Plan Review Details - Permit 04120909
Plan Review Stops For Permit 04120909
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-01-26 Cont ID  
Sent By gsalfeld Date 2005-01-26 Time 09:00 Rev Time 1.00
Received By gsalfeld Date 2005-01-26 Time 09:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2004-12-23 Cont ID  
Sent By kstevens Date 2004-12-23 Time 13:28 Rev Time 0.66
Received By kstevens Date 2004-12-23 Time 13:28 Sent To  
Notes
2004-12-23 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 A) THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
 1. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 B) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SECTION 104.2.1
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-19 Cont ID  
Sent By mjacobs Date 2005-01-19 Time 15:16 Rev Time 0.00
Received By mjacobs Date 2005-01-19 Time 15:16 Sent To G
Notes
2005-01-19 00:00:00TO "GAS" BOX./RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-17 Cont ID  
Sent By mjacobs Date 2004-12-17 Time 07:46 Rev Time 0.00
Received By mjacobs Date 2004-12-17 Time 07:46 Sent To G
Notes
2004-12-17 00:00:00SENT TO "GAS' BOX.