Plan Review Details - Permit 05010308
Plan Review Stops For Permit 05010308
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By jwitmer Date 2005-01-24 Time 09:11 Rev Time 2.22
Received By jwitmer Date 2005-01-24 Time 09:02 Sent To  
Notes
2005-01-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010308
 ADD: 4047 OKEECHOBEE BLVD
 SUITE 2002& 2003
 CONT: CAREY BENJAMIN PROPERTIES
 TEL: (561)723-1249
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) THE VALUE INDICATED ON THE PERMIT
 APPLICATION IS TO LOW FOR THE AMOUNT OF
 WORK INDICATED ON THE PLANS. IF VALUE
 ISN'T INCREASE TO THE CORRECT VALUE THE
 CITY WILL CALCULATE THE VALUE USING
 MARSHALL & SWIFT TO CALCULATE VALUE.
  
 2)ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 3) IF THE VALUE OF THE CALCULATED WORK
 SHALL BE ABOVE $25,000.00 FL S. S.
 481.229(C) STATES PLANS ARE TO BE
 SUBMITTED TO THE BUILDING DEPARTMENT
 MUST USE THE SERVICES OF A REGISTERED
 FL
 ARCHITECT.
  
 4) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 5) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO
 THE
 AUTHORITY HAVING JURISDICTION. SUCH
 IDEN
 TIFICATION SHALL BE ABOVE ANY
 DECORATIVE
 CEILING CEILING AND IN CONCEALED
 SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 6) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 7) PLANS DO NOT INDICATE DOOR
 CLEARENCES
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING
 CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 8) 11-4.13.5 DOORWAYS, MINIMUM CLEAR
 WIDTH: DOORWAY SHALL HAVE A MINI- MUM
 CLEAR OPENING OF 32" WITH THE DOOR OPEN
 90 DEGREES, MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE OPPOSITE STOP.
  
 9) 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 10) THE WIDTH OF THE CORRIDORS SEE
 TABLE 1004.
  
 11)1016.3.1. EXIT SIGNS:
 EXIT SIGNS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLE ILLUMINATED BY A
 RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE
 VISIBLE IN BOTH THE NORMAL & EMERGENCY
 LIGHTING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-11 Cont ID  
Sent By dpalmer Date 2005-01-11 Time 13:10 Rev Time 0.25
Received By dpalmer Date 2005-01-11 Time 13:10 Sent To  
Notes
2005-01-11 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE FBC 104.2.1 .
 PLEASE SEE ALL PLANS/D RAWINGMUST
 CONTAIN PRINTED NAME AND SIGNATURE OF
 PERSON RESPONSIBLE FOR PLANS.
  
 2)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS TO SPLIT 2-UNITS INTO OFFICES?
 PLEASE CLARIFY.
  
 3)NOTE: PLEASE SUBMIT MIN ELECTRICAL
 REQUIRED FOR NEW OFFICE AREAS LTS? EM
 LTS? ANY EXT LTS REQUIRED.
 NEC 700, 215.5
 ALL NEW ELECTRICAL TO BE SHOWN AND ALL
 CIRCUITING TO PLACES ON PLANS AND
 CORRELATE WITH PANEL SCHEDULE TO BE
 SUBMITTED.
 IF CREATEING TWO NEW SPACES, PLEASE SEE
 MIN SEPARATION REQUIRED FOR EELCTRICAL
 CIRCUITING/ BOXES ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-27 Cont ID  
Sent By mcarsill Date 2005-01-27 Time 14:22 Rev Time 0.00
Received By mcarsill Date 2005-01-27 Time 14:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-07 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 15:55 Rev Time 0.00
Received By kstevens Date 2005-01-07 Time 16:27 Sent To  
Notes
2005-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 BUILDING
  
 1) MORE INFORMATION IS REQUIRED FOR PLAN
 REVIEW. APPLICATION DESCRIPTION OF
 PROJECT IN DETAIL STATES "DIVIDE 2 UNITS
 INTO OFFICES". IT SEEMS AS IF THERE IS
 ONE OFFICE ON DRAWING. PLEASE CLARIFY.
 SECTION 104.2.1.
 2) SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1002.1 AND 403.1.
 SHOW SQUARE FOOTAGE OF THE
 SPACE/SPACES.
 A DRINKING FOUNTAIN IS REQUIRED IN EACH
 SPACE.
 3) ALL INFORMATION AND DRAWINGS SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1.
 4) TWO OR MORE COPIES OF SPECIFICATIONS
 AND DRAWINGS DRAWN TO SCALE WITH
 SUFFICIENT CLARITY AND DETAIL TO
 INDICATE THE NATURE AND CHARACTER OF THE
 WORK SHALL ACCOMPANY THE APPLICATION FOR
 PERMIT. SECTION 104.2.1.
 5) FLOOR PLAN INDICATES A KITCHENETTE.
 SUBMIT A DETAIL FOR THE KITCHENETTE
 SHOWING THE LAYOUT OF CABINETS AND
 FIXTURES. IF THERE IS A SINK IN THE
 KITCHENETTE IT SHALL BE ACCESSIBLE AND A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. SECTION
 104.2.1.
 6) IF ANY PLUMBING PIPING IS INSTALLED A
 SANITARY RISER DIAGRAM AND A WATER RISER
 DIAGRAM ARE REQUIRED. SHOW ALL PIPE
 SIZES, CONNECTIONS TO BUILDING DRAIN AND
 BUILDING WATER SUPPLY, VENTS, VALVES,
 WATER HAMMER ARRESTORS ECT. SECTION
 104.3.1.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
2005-01-07 00:00:00TO "COMM BD#51"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-26 Cont ID  
Sent By pkrauss Date 2005-01-26 Time 12:55 Rev Time 0.20
Received By pkrauss Date 2005-01-26 Time 12:50 Sent To  
Notes
2005-01-26 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
 PLEASE PROVIDE PLANS, EQUIPMENT
 SCHEDULE, OUTSIDE AIR CALUCALTIONS AND
 ALL OTHER PERTINENT INFORMATION WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-31 Cont ID  
Sent By kstevens Date 2005-01-31 Time 15:54 Rev Time 0.37
Received By kstevens Date 2005-01-31 Time 15:54 Sent To  
Notes
2005-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 BUILDING
  
 1) MORE INFORMATION IS REQUIRED FOR
 PLAN
 REVIEW. APPLICATION DESCRIPTION OF
 PROJECT IN DETAIL STATES "DIVIDE 2
 UNITS
 INTO OFFICES". IT SEEMS AS IF THERE IS
 ONE OFFICE ON DRAWING. PLEASE CLARIFY.
 SECTION 104.2.1.
 2) SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1002.1 AND 403.1.
 SHOW SQUARE FOOTAGE OF THE
 SPACE/SPACES.
 A DRINKING FOUNTAIN IS REQUIRED IN EACH
 SPACE.
 3) ALL INFORMATION AND DRAWINGS SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1.
 4) TWO OR MORE COPIES OF SPECIFICATIONS
 AND DRAWINGS DRAWN TO SCALE WITH
 SUFFICIENT CLARITY AND DETAIL TO
 INDICATE THE NATURE AND CHARACTER OF
 THE
 WORK SHALL ACCOMPANY THE APPLICATION
 FOR
 PERMIT. SECTION 104.2.1.
 5) FLOOR PLAN INDICATES A KITCHENETTE.
 SUBMIT A DETAIL FOR THE KITCHENETTE
 SHOWING THE LAYOUT OF CABINETS AND
 FIXTURES. IF THERE IS A SINK IN THE
 KITCHENETTE IT SHALL BE ACCESSIBLE AND
 A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. SECTION
 104.2.1.
 6) IF ANY PLUMBING PIPING IS INSTALLED
 A
 SANITARY RISER DIAGRAM AND A WATER
 RISER
 DIAGRAM ARE REQUIRED. SHOW ALL PIPE
 SIZES, CONNECTIONS TO BUILDING DRAIN
 AND
 BUILDING WATER SUPPLY, VENTS, VALVES,
 WATER HAMMER ARRESTORS ECT. SECTION
 104.3.1.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]