Plan Review Details - Permit 04121024
Plan Review Stops For Permit 04121024
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-04-21 Cont ID  
Sent By alange Date 2006-04-21 Time 08:54 Rev Time 0.50
Received By alange Date 2006-04-21 Time 08:54 Sent To  
Notes
2006-04-21 00:00:00DOOR REV OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-04-11 Cont ID  
Sent By alange Date 2006-04-11 Time 08:13 Rev Time 0.50
Received By alange Date 2006-04-11 Time 08:13 Sent To  
Notes
2006-04-11 00:00:00REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-10-19 Cont ID  
Sent By alange Date 2005-10-19 Time 07:19 Rev Time 1.00
Received By alange Date 2005-08-18 Time 09:35 Sent To  
Notes
2005-10-19 00:00:00DOOR REVISION OK AND LOCAL PRODUCT
 APPROVAL APPROVED BY RBALANGE

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-07-18 Cont ID  
Sent By alange Date 2005-07-18 Time 09:44 Rev Time 0.33
Received By alange Date 2005-07-18 Time 09:44 Sent To  
Notes
2005-07-18 00:00:00REVISION
  
 PRODUCT APPROVAL SUBMITTED FOR CENTRY
 MANUFACTURING MODEL 300 DOOR DOES NOT
 HAVE AN APPROVED STATE APPROVAL.
 PLEASE COMPLETE THE APPLICATION FOR
 LOCAL PRODUCT APPROVAL AND RESUBMIT.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-04-29 Cont ID  
Sent By alange Date 2005-04-29 Time 16:03 Rev Time 0.50
Received By alange Date 2005-04-29 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-03-02 Cont ID  
Sent By mjacobs Date 2005-03-02 Time 08:42 Rev Time 1.00
Received By mjacobs Date 2005-03-02 Time 08:42 Sent To PC
Notes
2005-03-02 00:00:00BUILDING PLAN REVIEW
 PERMIT:04121024
 ADD:619 AVENIDA ALEGRE
 CONT:H.A. CONTRACTING CORP.
 TEL: (305)591-9212
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:3
 ACTION:DENIED
  
 1) THE INFORMATION AND TEST REPORTS FOR
 THE 3000A ACOUSTICAL FRENCH DOOR IS
 EXPEIRED. PLEASE SUBMIT A CURRENT AND
 UPDATED REPORT FOR THIS PRODUCT.
  
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-17 Cont ID  
Sent By alange Date 2005-02-17 Time 11:09 Rev Time 0.33
Received By alange Date 2005-02-17 Time 11:09 Sent To  
Notes
2005-02-17 00:00:00DENIED
  
 3.SEE ELECTRICAL REVIEW NOTED
 REGARDING SIGNING AND SEALING OF
 DOCUMENTS.BUILDING REVIEW OK PENDING
 THIS ITEM.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-06 Cont ID  
Sent By lsmith Date 2005-01-06 Time 08:18 Rev Time 1.00
Received By lsmith Date 2005-01-06 Time 08:18 Sent To  
Notes
2005-01-06 00:00:00BUIDING PLAN REVIEW: FAILED
  
  
 1.PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SUBMIT THE FLORIDA PRODUCT APPROVALS FOR
 THE WINDOWS, DOORS & STORM PANELS.
  
 2. SUBMIT THE DADE COUNTY PRODUCT
 APPROVAL FOR THE WINDOWS
  
 3. THE WINDOW DRAWINGS BY DONALD W.
 SHACKELFORD P.E. SHOW WINDOW # 13 AS 29"
 X 42".THE WINDOW SCHEDULE ON THE PLAN
 SHOWS THE WINDOW TO BE 29" X 43"
  
 4. SEE NOTE FROM ELECTRICAL REVIEWER
 REGARDING THE SEAL & SIGNATURE
 REQUIREMENTS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUIDING PLANS EXAMINER
 805-6713
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-11-16 Cont ID  
Sent By dpalmer Date 2005-11-16 Time 18:54 Rev Time 0.25
Received By dpalmer Date 2005-11-16 Time 18:54 Sent To  
Notes
2005-11-16 00:00:00*** NEW SUB PANEL LOCATION.
 SUB PERMIT CLOSED.

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2005-02-24 Cont ID  
Sent By dpalmer Date 2005-02-24 Time 17:23 Rev Time 0.05
Received By dpalmer Date 2005-02-24 Time 17:23 Sent To M
Notes
2005-02-24 00:00:00BLDG REV CAME IN BEFORE PERMIT WAS
 ISSUED.
 NO ELECTRICAL REVIEW NEEDED.
 SENT TO LS>

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-24 Cont ID  
Sent By dpalmer Date 2005-02-24 Time 14:12 Rev Time 0.25
Received By dpalmer Date 2005-02-24 Time 14:09 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-14 Cont ID  
Sent By dpalmer Date 2005-02-14 Time 16:25 Rev Time 0.25
Received By dpalmer Date 2005-02-14 Time 16:24 Sent To M
Notes
2005-02-14 00:00:00******** UNSAT2ND REVIEW ***********
  
 1)NOTE; PLEASE SEE NOTES #1FROM
 PREVIOUS REVIEW.
 PLEASE PROVIDE LICENSE #'S AS REQUIRED
 PER FAC AND FS.
  
 PLEASE SEE STRUCTUAL CALCS WHICH ARE
 PHOTO -COPIES OF SIGNATURE.
  
 SEE BLDG REVIEW NOTES. MUST BE ORIGINAL
 SIGNATURE. 471.025
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-28 Cont ID  
Sent By dpalmer Date 2004-12-28 Time 07:22 Rev Time 0.25
Received By dpalmer Date 2004-12-28 Time 07:22 Sent To M
Notes
2004-12-28 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 FAC 61G15-23.002 FOR MISSING LICENSE
 INFORMATION FOR ARCHITECTS AND
 ENGINEERINGFIRM PER FS 481.219,
 471.023.
 THIS INFORMATION IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLANS WHICH CONTAIN THE TITLE
 BLOCK FOR ENGINEER RESPONSIBLE FOR
 PLANS/DESIGN, MUST SIGN, DATE AND SEAL
 PLANS. FS 471.025
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCUALTIONS.
  
  
 **PLEASE NOTE***
 PLANS MENTIONS KNOB AND TUBE WIRING
 PRESENT.
 UPON SERVICE CHANGE, IF KNOB AND TUBE IS
 STILL PRESENT THEN, THE CONNECTION OF
 THESE CIRCUITS WILL NOT BE PERMITTED.
 RE-WIRE MUST BE PERMITTED AND COMPLETE
 BEFORE CALLING IN FINALS FOR PERMITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-04-20 Cont ID  
Sent By adarroug Date 2006-04-20 Time 10:58 Rev Time 0.00
Received By adarroug Date 2006-04-20 Time 10:58 Sent To B
Notes
2006-04-20 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 17:20 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 17:20 Sent To B
Notes
2006-04-10 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 18:08 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 18:08 Sent To E
Notes
2005-11-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-15 Cont ID  
Sent By adarroug Date 2005-08-15 Time 15:08 Rev Time 0.00
Received By adarroug Date 2005-08-15 Time 15:08 Sent To B
Notes
2005-08-15 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 08:38 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 08:38 Sent To B
Notes
2005-07-18 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-25 Cont ID  
Sent By adarroug Date 2005-04-25 Time 15:27 Rev Time 0.00
Received By adarroug Date 2005-04-25 Time 15:27 Sent To B
Notes
2005-04-25 00:00:00TO "LMARTINEZ" DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-24 Cont ID  
Sent By adarroug Date 2005-02-24 Time 09:45 Rev Time 0.00
Received By adarroug Date 2005-02-24 Time 09:45 Sent To E
Notes
2005-02-24 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 10:19 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 10:19 Sent To B
Notes
2005-02-09 00:00:00TO DPALMER DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-21 Cont ID  
Sent By mjacobs Date 2004-12-21 Time 11:37 Rev Time 0.00
Received By mjacobs Date 2004-12-21 Time 11:36 Sent To E
Notes
2004-12-21 00:00:00SENT TO "E' BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-02-15 Cont ID  
Sent By prafter Date 2005-02-15 Time 11:11 Rev Time 0.25
Received By prafter Date 2005-02-15 Time 11:11 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-05 Cont ID  
Sent By prafter Date 2005-01-05 Time 12:27 Rev Time 0.45
Received By prafter Date 2005-01-05 Time 12:27 Sent To B
Notes
2005-01-05 00:00:00BEDROOM ONE REQUIRES RETURN AIR OUT OF
 ROOM .
 2001 FBC/M 604.1 EXCEPTION 1.
 PAT RAFTER 561/805/6725 OR 805/6719 ..