Plan Review Details - Permit 04121830
Plan Review Stops For Permit 04121830
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-05-26 Cont ID  
Sent By shill Date 2006-05-26 Time 12:38 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2006-05-26 00:00:00REVISED A3 PER PROVISO

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-04-25 Cont ID  
Sent By shill Date 2005-04-25 Time 11:32 Rev Time 1.00
Received By shill Date 2005-04-25 Time 11:32 Sent To PC
Notes
2005-04-25 00:00:00****PROVISO****
  
 SEPARATE PERMIT FOR FLEETWOOD WINDOWS &
 DOORS
  
 REVISE CONNECTORS, SHEET A3
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-04-22 Cont ID  
Sent By shill Date 2005-04-22 Time 15:22 Rev Time 1.00
Received By shill Date 2005-04-22 Time 15:22 Sent To  
Notes
2005-04-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LISTS, ITEM #11 (FIRST
 REVIEW) AND ITEM #3 (SECOND REVIEW).
 VALUES/FASTENING FOR THE CONNECTORS ARE
 NOT CONSISTENT WITH THE MANUFACTURER'S
 SPECIFICATIONS OR WITH THE FLORIDA
 PRODUCT APPROVAL.AS PER THE ASSISTANT
 BUILDING OFFICIAL, FASTENING SPECIFIED
 IS TO BE CONSISTENT WITH THE FLORIDA
 PRODUCT APPROVAL OR YOU MUST APPLY FOR A
 LOCAL PRODUCT APPROVAL WITH
 CALCULATIONS, FAC9B-72.A NOTE ON THE
 PLAN IS NOT A LOCAL PRODUCT APPROVAL.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FOR THE FLEETWOOD
 WINDOWS & DOORS, FAC9B72.
  
 3.)THE NOC IS EXPIRED, OVER 90 DAYS
 WITHOUT COMMENCING WORK, FS713.13(2).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-28 Cont ID  
Sent By shill Date 2005-03-28 Time 08:26 Rev Time 2.00
Received By shill Date 2005-03-28 Time 08:26 Sent To PC
Notes
2005-03-28 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)FROM PREVIOUS NOTE #4 THE BEDROOM
 IS NOW LABELED "OFFICE", BUT THE PLANS
 ARE STILL LABELED "MODEL NAPA W/GUEST
 HOUSE".TO AVOID CONFUSION, AND AS THIS
 IS A LIFE SAFETY ISSUE (SMOKE
 DETECTORS), PLEASE EITHER REMOVE "GUEST
 HOUSE" REFERENCE FROM PLAN OR INDICATE
 WHICH PART OF THE HOUSE IS THE GUEST
 HOUSE.
  
 2.)SOME OF THE DESIGN STANDARDS WERE
 CHANGED BUT ARE NOT CURRENT OR
 REFERENCED IN THE FBC.SPECIFICALLY,
 ACI-95 (CONCRETE UNIT MASONRY, H AND
 WIND LOADS) SHOULD BE ACI-02.TRUSSES,
 D, REFERS TO TPI85. I WAS UNABLE TO
 LOCATE PCT80 AND BWT76 ON THE TPI
 WEBSITE.ARE THEY PRODUCED BY ANOTHER
 ORGANIZATION?PLEASE SEE BCSI 1 BY TPI
 WHICH ADDRESSES BRACING AND DESIGN.
 PLEASE CHECK ALL STANDARDS, FBC35.
  
 3.)SEE PREVIOUS LIST, ITEM #11.
 NAILING CONFLICTS WITH THE CATALOG.
 VALUES USED SHOULD BE CONSISTENT WITH
 THE PAPERWORK ON THE FLORIDA WEBSITE
 WWW.FLORIDABUILDING.ORG.IF FASTENING
 SPECIFIED IS NOT CONSISTENT WITH
 MANUFACTURER'S SPECIFICATION, APPLY FOR
 A LOCAL PRODUCT APPROVAL PURSUANT TO
 FAC9B72 WITH CALCULATIONS AS PER
 ASSISTANT BUILDING OFFICIAL.
  
 4.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FOR THE FLEETWOOD
 WINDOWS & DOORS, FAC9B72.
 WWW.FLORIDABUILDING.ORG

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-02 Cont ID  
Sent By shill Date 2005-02-02 Time 14:19 Rev Time 4.00
Received By shill Date 2005-02-01 Time 13:12 Sent To PC
Notes
2005-02-02 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE OWNER INFORMATION DOESN'T
 MATCH
 OUR RECORDS.
  
 2.)THE NOC IS EXPIRED, MORE THAN 90
 DAYS WITHOUT COMMENCING WORK,
 FS713.13(2).
  
 3.)A3, THE NOTE REGARDING THE 10# LL
 IS NOT IN COMPLIANCE WITH FBC TABLE
 1604.1.ATTICS WITH STORAGE ARE TO
 HAVE
 A 30# BCLL.ROOF FRAMING PLAN SHOWS
 10#
 FOR STORAGE AREAS (TWO NOTES).
  
 4.)THE FLOOR PLAN SHOWS THE ROOM
 ADJACENT TO THE CABANA AS AN OFFICE,
 ROOF FRAMING PLAN SHOWS IT AS A GUEST
 ROOM.IS THIS AREA THE "GUEST HOUSE"
 REFERRED TO ON THE PLAN?SLEEPING
 ROOMS
 ARE TO HAVE SMOKE DETECTORS IN
 COMPLIANCE WITH FBC 905.2.2.
  
 5.)THE TWO SETS OF PLANS SUBMITTED
 HAVE DIFFERENT SIGNATURES AND DATES.
  
 6.)SHEET T1, CONCRETE UNIT MASONRY, H
 REFERS TO A CODE FOR HVHZ.CITY OF WPB
 IS NOT IN THE HVHZ.PLEASE CORRECT
 REFERENCES (ACI REFERENCES ARE
 DIFFERENT
 FOR HVHZ AS WELL).
  
 7.SHEET T1, WIND LOADS (DESIGN
 PARAMETERS), REFERS TO A STANDARD FOR
 WOOD CONSTRUCTION WHICH I AM UNABLE TO
 LOCATE IN THE FBC.
  
 8.)A6, KNEE WALL ON GIRDER TRUSS,
 REFERS TO HUGHES CONNECTORS.THEY HAVE
 BEEN OUT OF BUSINESS FOR YEARS.
 SPECIFY
 ONLY AVAILABLE PRODUCTS.
  
 9.)A3 (AT GARAGE) REFERS TO AHU
 INSTALLATION DETAIL ON SHEET 9, BUT
 THERE IS NO SHEET 9.
  
 10.) ROUGH CARPENTRY NOTES (U), SHEET
 T1, SPECIFIES 5/8" PLYWOOD WHICH
 CONFLICTS WITH THE DETAILS.
  
 11.) A3, USP ANCHOR SCHEDULE, HTA20,
 NAILING CONFLICTS WITH CATALOG.
 ALLOWABLE LATERAL LOAD ON PLAN EXCEED
 PRODUCT LIMITATIONS.CHECK ALL
 CONNECTORS.
  
 12.)FLORIDA OR LOCAL PRODUCT
 APPROVALS
 REQUIRED FOR ALL PRODUCTS, USP ANCHOR
 SCHEDULE.SOME REFER TO NOAS.
 WWW.FLORIDABUILDING.ORG.
  
 13.) THERE ARE NOTES ON THE FLOOR PLAN
 FOR TEMPERED GLASS, BUT ANOTHER NOTE ON
 THE PLAN INDICATES THAT ALL WINDOWS
 WILL
 BE IMPACT.SOME PRODUCT APPROVALS
 SUBMITTED ARE FOR NONIMPACT PRODUCTS.
 ADDRESS.FOR PRODUCT APPROVALS
 COVERING
 SEVERAL PRODUCTS, INDICATE THE PRODUCT
 YOU ARE USING.
  
 14.)IMPACT PROTECTIONS REQUIRED
 FBC1606.1.4.IF GLAZING IS NOT IMPACT,
 PROVIDE PRODUCT APPROVALS AND HURRICANE
 SHUTTER INSTALLATION SCHEDULE OR A
 SEPARATE PERMIT FOR SHUTTERS WILL BE
 REQUIRED.CHANGE THE NOTES ON THE
 PLAN.
  
 15.)THE GARAGE JAMB DETAIL, A6,
 CONFLICTS WITH THE PRODUCT APPROVAL.
  
 16.)A6, WINDOW & SGD JAMB DETAIL,
 SPECIFY BUCK ATTACHMENT (LENGTH).
  
 17.)THE PLAN SPECIFIES CLAY BARREL
 TILE (A6), PRODUCT APPROVAL SUBMITTED
 IS
 FOR CONCRETE TILE.
  
 18.)THE TEST REPORT FOR THE ENTRY IS
 FOR GLAZED AND OPAQUE DOORS.
 FBC1005.4.5 REQUIRES A MEANS OF ESCAPE
 IN THE EVENT OF TEMPORARY INSTALLATION
 OF HURRICANE PROTECTION.IS THE FRONT
 DOOR GLAZED OR OPAQUE?
  
 19.)CASEMENT WINDOWS IN A 26 SIZE
 WERE
 SPECIFIED ON THE PLAN; PGT IMPACT
 PRODUCT APPROVALS SUBMITTED.THE
 WINDOWS ARE UNAVAILABLE IN THIS SIZE.
 ADDRESS.
  
 20.)FAC9B72, FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED FOR ALL
 PRODUCTS.WWW.FLORIDABUILDING.ORG
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-05-09 Cont ID  
Sent By dpalmer Date 2006-05-09 Time 19:54 Rev Time 0.00
Received By dpalmer Date 2006-05-09 Time 19:54 Sent To PC
Notes
2006-05-09 00:00:00REVISIONS FOR BLDG AND PLUMB FOR LOT #5
 ALSO SUBMITTED WITH ELECTRICAL REV'S.??

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-12-24 Cont ID  
Sent By dpalmer Date 2005-12-24 Time 06:50 Rev Time 0.00
Received By dpalmer Date 2005-12-24 Time 06:39 Sent To  
Notes
2005-12-24 00:00:00*** PROVISO ***
  
 1)NOTE: PLEASE CORRELATE RISER FOR SUB
 PANEL "C" WITH PANEL SCHEDULE "B".
 PLEASE SEE PANEL SCHEDULE "B" INDICATE
 3#6'S AND 1#6 GRND, HOWEVER RISER SHOWS
 3#4'S AND 1#6 GRND.
  
 PLEASE REVISE BEFORE FINAL ELECTRICAL
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-12-07 Cont ID  
Sent By dpalmer Date 2005-12-07 Time 17:12 Rev Time 0.75
Received By dpalmer Date 2005-12-07 Time 14:57 Sent To  
Notes
2005-12-07 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE FOUNTAIN PUMP SHOWN
 WITH 20A OCP ON #14.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 FOR POOL PANEL AND PANEL "B" WITH RISER
 DIAGRAM.
 PLEASE SEE PANEL "B" SHOWS 100A OCP AND
 #2 TO POOL PANEL. POOL PANEL ON RISER IS
 SHOWN AS 80A OCP AND #4 AND POOL PANEL
 SCHEDULE SHOWS 60A ??
 215.5
  
 3)NOTE: PLEASE SEE WARMING DRAWER SHOWN
 ON PLANS, YET THIS IS NOT ON PANEL
 SCHEDULE OR ADDED TO LOAD CALCS.
 215.5
  
 4)NOTE: PLEASE SEE SD IN MASTER BEDRM IS
 REQUIRED TO BE WITHIN 12"OF THE HIGHEST
 POINT OF A FLAT CEILING.
 PLEASE KNOW, IF TRAT CEILING IS 12" OR
 MORE ABOVE OTHER CEILING IN RM, THE SD
 WILL BE REQUIRED TO BE LOCATED IN TRAY
 CEILING AREA.
 NFPA-72 11.8.3.5
  
 5)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THE # IN LOAD
 CALCS ETC.
 PLEASE SEE LOAD CALCS INDICATE A TOTAL
 OF 84, HOWEVER THERE ARE 125+
 PLEASE ADJUST.
 220.3B4
  
 6)NOTE: PLEASE CLARIFY NOTE FOR ALL
 "OUTLETS " IN BEDRMS TO HAVE ARC FAULT
 PROTECTION. THIS INCLUDES , SD', FANS,
 LTS, AND RECEPTS.
 2002 NEC 210.12
 IT IS KNOWN THAT THE RECEPTS ARE SHOWN
 AS AFCI, HOWEVER A AFCI RECEPT IS NOT
 KNOWN TO BE MADE AT THIS TIME.
  
 7)NOTE: PLEASE SHOW LOCATION OF POOL
 PANEL ON PLANS.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-12 Cont ID  
Sent By dpalmer Date 2005-04-12 Time 18:14 Rev Time 0.50
Received By dpalmer Date 2005-04-12 Time 18:14 Sent To P
Notes
2005-04-12 00:00:00PLANS REDLINED
  
 PLEASE SEE MISSING RECEPT PER 210.52
  
 PLEASE SEE NEW SUB-PANEL "C" IS NOT
 SHOWN ON PLANS FOR LOCATION??
  
 PLEASE REVISE WITH ANY OTHER CHANGES
 BEFORE ROUGH ELECTRICAL INSPECTION.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-21 Cont ID  
Sent By dpalmer Date 2005-03-21 Time 08:35 Rev Time 0.50
Received By dpalmer Date 2005-03-18 Time 11:50 Sent To P
Notes
2005-03-21 00:00:00*********UNSAT *******
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW.
  
 1)NOTE: NOTE #1, NO PLEASE CORRELATE
 RISER DIAGRAM AND PANELS.
 PLEASE SEE PANEL "A" IS SHOWN FEEDING
 SUB-PANEL "C" , RISER SHOWS PANEL "B"?
 PLEASE SEE PANEL "C" IS SHOWN AS 80A
 AND RISER SHOWS AS 150A?
 PLEASE SEE RISER MENTIONS FEED FOR SUB
 PANEL WITH 4#12'S ALONG WITH FEEDER??
  
 2)NOTE: PLEASE SEE FOUNTAIN PUMP SHOWN
 AS 2P20 ON #14 AWG.
  
 3)NOTE: PLEASE SEE BLOWER IS SHOWN AS
 GAS FOR POOL??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-03-18 00:00:00IN FOR REVIEW. PLANS UNSAT, NOTES TO
 FOLLOW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-05 Cont ID  
Sent By dpalmer Date 2005-01-05 Time 14:18 Rev Time 0.75
Received By dpalmer Date 2005-01-05 Time 14:18 Sent To M
Notes
2005-01-05 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE RISER AND
 PANELS, PANEL "A" SHOWN AS 150A AND
 200A
 ON RISER.
 PLEASE ALSE SEE PLANS INDICATE A MAIN
 DISC ON THE OUTSIDE OF DWELLING, YET
 RISER DOES NOT CONFRIM THIS.?
 215.5
  
 2)NOTE: PLEASE SEE 250.66,310.15B6 FOR
 MIN SIZE GROUNDING ELECTRODE CONDUCTOR.
  
 1/0 MIN.
  
 3)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES A WHIRLPOOL TUB, HOWEVER,
 PLANS DO NOT INDICATE ANY GFI FOR THIS
 AT WHAT APPEARS TO BE WP TUB AT MASTER
 BATH LOCATION.
 215.5
  
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE MISSING REDLINED.
  
 4)NOTE: PLEASE SEE 210.70 FOR REQUIRED
 LT FOR AHU/ EQUIPMENT IN ATTIC.
  
 5)NOTE: PLEASE SEE MISSING RECEPT(S)
 PER
 210.52
  
 6)NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR KITCHEN ISLAND. PER 210.52C2AT
 LEAST
 ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED
 AT EACH ISLAND COUNTER SPACE WITH A
 LONG
 DIMENSION OF 600 MM (24 IN.) OR GREATER
 AND A SHORT DIMENSION OF 300 MM (12
 IN.)
 OR GREATER.
  
 7)NOTE: PLEASE SEE 220.3B4 AN OUTLET
 SUPPLYING RECESSED LUMINAIRE(S)
 [LIGHTING FIXTURE(S)] SHALL BE COMPUTED
 BASED ON THE MAXIMUM VOLT-AMPERE RATING
 OF THE EQUIPMENT AND LAMPS FOR WHICH
 THE
 LUMINAIRE(S) [FIXTURE(S)] IS RATED.
  
 8)NOTE: PLEASE VERIFY OCP FOR 7.5KW
 AHU#3, SHOWN AS 60A. ONLY A NOTE:
  
 PLEASE SEE ONE SET OF PLANS HAVE BEEN
 REDLINED FOR AREAS OF NOTES AND
 LOCATIONS FOR SOME OF THE ITEMS LISTED
 ABOVE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-05-16 Cont ID  
Sent By adarroug Date 2006-05-12 Time 16:32 Rev Time 0.00
Received By adarroug Date 2006-05-12 Time 16:32 Sent To P
Notes
2006-05-16 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-05-03 Cont ID  
Sent By adarroug Date 2006-05-03 Time 14:23 Rev Time 0.00
Received By adarroug Date 2006-05-03 Time 14:23 Sent To E
Notes
2006-05-03 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-19 Cont ID  
Sent By adarroug Date 2005-12-19 Time 14:13 Rev Time 0.00
Received By adarroug Date 2005-12-19 Time 14:13 Sent To E
Notes
2005-12-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-28 Cont ID  
Sent By adarroug Date 2005-11-28 Time 15:49 Rev Time 0.00
Received By adarroug Date 2005-11-28 Time 15:49 Sent To E
Notes
2005-11-28 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-07 Cont ID  
Sent By adarroug Date 2005-04-07 Time 10:53 Rev Time 0.00
Received By adarroug Date 2005-04-07 Time 10:53 Sent To E
Notes
2005-04-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 14:10 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 14:10 Sent To E
Notes
2005-03-17 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-04 Cont ID  
Sent By mjacobs Date 2005-01-04 Time 15:17 Rev Time 0.00
Received By mjacobs Date 2005-01-04 Time 15:17 Sent To E
Notes
2005-01-04 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-01 Cont ID  
Sent By mjacobs Date 2005-02-02 Time 15:51 Rev Time 0.00
Received By shill Date 2005-01-03 Time 15:51 Sent To  
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-04-21 Cont ID  
Sent By prafter Date 2005-04-21 Time 11:59 Rev Time 1.00
Received By prafter Date 2005-04-21 Time 11:59 Sent To B
Notes
2005-04-21 00:00:00THIRD MECH. PLAN REVIEW.
 PROVISOS. 1. AND 2. SATIFIED, REFLECTED
 ON A/C PLANS.
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By prafter Date 2005-01-10 Time 14:48 Rev Time 0.00
Received By prafter Date 2005-01-10 Time 11:13 Sent To P
Notes
2005-01-10 00:00:00PROVISO: #1 R/A OUT OF CLUB ROOM MUST
 BE EQUEAL TO SUPPLY AIR. 2001 F.B.C./M
 601.4 .
 #2. HER BATH MUST CONFORM WITH 2001
 F.B.C./M 402.3.1 FOR EXHAUST FAN .
 PAT RAFTER 561/805/6725 OR 8056719 .

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-05-22 Cont ID  
Sent By mperson Date 2006-05-22 Time 15:00 Rev Time 1.00
Received By mperson Date 2006-05-22 Time 15:00 Sent To M
Notes
2006-05-22 00:00:00REVISION: AS BUILT SANITARY PLUMBING
 RISER DIAGRAM
  
 ******PROVISO******
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. NOTE: WASHING
 MACHINE CLEANOUT SHALL BE 4' ABOVE
 FINNISH FLOOR.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-04-19 Cont ID  
Sent By kstevens Date 2005-04-19 Time 18:32 Rev Time 0.25
Received By kstevens Date 2005-04-19 Time 18:32 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-26 Cont ID  
Sent By kstevens Date 2005-03-26 Time 17:56 Rev Time 0.60
Received By kstevens Date 2005-03-26 Time 17:56 Sent To B1
Notes
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A) SHT A6 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLANS.
 1) RISER INDICATES "TO SEPTIC TANK"
 SEPTIC TANKS ARE NOT APPROVED. CITY
 SEWER SYSTEM AVAILABLE.
 2) FOR W/M TRAP TO CONNECT TO STACK
 DOWN LOW AND HAVE A MINIMUM 2' STANDPIPE
 AND THE CLEANOUT SHALL BE 4' ABOVE THE
 FLOOR FOR ACCESS. SECTIONS 1002.1 AND
 708.10.
 3) BIDET TRAP SHALL BE UNDER THE SLAB,
 NOT ABOVE THE FLOOR AS SHOWN. SECTION
 104.2.1.
 4) SINK DOWNSTREAM OF "HIS" BATHROOM IS
 NOT SHOWN ON THE FLOOR PLAN. SECTION
 104.2.1.
 (SEE RED LINE CORRECTIONS ON ONE SET OF
 PLANS).
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-11 Cont ID  
Sent By jleech Date 2005-01-11 Time 15:48 Rev Time 1.00
Received By jleech Date 2005-01-11 Time 15:48 Sent To B
Notes
2005-01-11 00:00:00DENIED;
 1.W/M REQUIRES IT'S ON DRAIN AND VENT.
 NOT ON SAME WALL.
 2.PAGE T-1 CONSTRUCTION NOTES PLUMBING.
 CHANGE TO ALL SHOWER VALVES, NOT SHOWER
 HEADS.
 3.BATHROOM 3 SHOW LAV ARM AND TRAP.
 4.BATHROOM 4 FLOOR PLAN SHOWS TUB RISER
 DIAGRAM SHOWS SHOWER.
 5.BAR SINK ON RISER DIAGRAM IS NOT TO
 FLOOR PLAN. SEE RED LINES ON RISER
 DIAGRAM.
 6.DISHWASHER TO DRAIN UNDER KITCHEN SINK
 NOT TO WET VENT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-04 Cont ID  
Sent By mmclean Date 2005-01-04 Time 14:18 Rev Time 0.00
Received By mmclean Date 2005-01-04 Time 14:18 Sent To I
Notes
***NONE***