Plan Review Details - Permit 04121031
Plan Review Stops For Permit 04121031
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-05-02 Cont ID  
Sent By mjacobs Date 2005-05-02 Time 08:32 Rev Time 0.75
Received By mjacobs Date 2005-05-02 Time 08:21 Sent To PC
Notes
2005-05-02 00:00:00BUILDING PLAN REVIEW
 PERMIT:04121031
 ADD:3333 GEORGIA AVE.
 CONT:H.A. CONTRACTING CORP
 TEL: (305)591-9212
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:1ST REVIEW
 ACTION:PASSED
 1) THESE SUBMITTALS WERE REQUESTED
 BY THE INSPECTOR. THE CONTRACTOR WAS
 ALTERING DIFFERENT OPENINGS.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-01 Cont ID  
Sent By mjacobs Date 2005-03-01 Time 13:36 Rev Time 1.50
Received By mjacobs Date 2005-03-01 Time 13:36 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-17 Cont ID  
Sent By alange Date 2005-02-17 Time 13:39 Rev Time 0.33
Received By alange Date 2005-02-17 Time 13:39 Sent To  
Notes
2005-02-17 00:00:00DENIED
  
 SEE ELECTRICAL REVIEW NOTES REGARDING
 SIGNING AND SEALING DOCUMENTS.THIS
 REQUIRED BEFORE A PERMIT SHALL BE
 ISSUED.BUILDING REVIEW OK.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-06 Cont ID  
Sent By lsmith Date 2005-01-06 Time 10:28 Rev Time 1.00
Received By lsmith Date 2005-01-06 Time 10:28 Sent To  
Notes
2005-01-06 00:00:00BUILDING PLAN REVIEW: FAILED
  
  
 1. PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SUBMIT THE FL PRODUCT APPROVALS FOR THE
 WINDOWS, DOORS & STORM PANELS.
  
 2. THE WINDOW DRAWINGS BY DONALD W.
 SHACKELFORD P.E. SHOW WINDO #6 AS 36" X
 38".THE PLANS SHOW 37" X 38.
  
 3. SEE ELECTRICAL COMMENTS REGARDING THE
 SEAL & SIGNATURE REQUIREMENTS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-24 Cont ID  
Sent By dpalmer Date 2005-02-24 Time 14:58 Rev Time 0.20
Received By dpalmer Date 2005-02-24 Time 14:58 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-14 Cont ID  
Sent By dpalmer Date 2005-02-14 Time 16:46 Rev Time 0.25
Received By dpalmer Date 2005-02-14 Time 16:46 Sent To M
Notes
2005-02-14 00:00:00******** UNSAT2ND REVIEW ***********
  
 1)NOTE; PLEASE SEE NOTES #1FROM
 PREVIOUS REVIEW.
 PLEASE PROVIDE LICENSE #'S AS REQUIRED
 PER FAC AND FS.
  
 PLEASE SEE STRUCTUAL CALCS WHICH ARE
 PHOTO -COPIES OF SIGNATURE.
  
 SEE BLDG REVIEW NOTES. MUST BE ORIGINAL
 SIGNATURE. 471.025
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-28 Cont ID  
Sent By dpalmer Date 2004-12-28 Time 08:30 Rev Time 0.25
Received By dpalmer Date 2004-12-28 Time 08:28 Sent To M
Notes
2004-12-28 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 FAC 61G15-23.002 FOR MISSING LICENSE
 INFORMATION FOR ARCHITECTS AND
 ENGINEERINGFIRM PER FS 481.219,
 471.023.
 THIS INFORMATION IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLANS WHICH CONTAIN THE TITLE
 BLOCK FOR ENGINEER RESPONSIBLE FOR
 PLANS/DESIGN, MUST SIGN, DATE AND SEAL
 PLANS. FS 471.025
  
  
 4)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCUALTIONS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 11:33 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 11:33 Sent To B
Notes
2005-04-29 00:00:00TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 14:54 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 14:54 Sent To E
Notes
2005-02-18 00:00:00TO "DPALMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 10:13 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 10:13 Sent To E
Notes
2005-02-09 00:00:00TO DPALMER DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-21 Cont ID  
Sent By mjacobs Date 2004-12-21 Time 11:55 Rev Time 0.00
Received By mjacobs Date 2004-12-21 Time 11:55 Sent To E
Notes
2004-12-21 00:00:00SENT TO "E" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-02-15 Cont ID  
Sent By prafter Date 2005-02-15 Time 11:29 Rev Time 0.45
Received By prafter Date 2005-02-15 Time 11:29 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-05 Cont ID  
Sent By prafter Date 2005-01-05 Time 10:57 Rev Time 0.45
Received By prafter Date 2005-01-05 Time 10:39 Sent To B
Notes
2005-01-05 00:00:001. RETURN AIR OUT OF BEDROOM MUST
 COMPLY WITH 2001 FBC/M 601.4 .
 2. RATURN AIR THROUGH UTILITY ROOM
 WITH GAS H.W.H. IS NOT ALLOWED 2001
 FBC/M 602.1. .
 PAT RAFTER561/805/6725 OR 805/6719
 .