Plan Review Stops For Permit 04121033 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2005-03-01 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2005-03-01 |
Time |
10:18 |
Rev Time |
1.50 |
Received By |
mjacobs |
Date |
2005-03-01 |
Time |
10:18 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-02-17 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-02-17 |
Time |
13:24 |
Rev Time |
0.33 |
Received By |
alange |
Date |
2005-02-17 |
Time |
13:19 |
Sent To |
|
|
Notes |
2005-02-17 00:00:00 | DENIED | | | | SEE ELECTRICAL REVIEW NOTES REGARDING | | SIGNING AND SEALING DOCUMENTS REQUIRED | | BEFORE ISSUING OF THIS PERMIT. | | BUILDING REVIEW IS OK. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-01-06 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2005-01-06 |
Time |
10:44 |
Rev Time |
1.00 |
Received By |
lsmith |
Date |
2005-01-06 |
Time |
10:44 |
Sent To |
|
|
Notes |
2005-01-06 00:00:00 | BUILDING PLAN REVIEW FAILED: | | | | | | 1.PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | SUBMIT THE FLORIDA PRODUCT APPROVALS FOR | | THE WINDOWS, DOORS & STORM PANELS. | | | | 2. THE WINDOW DRAWINGS BY DONALD W, | | SHACKELFORD P.E. SHOWS WINDOW #5 AS 26" | | X 51". THE WINDOW SCHEDULE ON THE PLANS | | SHOW THE WINDOW # 5 TO BE 27" X 51. | | | | 3. SEE ELECTRICAL NOTES REGARDING THE | | SEAL & SIGNATURE REQUIREMENT, | | | | ANY QUESTIONS PLEASE CALL: | | LEA SMITH, BUILDING PLANS EXAMINER | | 805-6713 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2005-02-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-02-24 |
Time |
15:22 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2005-02-24 |
Time |
15:22 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2005-02-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-02-14 |
Time |
16:36 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2005-02-14 |
Time |
16:36 |
Sent To |
M |
|
Notes |
2005-02-14 00:00:00 | ******** UNSAT2ND REVIEW *********** | | | | 1)NOTE; PLEASE SEE NOTES #1FROM | | PREVIOUS REVIEW. | | PLEASE PROVIDE LICENSE #'S AS REQUIRED | | PER FAC AND FS. | | | | PLEASE SEE STRUCTUAL CALCS WHICH ARE | | PHOTO -COPIES OF SIGNATURE. | | | | SEE BLDG REVIEW NOTES. MUST BE ORIGINAL | | SIGNATURE. 471.025 | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-12-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-12-28 |
Time |
08:47 |
Rev Time |
0.30 |
Received By |
dpalmer |
Date |
2004-12-28 |
Time |
08:47 |
Sent To |
M |
|
Notes |
2004-12-28 00:00:00 | **************** UNSAT ************* | | | | 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND | | FAC 61G15-23.002 FOR MISSING LICENSE | | INFORMATION FOR ARCHITECTS AND | | ENGINEERINGFIRM PER FS 481.219, | | 471.023. | | THIS INFORMATION IS REQUIRED FOR ALL | | TRADES AND FOR ALL SHEETS WHEATHER OR | | NOT COMMENT IS MADE BY OTHER | | REVIEWER(S). | | | | 2)NOTE: PLANS WHICH CONTAIN THE TITLE | | BLOCK FOR ENGINEER RESPONSIBLE FOR | | PLANS/DESIGN, MUST SIGN, DATE AND SEAL | | PLANS. FS 471.025 | | | | 3)NOTE: PLEASE SEE 220.31B FOR LOAD | | CALCUALTIONS. | | | | 4)NOTE: PLEASE SEE MISSING EQUIPMENT | | GROUNDING CONDUCTOR FROM MAIN HOUSE TO | | APT PANEL. PLEASE ALSO INCLUDE GROUND | | RODS AND CWP AT DETACHED BLDG. PER | | 250.32 | | | | 5)NOTE: PLEASE SEE 310.15B6 FOR MIN | | SEC'S 240.4B. | | PLEASE ALSO ADJUST GROUNDING ELECTRODE | | CONDUCTOR TO A MIN OF #2. PER 250.66 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-02-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-02-18 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-02-18 |
Time |
14:59 |
Sent To |
E |
|
Notes |
2005-02-18 00:00:00 | TO DPALMER DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-02-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-02-09 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-02-09 |
Time |
10:21 |
Sent To |
E |
|
Notes |
2005-02-09 00:00:00 | TO DPALMER DESK/RESUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-12-21 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2004-12-21 |
Time |
11:57 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2004-12-21 |
Time |
11:57 |
Sent To |
E |
|
Notes |
2004-12-21 00:00:00 | SENT TO "E" BOX. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2005-02-15 |
|
|
Cont ID |
|
Sent By |
prafter |
Date |
2005-02-15 |
Time |
11:19 |
Rev Time |
0.25 |
Received By |
prafter |
Date |
2005-02-15 |
Time |
11:19 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2005-01-05 |
|
|
Cont ID |
|
Sent By |
prafter |
Date |
2005-01-05 |
Time |
11:16 |
Rev Time |
0.45 |
Received By |
prafter |
Date |
2005-01-05 |
Time |
11:16 |
Sent To |
B |
|
Notes |
2005-01-06 00:00:00 | BUILDING PLAN REVIEW: FAILED: | | | | | | 1. PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, | | 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR | | INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | NEED | | FLORIDA PRODUCT APPROVALS FOR THE | | FOLLOWING: | | DOORS, WINDOWS & STORM PANELS | | | | 2.SUBMIT PRODUCT APPROVALS FOR THE | | WINDOWS. | | | | 3. THE WINDOW DRAWINGS BY DONALD W. | | SHACKELFORD P.E. SHOW WINDOW #5 AS 26" X | | 51" THE PLANS WINDOW SCHEDULE SHOWS #5 | | TO BE 27" X 51. | | | | 3. SEE ELECTRICAL COMMENTS REGARDING | | SEAL & SIGNATURE REQUIREMENTS. | | | | ANY QUESTIONS PLEASE CALL: | | LEA SMITH, BUILDING PLAN REVIEW | | 805-6713 |
|
|