Plan Review Details - Permit 05010365
Plan Review Stops For Permit 05010365
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-06-27 Cont ID  
Sent By jwitmer Date 2005-06-27 Time 14:05 Rev Time 0.77
Received By jwitmer Date 2005-06-27 Time 14:05 Sent To PC
Notes
2005-06-27 00:00:006/27/05
 SHOP DRAWINGS BAR JOIST, TILT WALL,
 STEEL BEAMS & ROOF REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-06-17 Cont ID  
Sent By jwitmer Date 2005-06-17 Time 13:59 Rev Time 0.55
Received By jwitmer Date 2005-06-17 Time 13:58 Sent To  
Notes
2005-06-17 00:00:0006-17-05REV# 1 DATED 5-23-05OK JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-06-16 Cont ID  
Sent By jlong Date 2005-06-29 Time 08:49 Rev Time 0.56
Received By jwitmer Date 2005-06-16 Time 12:34 Sent To PC
Notes
2005-06-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010365
 ADD: 5133 TYLER LAKES
 CONT: HEDRICK BROTHERS
 TEL: (561)267-4292
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL/ TILT WALL
 ACTION: DENIED
  
 PLEASE SUBMIT (3) SETS OF ALL
 SUBMITTALS, REVISIONS, PLANS OR REPORTS,
 THERE IS A RESIDENT INSPECTOR ON SITE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-05-06 Cont ID  
Sent By jwitmer Date 2005-05-06 Time 09:40 Rev Time 3.33
Received By jwitmer Date 2005-04-27 Time 07:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-03-14 Cont ID  
Sent By jwitmer Date 2005-03-14 Time 12:09 Rev Time 5.55
Received By jwitmer Date 2005-03-14 Time 12:09 Sent To  
Notes
2005-03-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010365
 ADD: 5133 TYLER LAKES BLVD
 CONT:(PLAN REVIEW)
 TEL: (248)721-3131
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT #1 FROM THE FIRST REVIEW:
 THE ARCHITECTURAL FIRM "ARCADIS"
 DOES NOT HAVE A CERTIFICATE OF
 AUTHORIZATION IN THE STATE OF FLORIDA,
 CORRECT TITLE BLOCK TO READ THE
 ARCHITECTS NAME AND LICENSE NUMBER.
 481.219 F.S. CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION NUMBER.
  
 2) COMMENT #2 FROMTHE FIRST REVIEW:
 THE ENGINEERING FIRM "MILLER LEGG &
 ASSOC2IATES"REQUIRES A CERTIFICATE OF
 AUTHORIZATION, 471.023 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF
 AN ENGINEER PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.
  
 3) COMMENT #4 FROM THE PEVIOUS REVIEW:
 THREE (3) SOILS REPORTS ARE REQUIRED.
 FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 4)COMMENT #8 FROM THE PEVIOUS REVIEW:
 FBC* 105.3RESIDENT INSPECTOR. SUBMIT
 INSPECTOR RESUME' AND LICENSE DOCUMENTS
 TO HAROLD PISKURA, DIRECTOR OF THE
 RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF THE
 FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 OWNER, RESIDENT JOB INSPECTOR,&
 CONTRACTOR.
  
 5) THREE (3) SETS OF ALL REPORTS,
 DRAWINGS, OR SUBMITTALS SHALL BE
 REQUIRED FOR A RESIDENT INSPECTOR.
  
 6)COMMENT # 15 FROM THE PREVIOUS REVIEW:
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7) COMMENT #16 FROM THE PREVIOUS REVIEW:
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES (3 FOR
 RESIDENT INSPECTOR) OF PRODUCT TESTING
 REPORTS,MISSING REPORTS ARE AS FOLLOWS:
 A) STOREFRONT- KAWNEER- FL627 THE
 TECHNICAL DRAWINGS DO NOT MATCH THE
 SUBMITTED DADE NOA!
 B) MULLIONS- MULLION REPORT SUBMITTED
 IS FOR ALENCO SINGLE HUNG WINDOWS
 AND THE LENGHT LIMITATION OF 72".
 C) NO SUBMITTALS FOR THE DOUBLE GLASS
 FRONT DOORS!
 D) OVERHEAD ROLL UP DOORS- SEE THE 600
 COIL-AWAYTECHNICAL SHEET D-308114
 THE 14' WIDE DOOR DOES NOT MEET THE
 WIND PRESSURES.
  
 8) WILL BE A PROVISO, THAT ALL SHOP
 DRAWINGS ( TILT WALL, BAR JOIST)
 SHALL BE REVIEWED BY THE DESIGN
 PROFESIONALS AND APPROVED BEFORE
 SUMITTAL TO THE BUILDING DEPARTMENT.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) COMPILE PLANS (STAPLE) INTO (3)
 COMPLETE SETS OF DRAWINGS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2005-04-27 Cont ID  
Sent By jwitmer Date 2005-04-27 Time 07:06 Rev Time 0.00
Received By jwitmer Date 2005-04-27 Time 07:06 Sent To  
Notes
2005-04-27 00:00:00NO REVIEW COMPLETED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By jwitmer Date 2005-01-25 Time 07:22 Rev Time 4.40
Received By jwitmer Date 2005-01-25 Time 07:16 Sent To  
Notes
2005-01-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010365
 ADD: 5133 TYLER LAKES BLVD
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) THE ARCHITECTURAL FIRM "ARCADIS"
 DOES
 NOT HAVE A CERTIFICATE OF AUTHORIZATION
 IN THE STATE OF FLORIDA, CORRECT TITLE
 BLOCK TO READ THE ARCHITECTS NAME AND
 LICENSE NUMBER. 481.219 F.S.
 CERTIFICATE OF AUTHORIZATION.THE
 TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF
 AN ARCHITECT PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.
  
 ) THE ENGINEERING FIRM "MILLER LEGG &
 ASSOC2IATES"REQUIRES A CERTIFICATE OF
 AUTHORIZATION, 471.023 F.S.
 CERTIFICATE
 OF AUTHORIZATION.THE TITLE BLOCK FOR
 ANY SHEET BEARING THE NAME OF AN
 ENGINEER PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF
 AUTHORIZATION
 NUMBER.
  
 3)ENGINEER JAMES R. FOX FULL LEGAL
 SIGNATURE REQUIRED, PLANS,
 SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE "FULL" SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 AFFIXED TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN
 QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE
 EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 5)SHEET T0.1 REVISE BUILDING CODE DATA,
 ADA,TO FLORIDA ACCESSIBILITY CODE FOR
 BUILDING CONSTRUCTION, CHAPTER 11 OF
 THE
 2001 FLORIDA BUILDING CODE, 2003
 REVISIONS. FLORIDA AMERICANS WITH
 DISABILITY ACCESSIBILITY IMPLEMENTATION
 ACT,SECTION 553.501-553.513
 INCORPORATES INTO THE LAWS OF FLORIDA
 THE ACCESSIBILITY REQUIREMENTSOF THE
 ADA, WHILE AT THE SAME TIME TO MAINTAIN
 THOSE PROVISIONS OF FLORIDA LAW THAT
 ARE
 MORE STREINGENT THAN THE ADA
 ACCESSIBILITY GUIDELINES.
  
 6) SHEET T).1 BUILDING CODE DATA,
 CHAPTER 4 411.5.4 REPAIR GARAGE
 "REPAIRS
 ARE NOT TO TAKE PLACE IN THIS
 FACILITY."
 I DISCUSSED THIS ISSUE WITH THE
 BUILDING
 OFFIIAL, HE BELIEVE SINCE NO REPAIRS
 ARE
 TO TAKE PLACE, THE INSPECTION OF CARS
 FROM ACCIDENT DAMAGE. CARS WILL BE
 MOVED
 IN & OUT OF THIS FACILITY JUST AS A
 PARKING GARAGE, AND POSSIBILY MORE
 FREQUENTLY, THEREFORE HE BELIEVE THAT
 SECTION 411.4.2REQUIRING (6) AIR
 CHANGES PER HR FITS THE DESCRIPTION OF
 THE PROJECT BETTER THUS ENVOKING THIS
 CODE SECTION.
  
 7) F1.1 WORK STATIONS (108) ARE PART OF
 A EGRESS CORRIDOR AS POSITIONED THERE
 IS
 ONLY 2'-0" CLEAR, THE MINIMUM CORRIDOR
 OR AISLE WIDTH IS 36" WITH A OCCUPANT
 LOAD OF LESS THAN 50, 50 OR MORE
 REQUIRES44", SEE TABLE 1004.
  
 8)SHEET A3.1 INDICATES THE USE OF TILT
 WALL PANELS, REQUIRING A SPECIAL
 INSPECTOR, FBC* 105.3RESIDENT
 INSPECTOR. SUBMIT INSPECTOR RESUME' AND
 LICENSE DOCUMENTS TO HAROLD PISKURA,
 ((561)805-6711) DIRECTOR OF THE
 RESIDENT
 INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR
 PROGRAM IS REQUIRED, ON THIS PROJECT,
 DUE TO ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL
 DESIGN
 OR METHODS OF CONSTRUCTION
  
 9) SHEET A3.1 & A5.2 INDICATE THE USE
 OF
 A PREMANUFACTURED CANOPY BUT NO PLANS
 ARE SUBMITTED, IS THIS A STATE APPROVED
 SYSTEM ( DEPARTMENT OF COMMUMITY
 AFFAIRS)? SUBMIT ADDITIONAL
 INFORMATION.
 NO CANOPY PLANS SUBMITTED AT THIS TIME,
 NO REVIEW CAN BE COMPLETED.
  
 10) SHEET A6.1 DETAIL# 7 IS MISSING THE
  
 U.L. LISTING FOR THE HEAD OF WALL
 FIRESTOPPING SYSTEM.
  
 11) SHEET S2.1 CAST IN PLACE CONCRETE
 NOTES CORECT ACI 318-02, ACI350-02.
  
 12) SHEET A2.1 & A5.1 INDICATE ROOF
 DRAINAGE WITH THU-WALL SCUPPERS BUT NO
 EMERGENCY OVERFLOW SCUPPERS:
 1503.4.2 OVERFLOW DRAINS SHALL BE THE
 SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH
 THE INLET FLOW LINE LOCATED 2" ABOVE
 THE
 LOWEST POINT OF THE ROOF LINE. OVERFLOW
 SCUPPERS SHALL BE A MINIMUM OF 4"IN
 HEIGTH AND SHALL BE PLACED IN WALLS OR
 PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF
 SURFACE.
  
 13) SHEET A5.1 SEE DETAIL# 2,1503.4.4
 PROTECTION AGAINST DECAY & TERMITES.
 CONDENSATE LINES & ROOF DOWN SPOUTS
 SHALL DISCHARGE AT LEAST 1 FT. AWAY
 FROM
 THE STRUCTURE SIDEWALL, WHETHER BY
 UNDERGROUND PIPING, TAIL EX- TENSIONS,
 OR SPLASH BLOCKS.
  
 14)1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS
 THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE
 ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 15)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 ****PLEASE SUBMIT THE COVERSHEET FOR
 ALL
 PRODUCT APPROVALS REQUIRED BY THE
 STATE*****
  
 16)FL BLD CODE 1606.1.5: COMPONENTS
 &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) GLASS BLOCK
 C)MULLIONS
 D) LOUVERS
 E) EXTERIOR DOORS SOLID & GLAZED
 F) OVERHEAD DOORS
 G) STORM SHUTTERS
 H) ROOFING ASSEMBLIES
  
 17)1707.4.5.1 MULLIONS OCCURRING BETWEEN
 INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 18)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 19)1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 20)PROVIDE PLANS FOR TILT WALLS AND FOR
  
 BAR JOIST.
  
 21)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-10-12 Cont ID  
Sent By dpalmer Date 2005-10-12 Time 13:32 Rev Time 0.25
Received By dpalmer Date 2005-10-12 Time 12:32 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-09-29 Cont ID  
Sent By dpalmer Date 2005-09-29 Time 10:43 Rev Time 0.00
Received By dpalmer Date 2005-09-29 Time 10:43 Sent To  
Notes
2005-09-29 00:00:00REV FOR SHEET 3.2 5.1

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-06-21 Cont ID  
Sent By dpalmer Date 2005-06-21 Time 07:25 Rev Time 0.50
Received By dpalmer Date 2005-06-21 Time 07:24 Sent To  
Notes
2005-06-21 00:00:00REDLINED 700.12E FOR EM/EXT LT
 CIRCUITING.
  
 REDLINED MCB REQUIRED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-20 Cont ID  
Sent By dpalmer Date 2005-04-20 Time 19:45 Rev Time 0.50
Received By dpalmer Date 2005-04-20 Time 18:53 Sent To  
Notes
2005-04-20 00:00:00REDLINED:
 EM/EXT LTS WIRED PER 700.12E
 REDLINED:
 MCB SHALL BE INSTALLED IN MDP, W/ NO
 EXCEPTIONS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-08 Cont ID  
Sent By dpalmer Date 2005-03-08 Time 14:50 Rev Time 1.50
Received By dpalmer Date 2005-03-08 Time 14:25 Sent To  
Notes
2005-03-08 00:00:00********* UNSAT 2ND REVIEW *********
  
 PLEASE SEE PLANS ARE STILL ONLY IN FOR
 PLAN REVIEW AND HAVE NOT BEEN SUBMITTED
 FOR PERMIT.
  
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 NO, PLEASE INCLUDE ALL
 REQUIRED LICENSE INFORMATION ON TITLE
 BLOCKS FOR ALL TRADES AND FOR ALL SHEETS
 AS REQUIRED UNDER FS 481.219,471.023
 FAC 61G1-16.004,61G15-23.002.
 PLEASE SEE ATTACHED SHEETS FROM STATE
 DBPR SITE PERTAINING TO FIRM SHOWN ON
 PLANS.
 THIS FIRM IS SHOWN AS "APPLICANT" AT
 THIS TIME.
 PLEASE SEE ALL TITLE BLOCKS. PH-SHEETS
 ETC.
 PLEASE ALSO BE AWARE, FIRM # SHOWN ON
 PLANS AT THIS TIME APPEAR TO BELONG TO A
 DIFFERENT FIRM.
 PLEASE ALSO BE AWARE, FIRM NAME AS
 REGISTERED WITH STATE MUST BE THE SAME
 AS ON TITLE BLOCK.
 PLEASE SEE THIS IS REQUIRED OF ALL
 SHEETS AND TRADES WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: NOTE #2, NO, PLEASE SEE SOME
 SHEETS SEAL IS NOT CLEARLY VISABLE WITH
 INFORMATION REQUIRED. PLEASE SEE FS
 471.025 FOR ENGINEERS AND 481.221 FOR
 ARCH'S.
 PLEASE ALSO SEE PLANS MUST BE SIGNED,
 "DATED " AND SEALED.
 LTR FROM ENGINEER MR. JAMES FOX WAS
 RECIEVED AND PLACED IN FILE FOR
 SIGNATURE VERIFICATION.
  
 3)NOTE:NOTE #3, OK, BLDG TO REVIEW WIND
 LOAD CALCULATIONS.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE CWP AND
 GRND ROD WAS ADDED, HOWEVER FOOTER
 STEEL, WAS NOT SHOWN. PLEASE SEE PLANS
 REFERENCE 250.50 FOR GES. PLEASE SEE FBC
 104.2.1, PLANS SHALL NOT CONTAIN
 REFERENCE TO TECHNICAL CODES IN WHOLE OR
 IN PART.
  
 5)NOTE: NOTE #5, OK, NOT SHOWN PER
 DETAIL NEC ARTICLES, HOWEVER ALL LOADS
 ARE SHOWN AS CONNECTED LOAD W/OUT
 DERATING. THIS IS OK.
  
 6)NOTE: NOTE #6, NO, PLEASE SEE PREVIOUS
 COMMENT WAS NOT TO CHANGE IDENTIFICATION
 OF MDP TO MCB. IT WAS TO REQUIRE A MCB,
 (MAIN CIRCUIT BREAKER).
 PLEASE SEE MAIN IS SHOWN AS PART OF A
 PANEL BOARD FOR SERVICE WHICH WILL
 CONTAIN MORE THAN 6-SPACES FOR MEANS OF
 DISC OF SERVICE. PLEASE SEE THAT A MCB
 WILL BE REQUIRED.230.71A, 240.4
  
  
 7)NOTE: NOTE #7 OK.
  
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICLA
 PLANS.
  
 PLEASE REMOVE ALL OLD SHEETS AND INSERT
 NEW REVISED SHEETS INTO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 PLEASE SEE ALL SHEETS WERE LOOSE IN
 ROLLS?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-21 Cont ID  
Sent By dpalmer Date 2005-01-21 Time 16:43 Rev Time 1.00
Received By dpalmer Date 2005-01-21 Time 15:12 Sent To  
Notes
2005-01-21 00:00:00************* UNSAT ******************
  
 *PLEASE SEE THIS IS IN FOR "PLAN
 REVIEW"
 ONLY AND NOT SUBMITTED FOR PERMIT.
  
  
 1)NOTE: PLEASE VERIFY LICENSE
 INFORMATION PLACED ON TITLE BLOCK FOR
 FIRM.
 PLEASE SEE THE REQUIRED CA # PER FS
 481.219/471.023 DOES NOT SEEM TO
 CORRELATE WITH STATE WEBSITE. PLEASE SEE
 COPY OF ATTACHED PRINT OUT FROM STATE
 WHICH INDICATES A A DIFFERENT COMPANY
 FOR LICENSE # SHOWN ON PLANS.
  
 2)NOTE: PLEASE SEAL FOR ENGINEER MUST BE
 RAISED,CLEAR AND VISABLE WITH ALL
 INFORMATION ON SAID SEAL AS REQUIRED
 UNDER FS 471.025
 PLEASE ALSO SEE PLANS APPEAR TO BE
 "SIGNED" WITH INITIALS? IF THIS IS
 INDEED THE LEGAL "SIGNATURE" FOR
 ENGINEER, PLEASE PROVIDE A SIGNED,DATED
 AND SEALED NOTORIZED LETTER FOR TO
 AFFIRM LEAGAL SIGNATURE. THIS LTR WILL
 BE PLACED IN OUT SIGNATURE FILE FOR ANY
 POSSIBLE FUTURE REFERENCE.
  
 3)NOTE: PLEASE PROVIDE WIND LOAD
 CALCUALTIONS FOR NEW SITE LIGHTING POLES
 AND FIXTURES. THIS IS REQUIRED AT THIS
 TIME AND MUST MEET FBC 140 MIN.
  
 4)NOTE: PLEASE VERIFY GROUNDING
 ELECTRODE SYSTEM. RISER INDICATES "SEE
 SPEC", YET INFORMATION REQUIRED PER
 250.50 COULD NOT BE LOCATED.
 PLEASE SHOW MIN CWP, FOOTER STEEL AND
 ANY OTHER METAL BLDG AS PART OF GE
 SYSTEM.
  
 5 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE ALSO SEE 220.12 FOR TRACK
 LIGHTING LOADS.
 PLEASE SHOW.
  
 6)NOTE: PLEASE INDICATE MDP AS MCB.
 240.4. 215.5
  
 7)NOTE: PLEASE SEE 2002 NEC ART 511
 PLEASE PLACE NOTE ON PLANS IF "NO
 SERVICE" ON VEHICLES.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2005-03-29 Cont ID  
Sent By mamini Date 2005-03-29 Time 11:13 Rev Time 0.00
Received By mamini Date 2005-03-29 Time 11:13 Sent To  
Notes
2005-03-29 00:00:00PASSED :
  
 1. SEE PERMIT # 05031570 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2005-03-01 Cont ID  
Sent By mamini Date 2005-03-01 Time 15:05 Rev Time 0.50
Received By mamini Date 2005-03-01 Time 15:04 Sent To  
Notes
2005-03-01 00:00:00FAILED:
  
 1. CIVIL PLANS MUST BE APPROVED BY THE
 PUBLIC UTILITIES AND ENGINEERING PRIOR
 TO SUBMITTING TO THE CONSTRUCTION
 SERVICES FOR THE ACTUAL PERMITTING.
 2. SEE SHEET C2.1 FOR DUMPSTER ENCLOSURE
 DETAILS.AS SHOWN ON SHEET 3 OF 11 DOES
 NOT COMPLY WITH CITY' REQUIREMENTS.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-01-11 Cont ID  
Sent By mamini Date 2005-01-11 Time 15:49 Rev Time 1.00
Received By mamini Date 2005-01-11 Time 15:49 Sent To  
Notes
2005-01-11 00:00:00FAILED:
  
 1. REVIEW COMMENTS BY THE PUBLIC
 UTILITIES AND ENGINEERING MUST BE
 ADDRESSED AND IMPLEMENTED INTO THE
 CIVIL PLANS PRIOR TO SUBMITTING FOR
 ACTUAL PERMITTING.
 2. DUMPSTER ENCLOSURE MUST BE SIZED PER
 CITY OF WPB'S REQUIREMENTS IF GARBAGE
 IS TO BE PICKED UP BY THE CITY; 12'-6"
 OPENING BETWEEN THE GATE POSTS,INTERIOR
 DIMENSIONS 12'-6" AND 12'-0" DEEP.
 3. FIRE DEPT. CONNECTION SHOULD BE
 LOCATED PASSED THE FIRE HYD. IN THE
 ISLAND AREA, AS PROPOSED WILL CREATE A
 LOOP WITH NO AFFECT ON PRESSURE. PLEASE
 VERIFY WITH FIRE DEPARTMENT, CAPT. NATE
 MCCRAY 805-6722.
 4. PLEASE VERIFY THE CONSTRUCTION OF
 THE DETECTABLE SURFACE AT THE EXIT INTO
 TYLERLAKES BLVD.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-10-12 Cont ID  
Sent By mwennerg Date 2005-10-12 Time 14:01 Rev Time 0.00
Received By mwennerg Date 2005-10-12 Time 14:01 Sent To  
Notes
2005-10-12 00:00:00REVISION DATED 9/28/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-06-28 Cont ID  
Sent By mwennerg Date 2005-06-28 Time 10:07 Rev Time 0.00
Received By mwennerg Date 2005-06-28 Time 09:53 Sent To  
Notes
2005-06-28 00:00:00REVISION DATED 5/27/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-05-09 Cont ID  
Sent By mwennerg Date 2005-05-09 Time 11:15 Rev Time 0.00
Received By mwennerg Date 2005-05-09 Time 11:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-03-29 Cont ID  
Sent By mwennerg Date 2005-03-29 Time 10:20 Rev Time 0.00
Received By mwennerg Date 2005-03-29 Time 10:20 Sent To  
Notes
2005-03-29 00:00:00DENIED
  
 1) PLANS SHOW AN ACCESS GATE INTO THE
 PROPERTY. PLEASE INCLUDE THE WIDTH
 DIMENSION WHICH SHALL BE A MINIMUM OF 20
 FEET FOR EMERGENCY VEHICLES.
  
 2) A KNOX KEY ENTRY WILL BE PROVIDED.
 WHAT WILL SERVE AS THE BACK UP IN THE
 EVENT OF POWER FAILURE?
  
 3) PLEASE SHOW THE LOCATION OF FIRE
 HYDRANTS. BE ADVISED THAT A FIRE HYDRANT
 MUST BE LOCATED NOT FURTHER THAN 150
 FEET FROM THE CLOSEST HYDRANT.
  
 4) PLEASE BE ADVISED THAT AN ADDRESS
 NUMBER IS REQUIRED ON THE BUILDING. THE
 NUMBERS SHALL BE AT LEAST 6" IN HEIGHT
 AND CONTRASTING TO THE BACKGROUND.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 WILL BE REQUIRED FOR THE FIRE SPRINKLER
 AND FIRE ALARM SYSTEMS.
  
 6) THE FIRE SPRINKLER SYSTEM SHALL BE
 MONITORED BY A U.L. LISTED CENTRAL
 STATION SERVICE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-27 Cont ID  
Sent By mcarsill Date 2005-01-27 Time 14:35 Rev Time 0.00
Received By mcarsill Date 2005-01-27 Time 14:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-10-04 Cont ID  
Sent By adarroug Date 2005-10-04 Time 16:50 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 16:50 Sent To  
Notes
2005-10-04 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 18:57 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 18:57 Sent To E
Notes
2005-09-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 08:53 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 08:53 Sent To M
Notes
2005-08-19 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 09:01 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 09:01 Sent To  
Notes
2005-07-22 00:00:00TO "F" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 11:47 Rev Time 0.00
Received By shill Date 2005-06-20 Time 11:47 Sent To B
Notes
2005-06-20 00:00:00TO JW DESK(3 SUBMITTALS)

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 11:39 Rev Time 0.00
Received By shill Date 2005-06-20 Time 11:39 Sent To B
Notes
2005-06-20 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 12:10 Rev Time 0.00
Received By shill Date 2005-06-10 Time 12:10 Sent To B
Notes
2005-06-10 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-06-09 Cont ID  
Sent By mjacobs Date 2005-06-09 Time 08:55 Rev Time 0.00
Received By mjacobs Date 2005-06-09 Time 08:55 Sent To ENG
Notes
2005-06-09 00:00:00TO 'ENG BOX'. REV.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-06-08 Cont ID  
Sent By mjacobs Date 2005-06-08 Time 16:42 Rev Time 0.00
Received By mjacobs Date 2005-06-08 Time 16:42 Sent To  
Notes
2005-06-08 00:00:00TO 'COMM BD#37/REV.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-01 Cont ID  
Sent By adarroug Date 2005-06-01 Time 13:38 Rev Time 0.00
Received By adarroug Date 2005-06-01 Time 13:38 Sent To  
Notes
2005-06-01 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-26 Cont ID  
Sent By adarroug Date 2005-05-26 Time 09:07 Rev Time 0.00
Received By adarroug Date 2005-05-26 Time 09:07 Sent To FIRE
Notes
2005-05-26 00:00:00TO "MWENNEGREN" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 14:38 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 14:38 Sent To  
Notes
2005-04-12 00:00:00TO "COMM" BD#4/PLANS ON RACK 1 ROLL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 11:48 Rev Time 0.00
Received By adarroug Date 2005-04-14 Time 14:39 Sent To Z
Notes
2005-04-12 00:00:00TO "Z" BOX/PLEASE SEE INCOMING STOP
 UNDER 05040494

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-01 Time 15:13 Rev Time 0.00
Received By adarroug Date 2005-03-01 Time 10:10 Sent To  
Notes
2005-03-01 00:00:00TO "COMM" BD#56/"COMM" RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-10 Cont ID  
Sent By mjacobs Date 2005-02-03 Time 15:46 Rev Time 0.00
Received By kstevens Date 2005-01-10 Time 14:57 Sent To  
Notes
2005-01-10 00:00:00TO "COMM BD#63"

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2005-10-12 Cont ID  
Sent By hmoser Date 2005-10-12 Time 11:18 Rev Time 0.00
Received By hmoser Date 2005-10-12 Time 11:18 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2005-09-30 Cont ID  
Sent By tgordon Date 2005-09-30 Time 09:01 Rev Time 0.20
Received By tgordon Date 2005-09-30 Time 09:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-08-29 Cont ID  
Sent By tgordon Date 2005-08-29 Time 16:37 Rev Time 0.45
Received By tgordon Date 2005-08-29 Time 16:37 Sent To  
Notes
2005-08-29 00:00:00*** MECH. REVISION ***
 PASSED. SHOWING R/A GRILLS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-06-29 Cont ID  
Sent By pkrauss Date 2005-06-29 Time 12:49 Rev Time 0.50
Received By pkrauss Date 2005-06-29 Time 12:49 Sent To  
Notes
2005-06-29 00:00:00PROVISO:
 CO SENSORS SHALL BE TESTED FOR FINAL
 INPECTION.PLEASE NOTE, CO SENSORS ARE
 TO INITIATE AUTOMATICALLY AT A MAXIMUM
 OF 25 PPMIN ACCORDANCE WITH 2001
 FBC(M)403.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-05-19 Cont ID  
Sent By pkrauss Date 2005-05-19 Time 09:28 Rev Time 0.50
Received By pkrauss Date 2005-05-19 Time 09:28 Sent To  
Notes
2005-05-19 00:00:00PROVISO:
 1.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED WITH NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS.
  
 2.THE LOCATION OF THE ACCU-1 APPEARS
 TO BE "INSIDE".CONDENSOR UNITS ARE TO
 BE INSTALLED "OUTSIDE" (OUTDOORS) PER
 THE MANUFACTURER'S SPECIFICATIONS.
 PLEASE REVISE PLANS TO RE-LOCATE ACCU-1.
  
 PER 2001 FBC CHAPTER 13 SUB SECTION
 407.1.ABCD.3.3, THE CONDENSING COIL OF
 ONE AIR CONDITIONING UNIT SHALL NOT BE
 INSTALLED IN THE COOL AIR STREAM OF
 ANOTHER AIR CONDITIONING UNIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-03-22 Cont ID  
Sent By pkrauss Date 2005-03-22 Time 09:29 Rev Time 0.45
Received By pkrauss Date 2005-03-22 Time 08:07 Sent To  
Notes
2005-03-22 00:00:00DENIED:
 COMMENT #3 FROM PREVIOUS REVIEW - PLANS
 ARE TO BE SIGNED BY THE ENGINEER IN
 ACCORDANCE WITH FS 471.025 & FAC
 61G15-23.002.PROVIDE A COPY OF DRIVES
 LICENSE OR STATE ID SHOWING LEGAL
 SIGNATURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-26 Cont ID  
Sent By pkrauss Date 2005-01-26 Time 06:43 Rev Time 1.45
Received By pkrauss Date 2005-01-25 Time 16:33 Sent To  
Notes
2005-01-26 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) TABLE
 403.3.PLEASE INCLUDE OFFICE AREAS AS
 WELL AS THE GARAGE AREAS.
  
 2.IT IS THE DETERMINATION OF THE
 BUILDING OFFICAL SINCE THIS IS NOT
 CLASSIFIED AS A "REPAIR GARAGE" AND
 SINCE CARS WILL BE MOVED IN AND OUT,
 THAT IT SHALL BE CLASSIFIED AS A
 "PARKING GARAGE".PLEASE SHOW
 COMPLIANCE WITH THE 2001 FBC 411.4.2.
  
 3.PLEASE REFERENCE COMMENTS BY
 ELECTRICAL & BUILDING ON THE SIGNATURER,
 TITLE BLOCK AND CERTIFICATE OF
 AUTHORIZATION FOR THE ARCHITECTURAL &
 ENGINEERING FIRMS (FS 471.023, 471.025 &
 481.219).
  
 4.PLEASE NOTE, PLAN SHEET M2.1
 INDICATES GAS FIRED HEATERS AS WELL
 HORIZONTAL UNIT HEATER (ELECTRIC).
 PLEASE CLARIFY THE PURPOSE OF THE
 ELECTRIC HEATER IN THE MECHANICAL ROOM.
  
  
 5.PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE GHUH INDICATED ON PLAN SHEETS
 M2.1 & M7.1.
  
 6.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR ALL MECHANICAL
 EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-06-24 Cont ID  
Sent By kstevens Date 2005-06-24 Time 18:34 Rev Time 0.49
Received By kstevens Date 2005-06-24 Time 18:34 Sent To  
Notes
2005-06-24 00:00:00REVISION OK - SHT P7.1 DETAIL #6

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-05-18 Cont ID  
Sent By kstevens Date 2005-05-18 Time 14:10 Rev Time 3.00
Received By kstevens Date 2005-05-14 Time 19:57 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-18 Cont ID  
Sent By kstevens Date 2005-03-18 Time 19:07 Rev Time 3.33
Received By kstevens Date 2005-03-18 Time 19:07 Sent To  
Notes
2005-03-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) FOLLOWING COMMENTS WERE NOT ADDRESSED
 OR NOT ADDRESSED SUFFICIENTLY. THE
 COMMENT NUMBER SHALL STAY THE SAME TO
 AVOID CONFUSION.
 1) SHTS IRR 1,2,&3 PRINTED NAME OF THE
 PERSON SEALING THE PLANS IS REQURED ON
 THE TITLE BLOCK. FAC 61G1-16.004(6) & FS
 481.2055. RESPONSE NOTED "OUR DOCUMENTS
 DO NOT INCLUDE AN IRR SHEET SERIES".
 THERE ARE IRRIGATION SHEETS SUBMITTED.
 ALSO THE CERTIFICATE OF AUTHORIZTION IS
 REQUIRED FOR ALL IRR. SHEETS. THIS IS
 REQUIRED AS AN "AA" OR "AR" NUMBER AS
 THE SHEETS WERE SIGNED & SEALED BY A
 LANDSCAPE ARCHITECT. FS 481.219(2)
 3) OIL WATER SEPARATOR SHALL BE SIZED
 AND APPROVED BY RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE. WASTE ORD
 #2938-96. (561) 837-4074 - RESPONSE
 NOTED, BUT SEE ATTACHED SHEET FROM
 RODNEY COMPO REQUIREING A 100 GAL OIL
 WATER SEPARATOR. SEPARATE PERMIT
 REQUIRED FOR SEPARATOR.
 10) ALL SHEETS, TITLE BLOCK FOR
 ARCHITECT, THE COMPANY NAME IS NOT THE
 SAME AS SHOWN ON THE DBPR LICENSE SEARCH
 FOR THE CERTIFICATE OF AUTHORIZATION,
 PLEASE MAKE THE CORRECTION ON THE TITLE
 BLOCK, SHOW APPROIATE BUSINESS NAME.
 (SEE ATTACHED SHEET FROM DBPR WEBSITE).
 FAC 61G1-16.004 & FS 481.291 - ALL
 SHEETS FOR ARCHITECT AND ENGINEER, THE
 DATE THAT THE SEAL AND SIGNATURE IS
 AFFIXED SHALL BE ON THE SEAL. FAC
 61G15-23.002(2) - FAC 61G1-16.003 / FS
 471.025 - 481.2055.
 11) SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES FOR FIXTURES. 2 DRINKING
 FOUNTAINS ARE REQUIRED. SHT TO-1
 INDICATES A DRINKING FOUNTAIN IN LOBBY
 AREA, BUT NO DRINKING FOUNTAIN IS SHOWN
 ON THE FLOOR PLAN, NOR ON THE SANT. OR
 WATER PIPING RISERS. ONLY ONE WATER
 COOLER IS SHOWN.
 13) SHT PE.1 WATER RISER ISOMETRIC SHALL
 SHOW FULL OPEN VALVES ON ALL EVER WATER
 DOWN-FEED WATER LINE. SECTION 606.1(4)
 ALL WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 & MANUF. INSTALL.
 INSTRUCTIONS.
 15) A SEPARATE GAS PERMIT IS REQUIRED,
 AND THE FOLLOWING INFORMATION IS
 REQUIRED TO ISSUE THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - NOT ALL LENGTHS ARE
 SHOWN ON THE ISOMETRIC. SHOW LOCATION OF
 METER AND ALL MEASURMENTS TO METER.
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - THIS WAS
 NOT SHOWN ON THE PLANS.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -
 IF THE GAS DELIVERY PRESSURE IS .5 PSI,
 DELETE ALL SECONDARY REGULATORS FROM THE
 ISOMETRIC AS THEY WILL NOT BE IN SYSTEM.
 ALL SHUT OFF VALVES SHALL BE LOCATE
 MAXIMUM OF 6' FROM GAS APPLIANCE.
 SECTION 409.7. SOME ARE SHOWN EXCEEDING
 THIS REQUIREMENT ON THE ISOMETRIC.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. - NO
 SHEETS WERE FOUND.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.-
 THE SHEETS THAT WERE VOIDED WERE NOT
 REMOVED FROM THE SETS OF PLANS. REMOVE
 ALL OLD SHEET AND SUBMIT ONE SET OF OLD
 SHEETS FOR COMPARISON. - ONE SET OF
 PLANS SUBMITTED FOR REVIEW WAS SUBMITTED
 AS LOOSE SHEETS. PLEASE SUBMIT TWO OR
 MORE SETS OF PLANS FOR REVIEW. SECTION
 104.2.1.
 **************NEW COMMENT***************
 1B) THE FOLLOWING SHEETS ARE NOT SHOWN
 ON THE DRAWING INDEX, BUT WERE INCLUDED
 IN THE SETS OF PLANS. SHEETS 1 THRU 11
 OF 11, SHEET 1 OF 1, L1 & L2, IRR 1,2,3
 PH-1, E1 OF 2, E1 OF 6. CORRELATE THE
 INDEX SHEET WITH SHEETS SUBMITTED.
 SECTION 104.2.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-03 Cont ID  
Sent By kstevens Date 2005-02-03 Time 13:20 Rev Time 12.00
Received By kstevens Date 2005-02-01 Time 16:53 Sent To  
Notes
2005-02-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHTS IRR 1, 2, & 3 PRINTED NAME OF
 THE OF THE PERSON SEALING THE PLANS IS
 REQUIRED ON THE TITLE BLOCK. FAC
 61G1-16.004(6) & FS 481.2055
 2) SHT IRR 3 POINT OF CONNECTION,
 (POC),
 STATES 2" WATER METER. CIVIL SHEET 8 OF
 11 INDICATES 1" TAP. PLEASE CLARIFY.
 SECTION 104.2.1.
 3) OIL WATER SEPARATOR SHALL BE SIZED
 AND APPROVED BY RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE. WASTE ORD.
 NO.
 2938-96. (561)837-4074.
 4) SHTS F1.1 & A8.2 CLEAR FLOOR SPACE
 FOR WATER CLOSETS AND URINAL ARE
 REQUIRED IN THE MENS TOILET ROOM. ALSO
 SHOW THE TURNING ARE IN THE TOILET ROOM
 NOT THE ACCESSIBLE STALL. - CLEAR FLOOR
 SPACE FOR THE WATER CLOSET IS REQUIRED
 IN THE WOMENS TOILET ROOM, WITH THE
 TURNING AREA SHOWN IN THE TOILET ROOM
 NOT THE ACCESSIBLE STALL. SECTIONS
 11-4.16.2, 11-4.18.3 & 11-4.22.3-
 ALSO
 SHOW THE CLEAR FLOOR SPACE FOR THE W/C
 IN ROOM #106, THE CLEAR FLOOR SPACE FOR
 THE BREAK ROOM SINK IN ROOM #115,
 (FORWARD APPROACH IS REQUIRED - MAX.
 19"
 UNDERNEATH THE SINK), 11-4.24.5.
 5) SHTS F1.1 & A8.2 BREAK ROOM SINK
 MODEL #CR-25-21 INDICATES A 7" DEEP
 SINK, BUT SECTION 11-4.24.4 STATES THAT
 6-1/2" IS THE MAXIMUM DEPTH. ALSO
 FAUCET
 SHALL BE LEVER OPERATED, PUSH TYPE,
 TOUCH TYPE, OR ELECTRONICALLY
 CONTROLLED. SECTION 11-4.24.7
 6) SHT A1.2 ROOM FINISH SCHEDULE, MORE
 INFORMATION FOR WB-1 & WB-2 SHOWN FOR
 THE BASE. INDICATE MATERIAL TYPE. PER
 SECTION 1204.2 MATERIAL SHALL BE NOT
 ABSORBENT. PLEASE CLARIFY.
 7) SHT A1.2 ROOM FINISH NOTE #3.
 INDICATE THAT WAINSCOT IS REQUIRED.
 SECTION 104.2.1. & SECTION 1204.2.
 8) SHT A2.1 SUBMIT CALCULATIONS FOR
 ROOF
 DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW TOTAL AREA OF THE
 ROOF
 AND SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS. INDICATE THE AREA
 OF
 THE ROOF THAT DRAINS TO EACH DOWNSPOUT.
 SHOW SIZE OF GUTTERS PER TABLE 1106.6,
 INDICATE SLOPE OF GUTTERS AND SHOW THE
 HIGH POINT OF THE GUTTER.
 9) SHT A8.1 DETAIL #2 SHOW KNEE
 CLEARANCE 11-4.23.3, ACCESSIBLE WATER
 CLOSET SHOW HEIGHT 11-4.16.3,
 ACCESSIBLE
 URINAL SHOW HEIGHT 11-4.18.2, CLEAR
 FLOOR SPACE 11-4.18.3.
 10) ALL SHEETS, TITLE BLOCK FOR
 ARCHITECT, THE COMPANY NAME IS NOT THE
 SAME AS SHOWN ON DBPR LICENSE SEARCH
 FOR
 THE CERTIFICATE OF AUTHORIZATION.
 PLEASE
 MAKE THE CORRECTION ON THE TITLE BLOCK.
 SHOW APPROIATE BUSINESS NAME. FAC
 61G1-16.004 & FS 481.291. - AN ENGINEER
 SHALL SIGN HIS NAME AND AFFIX HIS SEAL
 TO ALL PLANS. INITIALS ARE NOT
 ACCEPTABLE. THE DATE THAT THE SIGNATURE
 AND SEAL IS AFFIXED SHALL BE ENTERED ON
 THE PLANS IMMEDIATELY UNDER THE
 SIGNATURE OF THE PROFESSIONAL ENGINEER.
 FAC 61G15-23.002(1) & FS 471.025
 11) SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES FOR FIXTURES. INDICATE ON
 PLANS THE SQUARE FOOTAGE FOR EACH
 OCCUPANCY. TABLES 1003.1 & 403.1.
 12) SHT P2.1 HOUSE TRAP NOT APPROVED.
 DELETE FROM DETAIL "B". SECTION 1002.1
 12) SHT P3.1 ALL RISER DIAGRAMS SHALL
 BE
 IN ISOMETRIC FORM AND SHALL REFLECT THE
 FLOOR PLAN. SECTION 104.2.1.
 13) SHT P3.1 WATER RISER ISOMETRIC
 SHALL
 SHOW VALVES REQUIRED BY SECTION
 606.1(4)
 FULL OPEN VALVES ON EVERY DOWN-FEED
 WATER LINE, AND SHOW THE LOCATION OF
 ALL
 WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 AND SHALL BE LOCATED NEAR
 THE FIXTURE, IN AN "EFFECTIVE RANGE"
 NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 14) SHT P3.1 INSPECTION BAY WASTE &
 VENT
 INDICATES A VERTICAL VENT FOR THE 4"
 FD-3 ON RISER DIAGRAM, BUT ON SHT P2.1
 THE VENT IS INDICATED AS A HORIZONTAL
 DRY VENT WHICH IS NOT APPROVED PER
 SECTION 905.3 & 905.4 PLEASE CLARIFY.
 15) A SEPARATE GAS PERMIT IS REQUIRED,
 AND THE FOLLOWING INFORMATION IS
 REQUIRED TO ISSUE THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING
 USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM
 PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY
 LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS,
 BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK
 AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 K) INDICATE TYPE OF MATERIAL FOR
 REGULATOR VENTS. VENT MATERIAL SHALL BE
 NON COMBUSTABLE. SECTION 631.15
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-06-29 Cont ID  
Sent By jlong Date 2005-06-29 Time 08:46 Rev Time 0.00
Received By jlong Date 2005-06-29 Time 08:46 Sent To I
Notes
2005-06-29 00:00:00APPLICANT SUBMITTED MINOR PD AMENDMENT
 CASE NO. 1239N WHICH WAS APPROVED ON
 6/29/05.ALL PREVIOUS CONDITIONS OF
 APPROVAL HAVE BEEN SATISFIED.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-03-10 Cont ID  
Sent By mmclean Date 2005-03-10 Time 17:04 Rev Time 0.00
Received By mmclean Date 2005-03-10 Time 17:04 Sent To  
Notes
2005-03-10 00:00:00DENIED,
 1. APPROVED SITE PLAN AND LANDSCAPE PLAN
 NOT SUBMITTED, PLEASE RESUBMIT WITH NEW
 SITE PLAN ADDED WALLS AROUND SECURITY
 FENCE.
  
 JOSH LONG
 SENIOR PLANNER
 PLANNING & ZONING
 822-1449

Review Stop Z ZONING
Rev No 1 Status F Date 2005-01-13 Cont ID  
Sent By mmclean Date 2005-01-13 Time 16:26 Rev Time 0.00
Received By mmclean Date 2005-01-13 Time 16:26 Sent To  
Notes
2005-01-13 00:00:00DENIED, BY JOSH LONG, PLANNER 822-1435.
 NEED TO MAKE CHANGES TO SCREEN PARKING.