Plan Review Details - Permit 05010378
Plan Review Stops For Permit 05010378
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-02-08 Cont ID  
Sent By lursu Date 2006-02-08 Time 13:18 Rev Time 0.00
Received By lursu Date 2006-02-08 Time 13:17 Sent To  
Notes
2006-02-08 00:00:00UNITY OF TITLE ,NEW PCN =
 74434321060230120 HAS THE SAME ADDRESS:
 909 3RD ST .

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-07 Cont ID  
Sent By jwitmer Date 2006-02-07 Time 14:43 Rev Time 2.22
Received By jwitmer Date 2006-02-07 Time 14:16 Sent To  
Notes
2006-02-07 00:00:00ADD: 909 3RD ST
 CONT: NEWBOLD CONSTRUCTION
 TEL: (561)644-5764
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 THE NOC FILED WILL HAVE THE WRONG
 PROPERTY CONTROL NUMBER ONCE THE UNITY
 OF TITLE OCCURS.WILL HAVE TO BE REFILED.
 THE UNITITY OF TITLE WILL MAKE LOT # 12
 THE PCN TO USE TO IDENTIFY THE PROPERTY.
  
 ALSO CORRECT THE PCN ON THE PERMIT
 APPLICATION TO LOT 12.
 74-43-43-21-06-023-0120
  
  
  
 2) OK!
  
 3OK!
 4) OK!
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS OK
 B) ROOFING ASSEMBLIES NO
 C) TRACO WINDOWS DADE COUTY REPORT
 SUBMITTED SHOULD BE AAMA CERTIFICATION
 PROGRAM. NO
 D) STORM SHUTTERS REPORT SUBMITTED IS A
 SBCCI REPORT SUBMITTED TO STATE IS A
 MIAMI/ DADE REPORT CORRECT.NO
  
 7) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. NO, SAMPLE FORM ATTACHED
  
 8) SHEET 5 NOW IS MISSING? ASSUMING
 SHEET # 5 WAS FOR THE STEPPLE.
  
 9) IS THE STEEPLE PART OF THIS PERMIT?
 ASSUMING SHEET # 5 WAS FOR THE STEEPLE!
  
 10) SHEET 2 THE DINING ROOM INTO THE
 FELLOWSHIP HALL.FROM THE EXISTING ROOM
 CONNECTING WITH THE PROPOSED FELLOWSHIP
 HALL ONLY HAS ONE EXIT INTO THE NEW
 FELLOWSHIP HALL, 2 EXITS ARE REQUIRED
 FOR ROOMS WITH OCCUPANT LOADS GREATER
 THAN 50.
 TABLE 1003.1 ASSEMBLY WITHOUT FIXED
 SEATING OCC LOAD TO BE 7 SQ FT / NET THE
 OCC LOAD OF THE EXISTING DINING ROOM
 WOULD BE 98 REQUIRING 2 EXITS.
 1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
  
 EXIT SIGNS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLE ILLUMINATED BY A
 RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE
 VISIBLE IN BOTH THE NORMAL & EMERGENCY
 LIGHTING.MISSING IN EXISTING FELLOWSHIP
 HALL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-24 Cont ID  
Sent By jwitmer Date 2005-07-24 Time 15:59 Rev Time 1.55
Received By jwitmer Date 2005-07-24 Time 15:47 Sent To  
Notes
2005-07-24 00:00:00PERMIT: 05010378
 ADD: 909 3RD ST
 CONT: NEWBOLD CONSTRUCTION
 TEL: (561)644-5764
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 THE NOC FILED WILL HAVE THE WRONG
 PROPERTY CONTROL NUMBER ONCE THE UNITY
 OF TITLE OCCURS.WILL HAVE TO BE REFILED.
  
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.SEE ATTACHMENTS. UNITY OF
 TITLE FORMS ARE FOUND ON THE 5TH FLOOR
 ZONING DEPARTMENT.
  
 3 PROVIDE WHAT SLOPE THE CRICKET WILL
 HAVE? WILL IT ALSO HAVE SHINGLES ON
 ROOF?
  
 4) PROVIDE THE POSITIVE AND NEGATIVE
 PRESSUESFOR OPENINGS ON ELEVATIONS,
 ENCLUDE ENDZONES.
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) ROOFING ASSEMBLIES
 C) TRACO WINDOWS DADE COUTY REPORT
 SUBMITTED SHOULD BE AAMA CERTIFICATION
 PROGRAM.
 D) STORM SHUTTERS REPORT SUBMITTED IS A
 SBCCI REPORT SUBMITTED TO STATE IS A
 MIAMI/ DADE REPORT CORRECT.
  
 7) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 8) SHEET 5 NOW IS MISSING?
  
 9) IS THE STEEPLE PART OF THIS PERMIT?
  
 10) SHEET 2 MISSING THE EXITFROM THE
 DINING ROOM INTO THE FELLOWSHIP HALL.
 FROM THE EXISTING ROOM CONNECTING WITH
 THE PROPOSED FELLOWSHIP HALL ONLY HAS
 ONE EXIT INTO THE NEW FELLOWSHIP HALL,
 2 EXITS ARE REQUIRED FOR ROOMS WITH
 OCCUPANT LOADS GREATER THAN 50.
 1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
  
 EXIT SIGNS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLE ILLUMINATED BY A
 RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE
 VISIBLE IN BOTH THE NORMAL & EMERGENCY
 LIGHTING.MISSING IN EXISTING FELLOWSHIP
 HALL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By jwitmer Date 2005-01-24 Time 12:16 Rev Time 3.33
Received By jwitmer Date 2005-01-24 Time 11:01 Sent To  
Notes
2005-01-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010378
 ADD: 909 3RD ST
 CONT: NEWBOLD CONSTRUCTION
 TEL: (561)644-5764
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 3) 3401.7.1.1.2 WHEN THE ADDITION IS
 OVER 25% OF THETHE EXISTING BUILDING
 AREA AND NOT SEPERATED BY A FIRE WALL,
 THE EXISTING BUILDING AND THE ADDITION
 SHALL BE MADE TO COMPLY WITH ALL THE
 REQUIREMENTS OF THIS CODE FOR A BUILDING
 OF AREA EQUAL TO THE COMBINED AREA OF
 THE ADDITION AND EXISTING BUILDING.
 EXCEP: EXISTING BUILDINGS SHALL NOT BE
 REQUIRED TO BE UPGRADED TO THE
 STRUCTURAL REQUIREMENTS OF THE CODE IN
 EFFECT ON THE DATE OF THE PERMIT FOR THE
 ADDTION.
 4) PROVIDE THE CORRECT ENERGY FORMS, THE
 FORM SUBMITTED IS FOR RESIDENTIAL USE.
  
 5) DESIGN STANARDS TO BE REVISED AND
 UPDATED:
 2001 FLORIDA BUILDING CODE W/ 2003
 REVISIONS
 CONCRETE ACI 318-02
 MASONARY ACI 530/ ASCE 5 TMS402-02
  
 6) GABLE ENDWALL PLANS INDICATE THE USE
 OF A GABLE BEAM BUT NO MENTION OF THE
 BEAM AT THE EAVE HEIGHT NOR USE OF
 LENTALS? WHAT WILL HAPPEN OVER THE DOOR
 AND WINDOW OPENINGS?
  
 7) NO INFORMATION FOR WINDOW AND DOOR
 SIZES?
  
 8) PROVIDE WHAT SLOPE THE NEW ADDITION
 ROOF WILL BE?
  
 9) PROVIDE THE POSITIVE AND NEGATIVE
 PRESSUESFOR OPENINGS ON ELEVATIONS,
 ENCLUDE ENDZONES.
  
 10) FRONT ELEVATION OF THE FELLOWSHIP
 HALL MISSING THE 16" BEAM ON THE
 ELEVATION?
  
 11)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 12)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) ROOFING ASSEMBLIES
  
 13) WINDOW BUCK DETAIL INDICATES THE
 USE OF A 1X2 BUCK WINDOW FRAME IS A
 2.25" WIDE. 1707.4.4.2 TAPERED
 BUCKS: SHALL EXTEND BEYOND THE INTERIOR
 FACE OF THE WINDOW OR DOOR FRAME SUCH
 THAT FULL SUPPORT OF THE FRAME IS
 SUPPORTED.
  
 14) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15) SHEET 5 INDICATES THE USE OF A 90LB
 FELT FOR DRY IN??
  
 16) IS THE STEEPLE PART OF THIS PERMIT?
  
 17) SHEET 2 MISSING THE EXITFROM THE
 DINING ROOM INTO THE FELLOWSHIP HALL.
 1016.3.1. EXIT SIGNS:
 EXIT SIGNS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLE ILLUMINATED BY A
 RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE
 VISIBLE IN BOTH THE NORMAL & EMERGENCY
 LIGHTING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-10-26 Cont ID  
Sent By dpalmer Date 2006-10-26 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2006-10-25 Time 12:33 Sent To PC
Notes
2006-10-26 12:46:51NO REVIEW DONE, PROJECT EXPIRED SEE FRONT SCREEN.
2006-10-25 17:13:31PROJECT ONHOLD.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-01-31 Cont ID  
Sent By dpalmer Date 2006-01-31 Time 20:31 Rev Time 0.00
Received By dpalmer Date 2006-01-31 Time 19:34 Sent To  
Notes
2006-01-31 00:00:00************ UNSAT 3RD REVIEW *********
  
 PLEASE SEE MANY NOTES FROM REVIEWS ONE
 AND TWO STILL NEED TO BE ADDRESSED.
  
 1)NOTE:PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL
 SCHEDULE(S).
 PLEASE SEE THERE ARE A FEW ITEMS ON
 PLANS WHICH STILL DO NOT SHOW THE
 CIRCUITING.
 PLEASE ALSO SEE NEW WATER FOUNTAIN HAS
 BEEN ADDED TO PLANS , HOWEVER PLANS DO
 NOT INDICATE ANY ELECTRICAL RECEPT FOR
 THIS UNIT.
  
 2) PLEASE SEE 700.12E FOR EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 215.5
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE LOAD CALCULATIONS SUBMITTED
 ARE ONLY LOAD ON SUB PANEL.
 PLEASE SHOW LOAD CALCUALTIONS FOR
 SERVICE AS REQUESTED ON PREVIOUS
 REVIEWS. PLEASE ALSO
 SEE LOAD CALCULATIONS ARE FOR
 RESIDENTIAL USE.
  
 4)NOTE: PLEASE SEE NEW MAIN DISCONNECT
 PANELS APPEARS TO BE SHOWN, HOWEVER NO
 INFORMATION IS PROVIDED FOR THIS.
 AIC RATING, VOLTAGE, AMPERAGE, GROUPING
 ETC
 215.5,110.9,110.14,230.72 ETC
 PLEASE SHOW PANELS, SERVICE LOCATION ON
 PLANS.
 PLEASE INDICATE CONDUCTORS FROM METER TO
 MAIN AND MAIN TO NEW SUB PANEL.
 215.5,240.4,310.16,250.24,250.6 ETC.
 ** PLEASE KNOW, SINCE LOAD CALCUALTIONS
 HAVE STILL NOT BEEN SUBMITTED FOR
 SERVICE, REVIEW FOR EXISTING SERVICE ENT CONDUCTORS CAN
 NOT BE VERIFIED AT THIS
 TIME.
 ** PLEASE SEE AHU IS NOW BEING SHOWN AT
 125%, HOWEVR THIS IS NOT REQUIRED.
 PLEASE SEE 424.3B ONLY REQUIRES THE OCP
 TO BE SIZED AT 125%.
  
 5)NOTE: PLEASE SEE FLORIDA STATUES
 481.221 WHICH REQUIRES TO THE ARCHITECT
 TO ALSO DATE PLANS WHEN SIGNING AND
 SEALING SAID PLANS.
  
 6)NOTE: PLEASE SEE RISER NOW SHOWS NEW
 PANELS WHICH INDICATE THESE ARE FOR
 ADDITION??
 PLEASE VEIRFY IF THESE ARE EXISITNG, NEW
 ETC.
 PLEASE KNOW, THERE IS NOT ENOUGH
 INFORMATION FOR THESE PANELS AS THEY DO
 NOT APPEAR TO BE SHOWN ON PLANS.
 215.5
  
 7)NOTE: PLEASE SEE FLORIDA STATUES
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND PLANS WITH REPEAT
 COMMENTS THREE OR MORE TIME FOR THE SAME
 CODE COMPLIANCE COMMENT(S).
 PLEASE KNOW, AS REQUIRED PER ABOVE FS, A
 4X FEE FOR THE PLAN REVIEW PORTION OF
 THE PERMIT FEE SHALL BE ACCESSED TO THE
 "DESIGN PROFESSIONAL" FOR SAID
 VIOLATION.
 PLEASE SEE THE FEE OF $1,764.00 IS NOW
 ACCESSED AND IS REQUIRED PER FS
 553.80(2)(B) TO BE PAID BEFORE
 RE-SUBMITTING PLANS.
 ** PLEASE KNOW, ONE COPY OF EACH OF THE
 ELECTRICAL PLANS SUBMITTED ARE NOW BEING
 RETAINED FOR FILE AND POSSIBLE REVIEW BY
 THE STATE BOARD OF ARCHITECTS AND STATE
 OF FLORIDA'S LEGAL COUNSEL.
 ** PLEASE KNOW, IT IS STRONGLY SUGGESTED
 A MEETING BE HELD ONCE ALL REVIEWS ARE
 COMPLETED BEFORE RESUBMITTING PLANS FOR
 NEXT REVIEWTO GO OVER ANY COMMENTS OR
 QUESTIONS.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETED SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHALL
 BE SUBMITTED FOR REFERENCE.
 PLEASE SEE THE ABOVE WAS REQUESTED ON
 PREVIOUS REVIEW, HOWEVER ALL OLD/VOIDED
 SHEETS WERE LEFT IN SETS.
  
  
 PLEASESUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 18:12 Rev Time 0.75
Received By dpalmer Date 2005-07-06 Time 18:12 Sent To  
Notes
2005-07-06 00:00:00************ UNSAT2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL
 SCHEDULE(S). PLEASE SEE 700.12E FOR
 EM/EXT LTS.
 215.5
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE LOAD CALCULATIONS SUBMITTED
 ARE ONLY LOAD ON SUB PANEL. PLEASE ALSO
 SEE LOAD CALCULATIONS ARE FOR
 RESIDENTIAL USE.
  
 2)NOTE: PLEASE SEE NEW MAIN DISCONNECT
 APPEARS TO BE SHOWN, HOWEVER NO
 INFORMATION IS PROVIDED FOR THIS.
 AIC RATING, VOLTAGE, AMPERAGE, GROUPING
 ETC
 215.5,110.9,110.14,230.72 ETC
 PLEASE INDICATE CONDUCTORS FROM METER TO
 MAIN AND MAIN TO NEW SUB PANEL.
 215.5,240.4,310.16,250.24,250.6 ETC.
  
 3)NOTE: PLEASE SHOW LOCATION OF COND
 UNIT AND DISC'S REQUIRED FOR A/C CU AND
 AHU. 440.11
 PLEASE ALSO SEE MISSING GFI RECEPT FOR
 CU. 210.63
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY AND ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASESUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-20 Cont ID  
Sent By dpalmer Date 2005-01-20 Time 09:52 Rev Time 1.00
Received By dpalmer Date 2005-01-20 Time 09:52 Sent To  
Notes
2005-01-20 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS AREMISSING
 REQUIRED TITLE BLOCKS WITH ALL REQUIRED
 INFORMATION AS SET-FORTH IN FAC
 61G15-23.002 AND FS 471.023.
 THIS IS REQUIRED ON ALL PLANS AND FOR
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE(S).
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS.
  
 3)NOTE: PLEASE CORRELATE ALL A/C
 EAUIPMENT AND LOADS ON PANEL, RISER AND
 LOAD CALCULATIONS.
 215.5
  
 4)NOTE: PLEASE SEE 424.3B FOR SIZING OF
 OCP.THE AMPACITY OF THE BRANCH-CIRCUIT
 CONDUCTORS AND THE RATING OR SETTING OF
 OVERCURRENT PROTECTIVE DEVICES SUPPLYING
 FIXED ELECTRIC SPACE-HEATING EQUIPMENT
 CONSISTING OF RESISTANCE ELEMENTS WITH
 OR WITHOUT A MOTOR SHALL NOT BE LESS
 THAN 125 PERCENT OF THE TOTAL LOAD OF
 THE MOTORS AND THE HEATERS. THE RATING
 OR SETTING OF OVERCURRENT PROTECTIVE
 DEVICES SHALL BE PERMITTED IN ACCORDANCE
 WITH 240.4(B).
  
 5)NOTE: PLEASE VERIFY SIZE OF SEC'S,
 SHOWS 200A MCB PANEL WITH ONE PHASE DOWN
 SIZED? HOW IS THIS CONDUCTOR PROTECTED?
 240.4
 PLEASE SEE RISER INDICATES 3-PHASE YET,
 THIS IS NOT SHOWN ON CALCS?
 PLEASE SEE LOAD IS SHOWN AT 216A'S ON A
 200A PANEL.
  
  
 6)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 7)NOTE: PLEASE SEE 422.13 A BRANCH
 CIRCUIT SUPPLYING A FIXED STORAGE-TYPE
 WATER HEATER THAT HAS A CAPACITY OF 450
 L (120 GAL) OR LESS SHALL HAVE A RATING
 NOT LESS THAN 125 PERCENT OF THE
 NAMEPLATE RATING OF THE WATER HEATER.
 PLEASE SEE MAX OCP IS 150% 422.11E
 IF THE OVERCURRENT PROTECTION RATING IS
 NOT MARKED AND THE APPLIANCE IS RATED
 OVER 13.3 AMPERES, NOT EXCEED 150
 PERCENT OF THE APPLIANCE RATED CURRENT.
 WHERE 150 PERCENT OF THE APPLIANCE
 RATING DOES NOT CORRESPOND TO A STANDARD
 OVERCURRENT DEVICE AMPERE RATING, THE
 NEXT HIGHER STANDARD RATING SHALL BE
 PERMITTED.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETSFOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-01-12 Cont ID  
Sent By mamini Date 2005-01-12 Time 09:35 Rev Time 0.50
Received By mamini Date 2005-01-12 Time 09:34 Sent To  
Notes
2005-01-12 00:00:00PASSED WITH PROVISOS:
  
 1. PARKING AREA PAVEMENT; MIN. OF 12"
 STABILIZATION AND 8" SHELLROCK OR 6" OF
 LIMEROCK COMPACTED PER AASHTO T-180 AND
 MIN. 1-1/4" TYPE II ASPHALT.
  
 2. POLLUTION PREVENTION PLANS MUST BE
 INSTALLED IN FIELD PRIOR TO BEGINNING
 ANY COSTRUCTION WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-02-01 Cont ID  
Sent By mwennerg Date 2006-02-01 Time 13:28 Rev Time 0.00
Received By mwennerg Date 2006-02-01 Time 13:28 Sent To  
Notes
2006-02-01 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT THE REVIEW RESPONSES
 INCLUDED WITH THIS SUBMITAL DOES NOT
 ADDRESS ANY PREVIOUS FIRE REVIEW
 COMMENTS. IN ADDITION TO THOSE COMMENTS,
 PLEASE SEE THE FOLLOWING:
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND OR
 FIRE ALARM REMODEL IF APPLICABLE.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND SHALL BE MOUNTED AT
 DISTANCES NOT TO EXCEED THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 4) PLEASE PROVIDE A CALCULATED OCCUPANT
 LOAD FOR THE FELLOWSHIP HALL. IT WOULD
 APPEAR THAT THE DOORS MARKED EXIT
 LEADING TO THE DINING ROOM SWING AGAINST
 THE DIRECTION OF TRAVEL. WHERE DO
 PERSONS GO ONCE THEY HAVE EXITED THROUGH
 THOSE DOORS?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-07-28 Cont ID  
Sent By nmccray Date 2005-07-26 Time 15:55 Rev Time 0.00
Received By nmccray Date 2005-07-26 Time 15:55 Sent To  
Notes
2005-07-28 00:00:00DENIED
  
 1) SHALL COMPLY WITH NFPA 101 LIFE
 SAFETY CODE 2003 EDITION CHAPTER 12 NEW
 ASSEMBLY OCCUPANCIES.
  
 2) WHAT TYPE OF SEATING ARRANGEMENT WILL
 YOU BE USING ?
  
 3) THE INTERIOR FINISH FOR THE WALLS AND
 CEILING SHALL BE CLASS A, CLASS B, OR
 CLASS C.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-27 Cont ID  
Sent By mcarsill Date 2005-01-27 Time 14:26 Rev Time 0.00
Received By mcarsill Date 2005-01-27 Time 14:26 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By ptjomsto Date 2005-01-10 Time 15:54 Rev Time 0.00
Received By ptjomsto Date 2005-01-10 Time 15:54 Sent To  
Notes
2005-01-10 00:00:00HISTORIC APPROVED 1/4/05 BY S PILAND

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-05 Cont ID  
Sent By adarroug Date 2006-10-05 Time 10:00 Rev Time 0.00
Received By adarroug Date 2006-10-05 Time 10:00 Sent To  
Notes
2006-10-19 16:22:43TO "COMM" BD#29
2006-10-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-30 Cont ID  
Sent By adarroug Date 2005-12-30 Time 13:43 Rev Time 0.00
Received By adarroug Date 2005-12-30 Time 13:43 Sent To  
Notes
2006-01-27 00:00:00TO "COMM" BD#23
2005-12-30 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-26 Cont ID  
Sent By adarroug Date 2005-07-26 Time 13:47 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 13:47 Sent To Z
Notes
2005-07-26 00:00:00OFF BD TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-28 Cont ID  
Sent By adarroug Date 2005-06-28 Time 10:19 Rev Time 0.00
Received By adarroug Date 2005-06-28 Time 10:18 Sent To  
Notes
2005-07-01 00:00:00TO "COMM" BD#24
2005-06-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-10 Cont ID  
Sent By mjacobs Date 2005-02-01 Time 08:47 Rev Time 0.00
Received By kstevens Date 2005-01-10 Time 16:32 Sent To  
Notes
2005-01-10 00:00:00TO "COMM BD#25"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-02-06 Cont ID  
Sent By hmoser Date 2006-02-06 Time 13:01 Rev Time 0.00
Received By hmoser Date 2006-02-06 Time 13:01 Sent To  
Notes
2006-02-06 00:00:00PLAN DENIED
 1- PLEASE REFER TO SECTION 104.2 2001
 FBC DRAWINGS AND SPECIFICATION.NEED
 SIGNATURE AND ADDRESS OF THE JOB ON
 PLANS.
 2- PLEASE REFER TO SECTION 602.2.1
 METERIALS EXPOSED IN PLENUMS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
2006-01-31 00:00:00NEEDS , NEW SHEETS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-25 Cont ID  
Sent By pkrauss Date 2005-01-25 Time 08:19 Rev Time 0.20
Received By pkrauss Date 2005-01-25 Time 08:01 Sent To  
Notes
2005-01-25 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PERMIT APPLICATION INDICATES
 MECHANICAL CONTRACTOR TO SUBMIT
 APPLICATION SEPARATELY.PLEASE PROVIDE
 PLANS & EQUIPMENT SCHEDULE WITH
 MECHANICAL PERMIT APPLICATION.FORM
 SUBMITTED FOR THE ENGERGY CALCULATIONS
 IS FOR RESIDENTIAL.THE PROPER FORM FOR
 THE ADDITION IS FORM 600A-01 (PAGE
 13.189 OF THE 2001 FBC CHAPTER 13).
  
 PLEASE NOTE THE ENERGY CODE COMPLIANCE
 FORM SHALL BE SUBMITTED AND APPROVED
 WITH THE BUILDING PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-02-18 Cont ID  
Sent By pschmitz Date 2006-02-18 Time 08:16 Rev Time 0.00
Received By pschmitz Date 2006-02-18 Time 08:15 Sent To  
Notes
2006-02-18 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC BUILDING 2004, CH 11
 DENIED THIRD TIME
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) SHTS 1 AND 2 PREVIOUS NOTES NOT
 ADDRESSED.
  
 2) SHT 6 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS.
  
 3) 11-4.15 DRINKING FOUNTAINS AND WATER
 COOLERS
 ?11-4.15.2 SPOUT HEIGHT. SPOUTS SHALL
 BE NO HIGHER THAN 36 INCHES (915
 MM), MEASURED FROM THE FLOOR OR GROUND
 SURFACES TO THE SPOUT OUTLET (SEE
 FIGURE 11-27(A)).
 ?11-4.15.4 CONTROLS. CONTROLS SHALL
 COMPLY WITH ?11-4.27.4.UNIT
 CONTROLS SHALL BE FRONT MOUNTED OR
 SIDE MOUNTED NEAR THE FRONT EDGE.
 ?11-4.15.5 CLEARANCES.
 ?11-4.15.5(1) WALL- AND POST-MOUNTED
 CANTILEVERED UNITS SHALL HAVE A
 CLEAR KNEE SPACE BETWEEN THE BOTTOM
 OF THE APRON AND THE FLOOR OR
 GROUND AT LEAST 27 INCHES (685 MM)
 HIGH, 30 INCHES (760 MM) WIDE, AND
 17 INCHES TO 19 INCHES (430 MM TO
 485 MM) DEEP (SEE FIGURE 11-27(A)
 AND FIGURE 11-27(B)).SUCH UNITS
 SHALL ALSO HAVE A MINIMUM CLEAR
 FLOOR SPACE 30 INCHES BY 48 INCHES
 (760 MM BY 1220 MM) TO ALLOW A
 PERSON IN A WHEELCHAIR TO APPROACH
 THE UNIT FACING FORWARD.
  
 4)?11-4.22 TOILET ROOMS.
 ?11-4.22.1 MINIMUM NUMBER. TOILET
 FACILITIES REQUIRED TO BE ACCESSIBLE
 BY ?11-4.1 SHALL COMPLY WITH ?11-4.22.
 ACCESSIBLE TOILET ROOMS SHALL BE
 ON AN ACCESSIBLE ROUTE.
 ?11-4.22.2 DOORS.
 ?11-4.22.2(1) ALL DOORS TO
 ACCESSIBLE TOILET ROOMS SHALL COMPLY
 WITH
 ?11-4.13.DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED
 FOR ANY FIXTURE.
  
 EXCEPTION: ALL NEW SINGLE-FAMILY
 HOUSES, DUPLEXES, TRIPLEXES,
 CONDOMINIUMS, AND TOWNHOUSES SHALL
 PROVIDE AT LEAST ONE BATHROOM,
 LOCATED WITH MAXIMUM POSSIBLE
 PRIVACY, WHERE BATHROOMS ARE PROVIDED ON
 HABITABLE GRADE LEVELS, WITH A DOOR THAT
 HAS A 29 INCH CLEAR OPENING.
 HOWEVER, IF ONLY A TOILET ROOM IS
 PROVIDED AT GRADE LEVEL, SUCH TOILET
 ROOM SHALL HAVE A CLEAR OPENING OF
 NOT LESS THAN 29 INCHES.
  
 ?11-4.22.3 CLEAR FLOOR SPACE. THE
 ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN ?11-4.22.4, ?11-4.22.5,
 ?11-4.22.6, AND ?11-4.22.7 SHALL BE
 ON AN ACCESSIBLE ROUTE.AN
 UNOBSTRUCTED TURNING SPACE COMPLYING
 WITH 11-
 4.2.3 SHALL BE PROVIDED WITHIN AN
 ACCESSIBLE TOILET ROOM.THE CLEAR FLOOR
 SPACE AT FIXTURES AND CONTROLS, THE
 ACCESSIBLE ROUTE, AND THE TURNING
 SPACE MAY OVERLAP.
  
 ?11-4.22.4 WATER CLOSETS. IF TOILET
 STALLS ARE PROVIDED, THEN AT LEAST
 ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH ?11-4.17; WHERE 6 OR
 MORE STALLS ARE PROVIDED, IN ADDITION
 TO THE STALL COMPLYING WITH
 ?11-4.17.3, AT LEAST ONE STALL 36 IN
 (915 MM) WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND
 PARALLEL GRAB BARS COMPLYING WITH
 FIGURE 11-30(D) AND ?11-4.26 SHALL BE
 PROVIDED.WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH
 ?11-4.16.IF WATER CLOSETS ARE NOT IN
 STALLS, THEN AT LEAST ONE SHALL COMPLY
 WITH ?11-4.16.
 ?11-4.22.6 LAVATORIES AND MIRRORS. IF
 LAVATORIES AND MIRRORS ARE
 PROVIDED, THEN AT LEAST ONE OF EACH
 SHALL COMPLY WITH ?11-4.19.
 ?11-4.22.7 CONTROLS AND DISPENSERS. IF
 CONTROLS, DISPENSERS,
 RECEPTACLES, OR OTHER EQUIPMENT ARE
 PROVIDED, THEN AT LEAST ONE OF EACH
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL COMPLY WITH ?11-4.27.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-07-22 Cont ID  
Sent By kstevens Date 2005-07-22 Time 08:34 Rev Time 1.13
Received By kstevens Date 2005-07-22 Time 08:34 Sent To  
Notes
2005-07-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUBMING
 FBC-2001 BUILDING
  
 A. THE PLANS HAVE BEEN CHANGED AND DO
 NOT SHOW ANY FACILITIES REQUIRED BY
 TABLE 403.1. NO RESPONSE TO FIRST REVIEW
 COMMENTS.
 1. FELLOWSHIP HALL INDICATES 1,381SF
 BEING ADDED TO EXISTING CHURCH AREA.
 THIS WILL BE AN ASSEMBLY OCCUPANCY AND
 AS SUCH WILL ADD 198 MORE OCCUPANTS TO
 THE OCCUPANCY LOAD OF THE EXISTING
 STRUCTURES. TABLE 1003.1
 2. PER TABLE 403.1, 1 W/C FOR MEN AND 2
 W/C'S FOR WOMEN, 1 LAV FOR MEN, 2 LAVS
 FOR WOMEN, A DRINKING FOUNTAIN AND A
 SERVICE SINK ARE REQUIRED.
 3. SUBMIT A SANITARY AND A WATER RISER
 DIAGRAM IN ISOMETRIC FORM FOR REVIEW.
 SECTION 104.3.1.1. SHOW ALL PIPE SIZES,
 VENTS ECT FOR SANT., AND ALL PIPE SIZES,
 VALVES, RPZ BACKFLOW, WATER HAMMER
 ARRESTORS, (WHERE REQUIRED BY SECTION
 604.9 LOCATED NEAR THE FIXTURE PER
 PDI-WH 201) AND POINT OF CONNECTION TO
 THE WATER SUPPLY.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-01 Cont ID  
Sent By kstevens Date 2005-02-01 Time 08:46 Rev Time 1.26
Received By kstevens Date 2005-02-01 Time 08:46 Sent To  
Notes
2005-02-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SUBMIT DETAILS FOR TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTION 11-4.16,
 11-4.18, 11-4.19, 11-22, 11-4.1.3(11)
 ADAPTABLE TOILET ROOM FOR PRIVATE
 OFFICE.
 2) SHT 6 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IS MEET
 CODE REQUIREMENTS.
 A) WOMENS TOILET ROOM BY KITCHEN, TRAP
 FOR W/C NOT APPROVED. W/C HAS INTEGRAL
 TRAP IN FIXTURE. SECTION 1002.1
 B) MENS TOILET URINAL SHOWS TRAP UNDER
 THE SLAB. IF THE URINAL IS A WALL HUNG
 URINAL, IT SHALL BE ON A STACK AND
 VENTED.
 C) BRANCH DRAIN TO FIRST TOILET ROOMS
 INDICATES A CONNECTION TO THE BOTTOM OF
 THE BLDG. DRAIN. PLEASE CLARIFY. SECTION
 104.2.1.
 D) BAPISTRY REQUIRES A TRAP. SECTION
 1002.1.
 E) MENS TOILET ROOM BY SANTURARY SHOWS
 TWO W/C'S, BUT FLOOR PLAN SHOW 1 W/C AND
 1 URINAL.
 (SEE ATTACHED FOR SANITARY RISER DIAGRAM
 THAT MEETS CODE AND REFLECTS THE FLOOR
 PLAN)
 3) SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZES, WATER HAMMER ARRESTORS
 WHERE REQUIRED, VALVES ECT. SECTION
 104.3.1.1.
 4) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025.
 5) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 6) WATER HEATER REQUIRES THERMAL
 EXPANSION CONTROL PER SECTION 607.3.2.
 7) PLANS INDICATE A KITCHEN AND DINING
 AREA. PLEASE INDICATE ON PLANS IF THIS
 IS FOR MEMBERS OR WILL THE PUBLIC BE
 SERVED.
 8) PER TABLE 403.1 A DRINKING FOUNTAIN
 AND A SERVICE SINK ARE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-05 Cont ID  
Sent By aaponte Date 2005-08-05 Time 09:57 Rev Time 0.00
Received By aaponte Date 2005-07-27 Time 08:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-02-07 Cont ID  
Sent By aaponte Date 2005-02-07 Time 16:37 Rev Time 0.00
Received By aaponte Date 2005-02-07 Time 16:37 Sent To  
Notes
2005-02-07 00:00:001. THE SITE PLAN HAS TO BE MODIFIED TO
 COMPLY WITH CHANGES RECOMMENDED BY DAC
 APPROVAL ON ITS OCTOBER 13, 2004
 MEETING.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved