2005-02-01 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04121765 |
| ADD: 6830 SPARROW HAWK DRIVE |
| CONT: THE RIF GROUP |
| TEL: (561)239-5790 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICATION PAGE WHERE THE CHANGES |
| CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT.THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) PROVIDE IMPACT FEE RECEIPT FOR THIS |
| PLAN. |
| |
| 3) PERMIT APPLICATION INDICATES THE SQ |
| FT AS 3,734 SQ FT, IN ACTUALLITY IT IS |
| 4,627 SQ FT. ADDITIONAL FEES OF $8.94 |
| DUE FOR STATE RADON FEES. |
| |
| 4) FBC 13-103.1.2 BEFORE A BUILDING |
| PERMIT CAN BE ISSUED, THE SUBMITTED |
| ENERGY CODE COMPLIANCE FORMS SHALL BE |
| SIGNED BY THE BUILDING OWNER, THE |
| OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| AGENT LEGALLY DESIGNATED BY THE OWNER. |
| |
| 5) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| WHERE THE BEARING CAPACITY OF THE SOIL |
| IS NOT DEFINITLY KNOWN OR IS IN |
| QUESTION THE BUILDING OFFICIAL MAY |
| REQUIRE EXPLORATIONS, TEST OR OTHER |
| ADEQUATE PROOF AS TO THE PERMISSIBLE |
| SAFE BEARING CAPACITY. REQUIRED TEST AND |
| RECOMMENDATIONS SUBMITTED TO VERIFY |
| BEARING CAPACITY SHALL BE CERTIFIED BY A |
| GEOTECHNICALREPORT FROM A DESIGN |
| PROFESSIONAL PROPERLY LICENSED IN THE |
| STATE OF FLORIDA. |
| |
| 6) COVERSHEET TYPE OF CONSTRUCTION |
| INDICATES THIS STRUCTURE IS TO BE FIRE |
| SPRINKLERED, PROVIDE PLANS. |
| |
| 7)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| SHEET A-6 GENERAL NOTE# 9, INDICATES |
| COMPLIANCE WITH TERMITE TREATMENT AND |
| REFRENCES 1042.7 FBC CHAPTER 10 DEALS |
| WITH MEANS OF EGRESS, THE LAST CHAPTER |
| IS 1029, EXPLAIN? |
| |
| 8) THE SAME SHEET NOTE# 13 DEALS WITH |
| COMPLIANCE WITH STORM SHUTTERS BUT |
| REFREENCES CODE SECTIONS DEALING WITH |
| HIGH VELOCITY HURRICANE ZONES THAT ARE |
| ONLY APPLICABLE TO DADE OR BROWARD |
| COUNTIES, PLEASE CORRECT. |
| |
| 9) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A)STORM SHUTTERS |
| B)NUVUE TRUSS ANCHORS |
| |
| 10)) FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE |
| INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL |
| PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 11) PLANS DO NOT INDICATE MEANS OF |
| ESCAPE WHEN STORM SHUTTERS ARE IN |
| PLACE. |
| FBC 1005.4.5 (GLITCH AMENDMENTS JULY 1, |
| 2003) REQUIRES AT LEAST ONE MEANS OF |
| ESCAPE FROM A DWELLING WHEN SHUTTERED |
| FOR IMPACT PROTECTION. THE MEANS OF |
| ESCAPE SHALL BE WITHIN THE FIRST FLOOR |
| OF THE DWELLING AND CAN NOT BE LOCATED |
| IN A GARAGE. OCCUPANTS IN ANY PART OF |
| THE DWELLING SHALL HAVE ACCESS TO IT |
| WITHOUT HAVING TO PASS THROUGH A |
| LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| INDICATE HOW COMPLIANCE WILL BE |
| ACHIEVED. |
| |
| 12) 1606.4.4 ANCHOR METHODS. PROVIDE |
| INFORMATION FOR INSTALLATION OF DOOR |
| AND WINDOW BUCKS. SHEET A-6 WINDOW |
| DETAILS INDICATE "FASTENERS THRU BUCK |
| AS |
| PER MANUFACTURERS PRODUCT APPROVAL". |
| THE |
| SIMONTON WINDOWS FIXED AND SINGLE HUNG |
| WINDOWS INDICATE TEST INSTALATION OF |
| FAASTENER ONLY INTO BUCK. DESIGN |
| PROFESSIONAL TO PROVIDE BUCK |
| ATTACHMENT. |
| |
| 13) S-1 CONCRETE NOTES MENTION ACI 301 |
| BUT NOTHING IS MENTIONED ABOUT ACI |
| 318-02 FOR STRUCTURAL CONCRETE? |
| |
| 14) S-2 2ND FLOOR, FLOOR FRAMING |
| DOESN'T |
| INDICATE DRAFT STOPPING LOCATIONS: |
| 2305.2.2 FLOOR/CEILING ASSEMBLIES |
| SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/ |
| ING ASSEMBLIES SEPERATING USEABLE SPACE |
| INTO 2 OR MORE APPROXIMATE AREAS WITH |
| NO |
| AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| PING SHALL BE PROVIDED PARALLEL TO THE |
| MAIN FRAMING MEMBERS. |
| |
| 15) S-3 TRUSS ANCHOR SCHEDULE, HIGH |
| VALUE FOR USP RT16T, SEE 205 USP |
| CATALOG |
| PAGE 86 GOOD FOR 1225 LBS UPLIFT. |
| |
| 16) 1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 17) PLANS, SPECIFICATIONS,REPORTS OR |
| OTHER DOCUMENTS PREPARED BY THE DESIGN |
| PROFESSIONAL AND BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| FL ATATE STAT: 61G16.003 ARCHITECTS |
| 17A) THE PERSONAL SEAL, SIGNATURE AND |
| DATE OF THE ARCHITECT SHALL APPEAR ON |
| ALL ARCHITECTURAL DOCUMENTS TO BE FILED |
| FOR PUBLIC RECORD. PROVIDE COMPLETE |
| SIGNATURE. |
| 17B)FL S S 481.219(2)&(3) & |
| 61G1-16.004(2) |
| WHEN THE TERM "ARCHITECTS" IS INDICATED |
| IN THE TITLE BLOCK A "CA" CERTIFICATE OF |
| AUTHORIZATION IS REQUIRED ALSO IN THE |
| TITLE BLOCK. |
| |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |