Plan Review Details - Permit 04121708
Plan Review Stops For Permit 04121708
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-01-13 Cont ID  
Sent By alange Date 2005-01-13 Time 13:42 Rev Time 0.75
Received By alange Date 2005-01-13 Time 13:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-12-30 Cont ID  
Sent By dpalmer Date 2004-12-30 Time 18:12 Rev Time 0.25
Received By dpalmer Date 2004-12-30 Time 18:12 Sent To P
Notes
2004-12-30 00:00:00REDLINED 210.8A6
 ALL RECEPTS SERVING KITCHEN COUNTERSPACE
 ARE TO BE GFI/GFI PROTECTED.
  
 REDLINED POSSIBLE RECEPTS PER 210.52 IN
 DINING RM. FIELD VERIFY BY INSPECT.
  
 PLANS STAMPED, DO NOT NEED TO BE
 REVISED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-28 Cont ID  
Sent By mjacobs Date 2004-12-28 Time 15:46 Rev Time 0.00
Received By mjacobs Date 2004-12-28 Time 15:46 Sent To E
Notes
2004-12-28 00:00:00TO "E" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By pkrauss Date 2005-01-10 Time 07:58 Rev Time 0.30
Received By pkrauss Date 2005-01-10 Time 07:48 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-01 Cont ID  
Sent By jleech Date 2005-01-01 Time 14:22 Rev Time 0.33
Received By jleech Date 2005-01-01 Time 14:22 Sent To M
Notes
2005-01-01 00:00:00FIXTURE CHANGEOUT ONLY