ARE AS | | FOLLOWS: | | A) TRUSS ANCHORS OK | | B) ROOFING ASSEMBLIES NO | | C) TRACO WINDOWS DADE COUTY REPORT | | SUBMITTED SHOULD BE AAMA CERTIFICATION | | PROGRAM. NO | | D) STORM SHUTTERS REPORT SUBMITTED IS A | | SBCCI REPORT SUBMITTED TO STATE IS A | | MIAMI/ DADE REPORT CORRECT.NO | | | | 7) FL BLD CODE 2001 SECTION 103.6, | | 1606.1.4, 1707.4 & 3401.7.2.4. | | PROCEDURES: 1(B) A COMPLETE INSTALLATION | | SCHEDULE SUMMARIZING & IDENTIFYING | | OPENING SIZES, STORY HEIGHTS, UNIT MARK | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM | | BAR REINFORCING REQUIREMENTS, WALL PRES- | | SURE ZONES, SLAT TYPES, ETC., SHALL BE | | SUBMITTED AT TIME OF PERMIT APPLICATION | | TO FACILITATE PLAN REVIEW AND PERMIT | | ISSUANCE. NO, SAMPLE FORM ATTACHED | | | | 8) SHEET 5 NOW IS MISSING? ASSUMING | | SHEET # 5 WAS FOR THE STEPPLE. | | | | 9) IS THE STEEPLE PART OF THIS PERMIT? | | ASSUMING SHEET # 5 WAS FOR THE STEEPLE! | | | | 10) SHEET 2 THE DINING ROOM INTO THE | | FELLOWSHIP HALL.FROM THE EXISTING ROOM | | CONNECTING WITH THE PROPOSED FELLOWSHIP | | HALL ONLY HAS ONE EXIT INTO THE NEW | | FELLOWSHIP HALL, 2 EXITS ARE REQUIRED | | FOR ROOMS WITH OCCUPANT LOADS GREATER | | THAN 50. | | TABLE 1003.1 ASSEMBLY WITHOUT FIXED | | SEATING OCC LOAD TO BE 7 SQ FT / NET THE | | OCC LOAD OF THE EXISTING DINING ROOM | | WOULD BE 98 REQUIRING 2 EXITS. | | 1004.1.4 WHERE 2 OR MORE EXITS OR | | EXIT ACCESS DOORS ARE REQUIED, AT LEAST | | 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL | | BE PLACED A DISTANCE APART EQUAL TO NOT | | LESS THAN 1/2 OF THE LENGTH OF THE MAX- | | IMUM OVERALL DIAGONAL DIMENSION OF THE | | BUILDING OR AREA TO BE SERVED. | | | | EXIT SIGNS SHALL BE MARKED BY AN | | APPROVED SIGN READILY VISIBLE FROM ANY | | DIRECTION OF EXIT ACCESS. EVERY EXIT | | SIGN SHALL BE SUITABLE ILLUMINATED BY A | | RELIABLE LIGHT SOURCE. EXTERNALLY AND | | INTERNALLY ILLUMINATED SIGNS SHALL BE | | VISIBLE IN BOTH THE NORMAL & EMERGENCY | | LIGHTING.MISSING IN EXISTING FELLOWSHIP | | HALL. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-07-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-07-24 |
Time |
15:59 |
Rev Time |
1.55 |
Received By |
jwitmer |
Date |
2005-07-24 |
Time |
15:47 |
Sent To |
|
|
Notes |
2005-07-24 00:00:00 | PERMIT: 05010378 | | ADD: 909 3RD ST | | CONT: NEWBOLD CONSTRUCTION | | TEL: (561)644-5764 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 2ND REVIEW | | ACTION: DENIED | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | THE NOC FILED WILL HAVE THE WRONG | | PROPERTY CONTROL NUMBER ONCE THE UNITY | | OF TITLE OCCURS.WILL HAVE TO BE REFILED. | | | | | | 2) THE PROPOSED BUILDING STRUCTURE | | TRANSGRESSES LEGAL BOUNDARY LINES | | BETWEEN THE LOTS WHICH COMBINE TO FORM | | 'THE SITE'.A 'UNITY OF TITLE' SHALL BE | | RECORDED AT THE COUNTY COURTHOUSE. | | SUBMIT A COPY OF THE RECORDED 'UNITY OF | | OF TITLE' DOCUMENT SO THAT FBC TABLE 600 | | BOUNDARY LINE REQUIREMENTS MAY BE DEEMED | | NOT APPLICABLE.SEE ATTACHMENTS. UNITY OF | | TITLE FORMS ARE FOUND ON THE 5TH FLOOR | | ZONING DEPARTMENT. | | | | 3 PROVIDE WHAT SLOPE THE CRICKET WILL | | HAVE? WILL IT ALSO HAVE SHINGLES ON | | ROOF? | | | | 4) PROVIDE THE POSITIVE AND NEGATIVE | | PRESSUESFOR OPENINGS ON ELEVATIONS, | | ENCLUDE ENDZONES. | | | | 5)PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 6)FL BLD CODE 1606.1.5: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORTS,MISSING REPORTS ARE AS | | FOLLOWS: | | A) TRUSS ANCHORS | | B) ROOFING ASSEMBLIES | | C) TRACO WINDOWS DADE COUTY REPORT | | SUBMITTED SHOULD BE AAMA CERTIFICATION | | PROGRAM. | | D) STORM SHUTTERS REPORT SUBMITTED IS A | | SBCCI REPORT SUBMITTED TO STATE IS A | | MIAMI/ DADE REPORT CORRECT. | | | | 7) FL BLD CODE 2001 SECTION 103.6, | | 1606.1.4, 1707.4 & 3401.7.2.4. | | PROCEDURES: 1(B) A COMPLETE INSTALLATION | | SCHEDULE SUMMARIZING & IDENTIFYING | | OPENING SIZES, STORY HEIGHTS, UNIT MARK | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM | | BAR REINFORCING REQUIREMENTS, WALL PRES- | | SURE ZONES, SLAT TYPES, ETC., SHALL BE | | SUBMITTED AT TIME OF PERMIT APPLICATION | | TO FACILITATE PLAN REVIEW AND PERMIT | | ISSUANCE. | | | | 8) SHEET 5 NOW IS MISSING? | | | | 9) IS THE STEEPLE PART OF THIS PERMIT? | | | | 10) SHEET 2 MISSING THE EXITFROM THE | | DINING ROOM INTO THE FELLOWSHIP HALL. | | FROM THE EXISTING ROOM CONNECTING WITH | | THE PROPOSED FELLOWSHIP HALL ONLY HAS | | ONE EXIT INTO THE NEW FELLOWSHIP HALL, | | 2 EXITS ARE REQUIRED FOR ROOMS WITH | | OCCUPANT LOADS GREATER THAN 50. | | 1004.1.4 WHERE 2 OR MORE EXITS OR | | EXIT ACCESS DOORS ARE REQUIED, AT LEAST | | 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL | | BE PLACED A DISTANCE APART EQUAL TO NOT | | LESS THAN 1/2 OF THE LENGTH OF THE MAX- | | IMUM OVERALL DIAGONAL DIMENSION OF THE | | BUILDING OR AREA TO BE SERVED. | | | | EXIT SIGNS SHALL BE MARKED BY AN | | APPROVED SIGN READILY VISIBLE FROM ANY | | DIRECTION OF EXIT ACCESS. EVERY EXIT | | SIGN SHALL BE SUITABLE ILLUMINATED BY A | | RELIABLE LIGHT SOURCE. EXTERNALLY AND | | INTERNALLY ILLUMINATED SIGNS SHALL BE | | VISIBLE IN BOTH THE NORMAL & EMERGENCY | | LIGHTING.MISSING IN EXISTING FELLOWSHIP | | HALL. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-01-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-01-24 |
Time |
12:16 |
Rev Time |
3.33 |
Received By |
jwitmer |
Date |
2005-01-24 |
Time |
11:01 |
Sent To |
|
|
Notes |
2005-01-24 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05010378 | | ADD: 909 3RD ST | | CONT: NEWBOLD CONSTRUCTION | | TEL: (561)644-5764 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | 2) THE PROPOSED BUILDING STRUCTURE | | TRANSGRESSES LEGAL BOUNDARY LINES | | BETWEEN THE LOTS WHICH COMBINE TO FORM | | 'THE SITE'.A 'UNITY OF TITLE' SHALL BE | | RECORDED AT THE COUNTY COURTHOUSE. | | SUBMIT A COPY OF THE RECORDED 'UNITY OF | | OF TITLE' DOCUMENT SO THAT FBC TABLE 600 | | BOUNDARY LINE REQUIREMENTS MAY BE DEEMED | | NOT APPLICABLE. | | | | 3) 3401.7.1.1.2 WHEN THE ADDITION IS | | OVER 25% OF THETHE EXISTING BUILDING | | AREA AND NOT SEPERATED BY A FIRE WALL, | | THE EXISTING BUILDING AND THE ADDITION | | SHALL BE MADE TO COMPLY WITH ALL THE | | REQUIREMENTS OF THIS CODE FOR A BUILDING | | OF AREA EQUAL TO THE COMBINED AREA OF | | THE ADDITION AND EXISTING BUILDING. | | EXCEP: EXISTING BUILDINGS SHALL NOT BE | | REQUIRED TO BE UPGRADED TO THE | | STRUCTURAL REQUIREMENTS OF THE CODE IN | | EFFECT ON THE DATE OF THE PERMIT FOR THE | | ADDTION. | | 4) PROVIDE THE CORRECT ENERGY FORMS, THE | | FORM SUBMITTED IS FOR RESIDENTIAL USE. | | | | 5) DESIGN STANARDS TO BE REVISED AND | | UPDATED: | | 2001 FLORIDA BUILDING CODE W/ 2003 | | REVISIONS | | CONCRETE ACI 318-02 | | MASONARY ACI 530/ ASCE 5 TMS402-02 | | | | 6) GABLE ENDWALL PLANS INDICATE THE USE | | OF A GABLE BEAM BUT NO MENTION OF THE | | BEAM AT THE EAVE HEIGHT NOR USE OF | | LENTALS? WHAT WILL HAPPEN OVER THE DOOR | | AND WINDOW OPENINGS? | | | | 7) NO INFORMATION FOR WINDOW AND DOOR | | SIZES? | | | | 8) PROVIDE WHAT SLOPE THE NEW ADDITION | | ROOF WILL BE? | | | | 9) PROVIDE THE POSITIVE AND NEGATIVE | | PRESSUESFOR OPENINGS ON ELEVATIONS, | | ENCLUDE ENDZONES. | | | | 10) FRONT ELEVATION OF THE FELLOWSHIP | | HALL MISSING THE 16" BEAM ON THE | | ELEVATION? | | | | 11)PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 12)FL BLD CODE 1606.1.5: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORTS,MISSING REPORTS ARE AS | | FOLLOWS: | | A) TRUSS ANCHORS | | B) ROOFING ASSEMBLIES | | | | 13) WINDOW BUCK DETAIL INDICATES THE | | USE OF A 1X2 BUCK WINDOW FRAME IS A | | 2.25" WIDE. 1707.4.4.2 TAPERED | | BUCKS: SHALL EXTEND BEYOND THE INTERIOR | | FACE OF THE WINDOW OR DOOR FRAME SUCH | | THAT FULL SUPPORT OF THE FRAME IS | | SUPPORTED. | | | | 14) FL BLD CODE 2001 SECTION 103.6, | | 1606.1.4, 1707.4 & 3401.7.2.4. | | PROCEDURES: 1(B) A COMPLETE INSTALLATION | | SCHEDULE SUMMARIZING & IDENTIFYING | | OPENING SIZES, STORY HEIGHTS, UNIT MARK | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM | | BAR REINFORCING REQUIREMENTS, WALL PRES- | | SURE ZONES, SLAT TYPES, ETC., SHALL BE | | SUBMITTED AT TIME OF PERMIT APPLICATION | | TO FACILITATE PLAN REVIEW AND PERMIT | | ISSUANCE. | | | | 15) SHEET 5 INDICATES THE USE OF A 90LB | | FELT FOR DRY IN?? | | | | 16) IS THE STEEPLE PART OF THIS PERMIT? | | | | 17) SHEET 2 MISSING THE EXITFROM THE | | DINING ROOM INTO THE FELLOWSHIP HALL. | | 1016.3.1. EXIT SIGNS: | | EXIT SIGNS SHALL BE MARKED BY AN | | APPROVED SIGN READILY VISIBLE FROM ANY | | DIRECTION OF EXIT ACCESS. EVERY EXIT | | SIGN SHALL BE SUITABLE ILLUMINATED BY A | | RELIABLE LIGHT SOURCE. EXTERNALLY AND | | INTERNALLY ILLUMINATED SIGNS SHALL BE | | VISIBLE IN BOTH THE NORMAL & EMERGENCY | | LIGHTING. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2006-10-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-26 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-25 |
Time |
12:33 |
Sent To |
PC |
|
Notes |
2006-10-26 12:46:51 | NO REVIEW DONE, PROJECT EXPIRED SEE FRONT SCREEN. | 2006-10-25 17:13:31 | PROJECT ONHOLD. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2006-01-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-01-31 |
Time |
20:31 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-01-31 |
Time |
19:34 |
Sent To |
|
|
Notes |
2006-01-31 00:00:00 | ************ UNSAT 3RD REVIEW ********* | | | | PLEASE SEE MANY NOTES FROM REVIEWS ONE | | AND TWO STILL NEED TO BE ADDRESSED. | | | | 1)NOTE:PLEASE SHOW ALL CIRCUITING ON | | PLANS AND CORRELATE WITH PANEL | | SCHEDULE(S). | | PLEASE SEE THERE ARE A FEW ITEMS ON | | PLANS WHICH STILL DO NOT SHOW THE | | CIRCUITING. | | PLEASE ALSO SEE NEW WATER FOUNTAIN HAS | | BEEN ADDED TO PLANS , HOWEVER PLANS DO | | NOT INDICATE ANY ELECTRICAL RECEPT FOR | | THIS UNIT. | | | | 2) PLEASE SEE 700.12E FOR EM/EXT LTS. | | THE BRANCH CIRCUIT FEEDING THE UNIT | | EQUIPMENT SHALL BE THE SAME BRANCH | | CIRCUIT AS THAT SERVING THE NORMAL | | LIGHTING IN THE AREA AND CONNECTED AHEAD | | OF ANY LOCAL SWITCHES. | | 215.5 | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | PLEASE SHOW PER | | 220.3,220.10,220.11,220.13 ETC. | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | AT 125% PER 215.3,230.42 | | PLEASE SEE LOAD CALCULATIONS SUBMITTED | | ARE ONLY LOAD ON SUB PANEL. | | PLEASE SHOW LOAD CALCUALTIONS FOR | | SERVICE AS REQUESTED ON PREVIOUS | | REVIEWS. PLEASE ALSO | | SEE LOAD CALCULATIONS ARE FOR | | RESIDENTIAL USE. | | | | 4)NOTE: PLEASE SEE NEW MAIN DISCONNECT | | PANELS APPEARS TO BE SHOWN, HOWEVER NO | | INFORMATION IS PROVIDED FOR THIS. | | AIC RATING, VOLTAGE, AMPERAGE, GROUPING | | ETC | | 215.5,110.9,110.14,230.72 ETC | | PLEASE SHOW PANELS, SERVICE LOCATION ON | | PLANS. | | PLEASE INDICATE CONDUCTORS FROM METER TO | | MAIN AND MAIN TO NEW SUB PANEL. | | 215.5,240.4,310.16,250.24,250.6 ETC. | | ** PLEASE KNOW, SINCE LOAD CALCUALTIONS | | HAVE STILL NOT BEEN SUBMITTED FOR | | SERVICE, REVIEW FOR EXISTING SERVICE ENT CONDUCTORS CAN | | NOT BE VERIFIED AT THIS | | TIME. | | ** PLEASE SEE AHU IS NOW BEING SHOWN AT | | 125%, HOWEVR THIS IS NOT REQUIRED. | | PLEASE SEE 424.3B ONLY REQUIRES THE OCP | | TO BE SIZED AT 125%. | | | | 5)NOTE: PLEASE SEE FLORIDA STATUES | | 481.221 WHICH REQUIRES TO THE ARCHITECT | | TO ALSO DATE PLANS WHEN SIGNING AND | | SEALING SAID PLANS. | | | | 6)NOTE: PLEASE SEE RISER NOW SHOWS NEW | | PANELS WHICH INDICATE THESE ARE FOR | | ADDITION?? | | PLEASE VEIRFY IF THESE ARE EXISITNG, NEW | | ETC. | | PLEASE KNOW, THERE IS NOT ENOUGH | | INFORMATION FOR THESE PANELS AS THEY DO | | NOT APPEAR TO BE SHOWN ON PLANS. | | 215.5 | | | | 7)NOTE: PLEASE SEE FLORIDA STATUES | | 553.80(2)(B) WITH RESPECT TO DESIGN | | PROFESSIONALS AND PLANS WITH REPEAT | | COMMENTS THREE OR MORE TIME FOR THE SAME | | CODE COMPLIANCE COMMENT(S). | | PLEASE KNOW, AS REQUIRED PER ABOVE FS, A | | 4X FEE FOR THE PLAN REVIEW PORTION OF | | THE PERMIT FEE SHALL BE ACCESSED TO THE | | "DESIGN PROFESSIONAL" FOR SAID | | VIOLATION. | | PLEASE SEE THE FEE OF $1,764.00 IS NOW | | ACCESSED AND IS REQUIRED PER FS | | 553.80(2)(B) TO BE PAID BEFORE | | RE-SUBMITTING PLANS. | | ** PLEASE KNOW, ONE COPY OF EACH OF THE | | ELECTRICAL PLANS SUBMITTED ARE NOW BEING | | RETAINED FOR FILE AND POSSIBLE REVIEW BY | | THE STATE BOARD OF ARCHITECTS AND STATE | | OF FLORIDA'S LEGAL COUNSEL. | | ** PLEASE KNOW, IT IS STRONGLY SUGGESTED | | A MEETING BE HELD ONCE ALL REVIEWS ARE | | COMPLETED BEFORE RESUBMITTING PLANS FOR | | NEXT REVIEWTO GO OVER ANY COMMENTS OR | | QUESTIONS. | | | | ** PLEASE SEE ANY OTHER COMMENTS FROM | | OTHER REVIEWER(S) WHICH MAY AFFECT | | ELECTRICAL PLANS. | | | | ** PLEASE BE SURE TO REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | REVISED SHEETS INTO COMPLETED SETS FOR | | REVIEW AND STAMPING. | | ONE COPY OF ALL OLD/VOIDED SHEETS SHALL | | BE SUBMITTED FOR REFERENCE. | | PLEASE SEE THE ABOVE WAS REQUESTED ON | | PREVIOUS REVIEW, HOWEVER ALL OLD/VOIDED | | SHEETS WERE LEFT IN SETS. | | | | | | PLEASESUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2005-07-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-07-06 |
Time |
18:12 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2005-07-06 |
Time |
18:12 |
Sent To |
|
|
Notes |
2005-07-06 00:00:00 | ************ UNSAT2ND REVIEW ********* | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | REVIEW STILL NEED TO BE ADDRESSED. | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | PLANS AND CORRELATE WITH PANEL | | SCHEDULE(S). PLEASE SEE 700.12E FOR | | EM/EXT LTS. | | 215.5 | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | PLEASE SHOW PER | | 220.3,220.10,220.11,220.13 ETC. | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | AT 125% PER 215.3,230.42 | | PLEASE SEE LOAD CALCULATIONS SUBMITTED | | ARE ONLY LOAD ON SUB PANEL. PLEASE ALSO | | SEE LOAD CALCULATIONS ARE FOR | | RESIDENTIAL USE. | | | | 2)NOTE: PLEASE SEE NEW MAIN DISCONNECT | | APPEARS TO BE SHOWN, HOWEVER NO | | INFORMATION IS PROVIDED FOR THIS. | | AIC RATING, VOLTAGE, AMPERAGE, GROUPING | | ETC | | 215.5,110.9,110.14,230.72 ETC | | PLEASE INDICATE CONDUCTORS FROM METER TO | | MAIN AND MAIN TO NEW SUB PANEL. | | 215.5,240.4,310.16,250.24,250.6 ETC. | | | | 3)NOTE: PLEASE SHOW LOCATION OF COND | | UNIT AND DISC'S REQUIRED FOR A/C CU AND | | AHU. 440.11 | | PLEASE ALSO SEE MISSING GFI RECEPT FOR | | CU. 210.63 | | | | PLEASE BE SURE TO SEE ANY POSSIBLE | | COMMENTS FROM OTHER REVIEWER(S) WHICH | | MAY AFFECT ELECTRICAL PLANS. | | | | PLEASE REMOVE ANY AND ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | STAMPING. | | | | PLEASESUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-01-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-01-20 |
Time |
09:52 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2005-01-20 |
Time |
09:52 |
Sent To |
|
|
Notes |
2005-01-20 00:00:00 | ************** UNSAT *************** | | | | 1)NOTE: PLEASE SEE PLANS AREMISSING | | REQUIRED TITLE BLOCKS WITH ALL REQUIRED | | INFORMATION AS SET-FORTH IN FAC | | 61G15-23.002 AND FS 471.023. | | THIS IS REQUIRED ON ALL PLANS AND FOR | | ALL SHEETS WHEATHER OR NOT COMMENT IS | | MADE BY OTHER REVIEWER(S). | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | PLANS AND CORRELATE WITH SUBMITTED PANEL | | SCHEDULE(S). | | PLEASE ALSO SEE 700.12E FOR CIRCUITING | | OF EM/EXT LTS. | | | | 3)NOTE: PLEASE CORRELATE ALL A/C | | EAUIPMENT AND LOADS ON PANEL, RISER AND | | LOAD CALCULATIONS. | | 215.5 | | | | 4)NOTE: PLEASE SEE 424.3B FOR SIZING OF | | OCP.THE AMPACITY OF THE BRANCH-CIRCUIT | | CONDUCTORS AND THE RATING OR SETTING OF | | OVERCURRENT PROTECTIVE DEVICES SUPPLYING | | FIXED ELECTRIC SPACE-HEATING EQUIPMENT | | CONSISTING OF RESISTANCE ELEMENTS WITH | | OR WITHOUT A MOTOR SHALL NOT BE LESS | | THAN 125 PERCENT OF THE TOTAL LOAD OF | | THE MOTORS AND THE HEATERS. THE RATING | | OR SETTING OF OVERCURRENT PROTECTIVE | | DEVICES SHALL BE PERMITTED IN ACCORDANCE | | WITH 240.4(B). | | | | 5)NOTE: PLEASE VERIFY SIZE OF SEC'S, | | SHOWS 200A MCB PANEL WITH ONE PHASE DOWN | | SIZED? HOW IS THIS CONDUCTOR PROTECTED? | | 240.4 | | PLEASE SEE RISER INDICATES 3-PHASE YET, | | THIS IS NOT SHOWN ON CALCS? | | PLEASE SEE LOAD IS SHOWN AT 216A'S ON A | | 200A PANEL. | | | | | | 6)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | PLEASE SHOW PER | | 220.3,220.10,220.11,220.13 ETC. | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | AT 125% PER 215.3,230.42 | | | | 7)NOTE: PLEASE SEE 422.13 A BRANCH | | CIRCUIT SUPPLYING A FIXED STORAGE-TYPE | | WATER HEATER THAT HAS A CAPACITY OF 450 | | L (120 GAL) OR LESS SHALL HAVE A RATING | | NOT LESS THAN 125 PERCENT OF THE | | NAMEPLATE RATING OF THE WATER HEATER. | | PLEASE SEE MAX OCP IS 150% 422.11E | | IF THE OVERCURRENT PROTECTION RATING IS | | NOT MARKED AND THE APPLIANCE IS RATED | | OVER 13.3 AMPERES, NOT EXCEED 150 | | PERCENT OF THE APPLIANCE RATED CURRENT. | | WHERE 150 PERCENT OF THE APPLIANCE | | RATING DOES NOT CORRESPOND TO A STANDARD | | OVERCURRENT DEVICE AMPERE RATING, THE | | NEXT HIGHER STANDARD RATING SHALL BE | | PERMITTED. | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | OTHER REVIEWER(S) WHICH MAY AFFECT | | ELECTRICAL PLANS. | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | ONLY INSERT NEW REVISED SHEETS INTO TWO | | COMPLETE SETSFOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2005-01-12 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2005-01-12 |
Time |
09:35 |
Rev Time |
0.50 |
Received By |
mamini |
Date |
2005-01-12 |
Time |
09:34 |
Sent To |
|
|
Notes |
2005-01-12 00:00:00 | PASSED WITH PROVISOS: | | | | 1. PARKING AREA PAVEMENT; MIN. OF 12" | | STABILIZATION AND 8" SHELLROCK OR 6" OF | | LIMEROCK COMPACTED PER AASHTO T-180 AND | | MIN. 1-1/4" TYPE II ASPHALT. | | | | 2. POLLUTION PREVENTION PLANS MUST BE | | INSTALLED IN FIELD PRIOR TO BEGINNING | | ANY COSTRUCTION WORK. | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | MOHAMMAD R. AMINI |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2006-02-01 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-02-01 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-02-01 |
Time |
13:28 |
Sent To |
|
|
Notes |
2006-02-01 00:00:00 | ******DENIED****** | | | | 1) PLEASE NOTE THAT THE REVIEW RESPONSES | | INCLUDED WITH THIS SUBMITAL DOES NOT | | ADDRESS ANY PREVIOUS FIRE REVIEW | | COMMENTS. IN ADDITION TO THOSE COMMENTS, | | PLEASE SEE THE FOLLOWING: | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS | | ARE REQUIRED FOR FIRE SPRINKLER AND OR | | FIRE ALARM REMODEL IF APPLICABLE. | | | | 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | REQUIRED AND SHALL BE MOUNTED AT | | DISTANCES NOT TO EXCEED THE 75' TRAVEL | | DISTANCE REQUIREMENT. | | | | 4) PLEASE PROVIDE A CALCULATED OCCUPANT | | LOAD FOR THE FELLOWSHIP HALL. IT WOULD | | APPEAR THAT THE DOORS MARKED EXIT | | LEADING TO THE DINING ROOM SWING AGAINST | | THE DIRECTION OF TRAVEL. WHERE DO | | PERSONS GO ONCE THEY HAVE EXITED THROUGH | | THOSE DOORS? | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLANS REVIEW (561) 805-6722 | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2005-07-28 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2005-07-26 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2005-07-26 |
Time |
15:55 |
Sent To |
|
|
Notes |
2005-07-28 00:00:00 | DENIED | | | | 1) SHALL COMPLY WITH NFPA 101 LIFE | | SAFETY CODE 2003 EDITION CHAPTER 12 NEW | | ASSEMBLY OCCUPANCIES. | | | | 2) WHAT TYPE OF SEATING ARRANGEMENT WILL | | YOU BE USING ? | | | | 3) THE INTERIOR FINISH FOR THE WALLS AND | | CEILING SHALL BE CLASS A, CLASS B, OR | | CLASS C. | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | 561-804-4754 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2005-01-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2005-01-27 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2005-01-27 |
Time |
14:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2005-01-10 |
|
|
Cont ID |
|
Sent By |
ptjomsto |
Date |
2005-01-10 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
ptjomsto |
Date |
2005-01-10 |
Time |
15:54 |
Sent To |
|
|
Notes |
2005-01-10 00:00:00 | HISTORIC APPROVED 1/4/05 BY S PILAND |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2006-10-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-05 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-05 |
Time |
10:00 |
Sent To |
|
|
Notes |
2006-10-19 16:22:43 | TO "COMM" BD#29 | 2006-10-05 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-12-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-12-30 |
Time |
13:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-12-30 |
Time |
13:43 |
Sent To |
|
|
Notes |
2006-01-27 00:00:00 | TO "COMM" BD#23 | 2005-12-30 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-07-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-26 |
Time |
13:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-26 |
Time |
13:47 |
Sent To |
Z |
|
Notes |
2005-07-26 00:00:00 | OFF BD TO ZONING |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-06-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-06-28 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-06-28 |
Time |
10:18 |
Sent To |
|
|
Notes |
2005-07-01 00:00:00 | TO "COMM" BD#24 | 2005-06-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-01-10 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2005-02-01 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2005-01-10 |
Time |
16:32 |
Sent To |
|
|
Notes |
2005-01-10 00:00:00 | TO "COMM BD#25" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2006-02-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2006-02-06 |
Time |
13:01 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2006-02-06 |
Time |
13:01 |
Sent To |
|
|
Notes |
2006-02-06 00:00:00 | PLAN DENIED | | 1- PLEASE REFER TO SECTION 104.2 2001 | | FBC DRAWINGS AND SPECIFICATION.NEED | | SIGNATURE AND ADDRESS OF THE JOB ON | | PLANS. | | 2- PLEASE REFER TO SECTION 602.2.1 | | METERIALS EXPOSED IN PLENUMS. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | 2006-01-31 00:00:00 | NEEDS , NEW SHEETS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2005-01-25 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-01-25 |
Time |
08:19 |
Rev Time |
0.20 |
Received By |
pkrauss |
Date |
2005-01-25 |
Time |
08:01 |
Sent To |
|
|
Notes |
2005-01-25 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR | | REVIEW.PERMIT APPLICATION INDICATES | | MECHANICAL CONTRACTOR TO SUBMIT | | APPLICATION SEPARATELY.PLEASE PROVIDE | | PLANS & EQUIPMENT SCHEDULE WITH | | MECHANICAL PERMIT APPLICATION.FORM | | SUBMITTED FOR THE ENGERGY CALCULATIONS | | IS FOR RESIDENTIAL.THE PROPER FORM FOR | | THE ADDITION IS FORM 600A-01 (PAGE | | 13.189 OF THE 2001 FBC CHAPTER 13). | | | | PLEASE NOTE THE ENERGY CODE COMPLIANCE | | FORM SHALL BE SUBMITTED AND APPROVED | | WITH THE BUILDING PERMIT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2006-02-18 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-02-18 |
Time |
08:16 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-02-18 |
Time |
08:15 |
Sent To |
|
|
Notes |
2006-02-18 00:00:00 | PLUMBING PLAN REVIEW EXAMINER | | PAUL SCHMITZ 561-805-6692 | | [email protected] | | FBC PLUMBING 2004 | | FBC BUILDING 2004, CH 11 | | DENIED THIRD TIME | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 1) SHTS 1 AND 2 PREVIOUS NOTES NOT | | ADDRESSED. | | | | 2) SHT 6 SANITARY RISER DIAGRAM DOES NOT | | REFLECT THE FLOOR PLAN, NOR DOES IT MEET | | CODE REQUIREMENTS. | | | | 3) 11-4.15 DRINKING FOUNTAINS AND WATER | | COOLERS | | ?11-4.15.2 SPOUT HEIGHT. SPOUTS SHALL | | BE NO HIGHER THAN 36 INCHES (915 | | MM), MEASURED FROM THE FLOOR OR GROUND | | SURFACES TO THE SPOUT OUTLET (SEE | | FIGURE 11-27(A)). | | ?11-4.15.4 CONTROLS. CONTROLS SHALL | | COMPLY WITH ?11-4.27.4.UNIT | | CONTROLS SHALL BE FRONT MOUNTED OR | | SIDE MOUNTED NEAR THE FRONT EDGE. | | ?11-4.15.5 CLEARANCES. | | ?11-4.15.5(1) WALL- AND POST-MOUNTED | | CANTILEVERED UNITS SHALL HAVE A | | CLEAR KNEE SPACE BETWEEN THE BOTTOM | | OF THE APRON AND THE FLOOR OR | | GROUND AT LEAST 27 INCHES (685 MM) | | HIGH, 30 INCHES (760 MM) WIDE, AND | | 17 INCHES TO 19 INCHES (430 MM TO | | 485 MM) DEEP (SEE FIGURE 11-27(A) | | AND FIGURE 11-27(B)).SUCH UNITS | | SHALL ALSO HAVE A MINIMUM CLEAR | | FLOOR SPACE 30 INCHES BY 48 INCHES | | (760 MM BY 1220 MM) TO ALLOW A | | PERSON IN A WHEELCHAIR TO APPROACH | | THE UNIT FACING FORWARD. | | | | 4)?11-4.22 TOILET ROOMS. | | ?11-4.22.1 MINIMUM NUMBER. TOILET | | FACILITIES REQUIRED TO BE ACCESSIBLE | | BY ?11-4.1 SHALL COMPLY WITH ?11-4.22. | | ACCESSIBLE TOILET ROOMS SHALL BE | | ON AN ACCESSIBLE ROUTE. | | ?11-4.22.2 DOORS. | | ?11-4.22.2(1) ALL DOORS TO | | ACCESSIBLE TOILET ROOMS SHALL COMPLY | | WITH | | ?11-4.13.DOORS SHALL NOT SWING | | INTO THE CLEAR FLOOR SPACE REQUIRED | | FOR ANY FIXTURE. | | | | EXCEPTION: ALL NEW SINGLE-FAMILY | | HOUSES, DUPLEXES, TRIPLEXES, | | CONDOMINIUMS, AND TOWNHOUSES SHALL | | PROVIDE AT LEAST ONE BATHROOM, | | LOCATED WITH MAXIMUM POSSIBLE | | PRIVACY, WHERE BATHROOMS ARE PROVIDED ON | | HABITABLE GRADE LEVELS, WITH A DOOR THAT | | HAS A 29 INCH CLEAR OPENING. | | HOWEVER, IF ONLY A TOILET ROOM IS | | PROVIDED AT GRADE LEVEL, SUCH TOILET | | ROOM SHALL HAVE A CLEAR OPENING OF | | NOT LESS THAN 29 INCHES. | | | | ?11-4.22.3 CLEAR FLOOR SPACE. THE | | ACCESSIBLE FIXTURES AND CONTROLS | | REQUIRED IN ?11-4.22.4, ?11-4.22.5, | | ?11-4.22.6, AND ?11-4.22.7 SHALL BE | | ON AN ACCESSIBLE ROUTE.AN | | UNOBSTRUCTED TURNING SPACE COMPLYING | | WITH 11- | | 4.2.3 SHALL BE PROVIDED WITHIN AN | | ACCESSIBLE TOILET ROOM.THE CLEAR FLOOR | | SPACE AT FIXTURES AND CONTROLS, THE | | ACCESSIBLE ROUTE, AND THE TURNING | | SPACE MAY OVERLAP. | | | | ?11-4.22.4 WATER CLOSETS. IF TOILET | | STALLS ARE PROVIDED, THEN AT LEAST | | ONE SHALL BE A STANDARD TOILET STALL | | COMPLYING WITH ?11-4.17; WHERE 6 OR | | MORE STALLS ARE PROVIDED, IN ADDITION | | TO THE STALL COMPLYING WITH | | ?11-4.17.3, AT LEAST ONE STALL 36 IN | | (915 MM) WIDE WITH AN OUTWARD | | SWINGING, SELF-CLOSING DOOR AND | | PARALLEL GRAB BARS COMPLYING WITH | | FIGURE 11-30(D) AND ?11-4.26 SHALL BE | | PROVIDED.WATER CLOSETS IN | | SUCH STALLS SHALL COMPLY WITH | | ?11-4.16.IF WATER CLOSETS ARE NOT IN | | STALLS, THEN AT LEAST ONE SHALL COMPLY | | WITH ?11-4.16. | | ?11-4.22.6 LAVATORIES AND MIRRORS. IF | | LAVATORIES AND MIRRORS ARE | | PROVIDED, THEN AT LEAST ONE OF EACH | | SHALL COMPLY WITH ?11-4.19. | | ?11-4.22.7 CONTROLS AND DISPENSERS. IF | | CONTROLS, DISPENSERS, | | RECEPTACLES, OR OTHER EQUIPMENT ARE | | PROVIDED, THEN AT LEAST ONE OF EACH | | SHALL BE ON AN ACCESSIBLE ROUTE AND | | SHALL COMPLY WITH ?11-4.27. | | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2005-07-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-07-22 |
Time |
08:34 |
Rev Time |
1.13 |
Received By |
kstevens |
Date |
2005-07-22 |
Time |
08:34 |
Sent To |
|
|
Notes |
2005-07-22 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUBMING | | FBC-2001 BUILDING | | | | A. THE PLANS HAVE BEEN CHANGED AND DO | | NOT SHOW ANY FACILITIES REQUIRED BY | | TABLE 403.1. NO RESPONSE TO FIRST REVIEW | | COMMENTS. | | 1. FELLOWSHIP HALL INDICATES 1,381SF | | BEING ADDED TO EXISTING CHURCH AREA. | | THIS WILL BE AN ASSEMBLY OCCUPANCY AND | | AS SUCH WILL ADD 198 MORE OCCUPANTS TO | | THE OCCUPANCY LOAD OF THE EXISTING | | STRUCTURES. TABLE 1003.1 | | 2. PER TABLE 403.1, 1 W/C FOR MEN AND 2 | | W/C'S FOR WOMEN, 1 LAV FOR MEN, 2 LAVS | | FOR WOMEN, A DRINKING FOUNTAIN AND A | | SERVICE SINK ARE REQUIRED. | | 3. SUBMIT A SANITARY AND A WATER RISER | | DIAGRAM IN ISOMETRIC FORM FOR REVIEW. | | SECTION 104.3.1.1. SHOW ALL PIPE SIZES, | | VENTS ECT FOR SANT., AND ALL PIPE SIZES, | | VALVES, RPZ BACKFLOW, WATER HAMMER | | ARRESTORS, (WHERE REQUIRED BY SECTION | | 604.9 LOCATED NEAR THE FIXTURE PER | | PDI-WH 201) AND POINT OF CONNECTION TO | | THE WATER SUPPLY. | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2005-02-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-02-01 |
Time |
08:46 |
Rev Time |
1.26 |
Received By |
kstevens |
Date |
2005-02-01 |
Time |
08:46 |
Sent To |
|
|
Notes |
2005-02-01 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) SUBMIT DETAILS FOR TOILET ROOMS | | SHOWING COMPLIANCE WITH SECTION 11-4.16, | | 11-4.18, 11-4.19, 11-22, 11-4.1.3(11) | | ADAPTABLE TOILET ROOM FOR PRIVATE | | OFFICE. | | 2) SHT 6 SANITARY RISER DIAGRAM DOES NOT | | REFLECT THE FLOOR PLAN, NOR DOES IS MEET | | CODE REQUIREMENTS. | | A) WOMENS TOILET ROOM BY KITCHEN, TRAP | | FOR W/C NOT APPROVED. W/C HAS INTEGRAL | | TRAP IN FIXTURE. SECTION 1002.1 | | B) MENS TOILET URINAL SHOWS TRAP UNDER | | THE SLAB. IF THE URINAL IS A WALL HUNG | | URINAL, IT SHALL BE ON A STACK AND | | VENTED. | | C) BRANCH DRAIN TO FIRST TOILET ROOMS | | INDICATES A CONNECTION TO THE BOTTOM OF | | THE BLDG. DRAIN. PLEASE CLARIFY. SECTION | | 104.2.1. | | D) BAPISTRY REQUIRES A TRAP. SECTION | | 1002.1. | | E) MENS TOILET ROOM BY SANTURARY SHOWS | | TWO W/C'S, BUT FLOOR PLAN SHOW 1 W/C AND | | 1 URINAL. | | (SEE ATTACHED FOR SANITARY RISER DIAGRAM | | THAT MEETS CODE AND REFLECTS THE FLOOR | | PLAN) | | 3) SUBMIT A WATER RISER DIAGRAM SHOWING | | ALL PIPE SIZES, WATER HAMMER ARRESTORS | | WHERE REQUIRED, VALVES ECT. SECTION | | 104.3.1.1. | | 4) ENGINEERS SHALL LEGIBLY INDICATE | | THEIR NAME, ADDRESS, AND LICENSE NUMBER | | ON EACH SHEET. IF PRACTICING THROUGH A | | DULY AUTHORIZED ENGINEERING BUSINESS, | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | NAME AND LICENSE NUMBER, AS WELL AS, THE | | NAME ADDRESS, AND CERTIFICATE OF | | AUTHORIZATION NUMBER OF THE ENGINEERING | | BUSINESS ON EACH SHEET. FAC | | 61G15-23.002(2) & FS 471.025. | | 5) AN RPZ BACKFLOW IS REQUIRED ON THE | | WATER SERVICE. SECTION 608.13.2 | | 6) WATER HEATER REQUIRES THERMAL | | EXPANSION CONTROL PER SECTION 607.3.2. | | 7) PLANS INDICATE A KITCHEN AND DINING | | AREA. PLEASE INDICATE ON PLANS IF THIS | | IS FOR MEMBERS OR WILL THE PUBLIC BE | | SERVED. | | 8) PER TABLE 403.1 A DRINKING FOUNTAIN | | AND A SERVICE SINK ARE REQUIRED. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2005-08-05 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2005-08-05 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2005-07-27 |
Time |
08:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2005-02-07 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2005-02-07 |
Time |
16:37 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2005-02-07 |
Time |
16:37 |
Sent To |
|
|
Notes |
2005-02-07 00:00:00 | 1. THE SITE PLAN HAS TO BE MODIFIED TO | | COMPLY WITH CHANGES RECOMMENDED BY DAC | | APPROVAL ON ITS OCTOBER 13, 2004 | | MEETING. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |