Plan Review Details - Permit 04121034
Plan Review Stops For Permit 04121034
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-16 Cont ID  
Sent By lsmith Date 2005-03-16 Time 15:59 Rev Time 0.50
Received By lsmith Date 2005-03-16 Time 15:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-17 Cont ID  
Sent By lsmith Date 2005-02-17 Time 08:34 Rev Time 0.75
Received By lsmith Date 2005-02-17 Time 08:34 Sent To  
Notes
2005-02-17 00:00:00BUILDING PLAN REVIEW: PROVISO
  
 1. HIGHLIGHT THE STORM PANEL DRAWINGS
 SHOWING THE METHOD OF ATTACHMENT TO
 HOUSE. SHOW WHAT TYPE OF ANCHORS & TYPE
 OF EXTERIOR WALLS.
  
 2. LOCAL PRODUCT APPROVAL HAS BEEN
 OBTAINED FOR THE SERIES 650 & 660 DEVAC
 MODEL WINDOWS. REMOVE ALL REFERENCES FOR
 MODELS OF WINDOWS NOT BEING INSTALLED IN
 THIS HOUSE. PLANS SHOW THE 660 WINDOWS
 ARE TO BE INSTALLED.
  
 3.DO NOT STAPLE PACKAGES. INDIVIDUAL
 STAPLED PAPERS LIKE PRODUCT APPROVALS
 ARE OKAY. DO NOT USE THE LARGE STAPLES
 THROUGH ALL THE PAPERS.
  
 4. SEE MECH. & ELEC. REVIEWERS NOTES.
 THESE MUST BE CORRECTED BEFORE A PERMIT
 CAN BE ISSUED.
  
 ANY QUESTIONS PLEASE CALL
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-06 Cont ID  
Sent By lsmith Date 2005-01-06 Time 11:09 Rev Time 1.00
Received By lsmith Date 2005-01-06 Time 11:09 Sent To  
Notes
2005-01-06 00:00:00BUILDING PLAN REVIEW: FAILED:
  
  
 1. PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 NEED
 FLORIDA PRODUCT APPROVALS FOR THE
 FOLLOWING:
 DOORS, WINDOWS & STORM PANELS
  
 2.SUBMIT DADE COUNTY PRODUCT APPROVALS
 FOR THE
 WINDOWS.
  
 3. THE WINDOW DRAWINGS BY DONALD W.
 SHACKELFORD P.E. SHOW WINDOW#15 AS 39
 ' X 38". THE PLANS WINDOW SCHEDULE
 SHOWS THE WINDOW TO BE 40" X 38".
  
 3. SEE ELECTRICAL COMMENTS REGARDING
 SEAL & SIGNATURE REQUIREMENTS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLAN REVIEW
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-03 Cont ID  
Sent By dpalmer Date 2005-03-03 Time 16:57 Rev Time 0.20
Received By dpalmer Date 2005-03-03 Time 16:57 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-14 Cont ID  
Sent By dpalmer Date 2005-02-14 Time 15:23 Rev Time 0.30
Received By dpalmer Date 2005-02-14 Time 15:23 Sent To M
Notes
2005-02-14 00:00:00******** UNSAT2ND REVIEW ***********
  
 1)NOTE; PLEASE SEE NOTES #1FROM
 PREVIOUS REVIEW.
 PLEASE PROVIDE LICENSE #'S AS REQUIRED
 PER FAC AND FS.
  
 PLEASE SEE STRUCTUAL CALCS WHICH ARE
 PHOTO -COPIES OF SIGNATURE.
 PLEASE SEE THERE ARE ALSO WHAT APPEARS
 TO BE COPIES OF TWO DIFFERENT
 SIGNATURES.
 SEE BLDG REVIEW NOTES. MUST BE ORIGINAL
 SIGNATURE. 471.025
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-28 Cont ID  
Sent By dpalmer Date 2004-12-28 Time 09:12 Rev Time 0.33
Received By dpalmer Date 2004-12-28 Time 09:12 Sent To M
Notes
2004-12-28 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 FAC 61G15-23.002 FOR MISSING LICENSE
 INFORMATION FOR ARCHITECTS AND
 ENGINEERINGFIRM PER FS 481.219,
 471.023.
 THIS INFORMATION IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLANS WHICH CONTAIN THE TITLE
 BLOCK FOR ENGINEER RESPONSIBLE FOR
 PLANS/DESIGN, MUST SIGN, DATE AND SEAL
 PLANS. FS 471.025
  
 3)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCUALTIONS.
  
 4)NOTE: PLEASE INDICATE EXISTING MCB
 SIZE.
  
  
 **PLEASE NOTE***
 PLANS MENTIONS KNOB AND TUBE WIRING
 PRESENT.
 UPON SERVICE CHANGE, IF KNOB AND TUBE
 IS
 STILL PRESENT THEN, THE CONNECTION OF
 THESE CIRCUITS WILL NOT BE PERMITTED.
 RE-WIRE MUST BE PERMITTED AND COMPLETE
 BEFORE CALLING IN FINALS FOR PERMITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-02 Cont ID  
Sent By adarroug Date 2005-03-02 Time 17:41 Rev Time 0.00
Received By adarroug Date 2005-03-02 Time 17:41 Sent To E
Notes
2005-03-02 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 10:39 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 10:39 Sent To E
Notes
2005-02-09 00:00:00TO DPALMER DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-21 Cont ID  
Sent By mjacobs Date 2004-12-21 Time 11:58 Rev Time 0.00
Received By mjacobs Date 2004-12-21 Time 11:58 Sent To E
Notes
2004-12-21 00:00:00SENT TO "E" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-03-15 Cont ID  
Sent By pkrauss Date 2005-03-15 Time 14:31 Rev Time 0.30
Received By pkrauss Date 2005-03-15 Time 14:31 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-02-15 Cont ID  
Sent By prafter Date 2005-02-15 Time 10:38 Rev Time 0.45
Received By prafter Date 2005-02-15 Time 10:38 Sent To B
Notes
2005-02-15 00:00:00SECOND MECH. A/C REVIEW:
  
 THERES BEN NO CORRECTIONS TO MECH.A/C
 PLANS. CORRECTIONS MUST BE REFLECTED ON
 PLANS.
 PAT RAFTER 561/805/6728 .
 PLEASE CALL IF THEARS ENY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-03-16 Cont ID  
Sent By pkrauss Date 2005-01-21 Time 08:41 Rev Time 0.25
Received By lsmith Date 2005-01-21 Time 08:41 Sent To  
Notes
2005-03-16 00:00:00SEE PK NOTES FOR THIS STOP. HAD TO ENTER
 AN "N" TO PRINT PERMIT LS
2005-01-21 00:00:00NOT A REVIEW PER CONVERSATION W/DAVID
 JONES - THE DOOR TO THE DEN AREA IS A
 FULL LOUVERED DOOR AND THERFORE A RETURN
 AIR JUMPER IS NOT REQUIRED.MECHANICAL
 CLOSET IN THE DOOR ALSO IS LOUVERED.
 BEDROOMS A 1 1/2" DOOR UNDERCUT.HOUSE
 IS EXISTING FLAT ROOF.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-05 Cont ID  
Sent By prafter Date 2005-01-05 Time 11:23 Rev Time 0.45
Received By prafter Date 2005-01-05 Time 11:22 Sent To B
Notes
2005-01-05 00:00:001. RETURN AIR TO A.H.U. MUST BE FROM
 FAMILY /LIVING AREA OF HOUSE ,NOT
 THROUGH NED AREA. 2001 FBC/M 601.4
 BALANCED RETURN AIR .
 2. BEDROOM TWO MUST HAVE RETURN AIR
 OUT OF ROOM .2001 FBC/M 601.4 .
 PAT RAFTER 561/805/6725OR 8056719 .