Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 13:30 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 13:30 Sent To M
Notes
2005-01-31 00:00:00TO "M/AC" BOX/REV.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-17 Cont ID  
Sent By mjacobs Date 2004-12-17 Time 15:14 Rev Time 0.00
Received By prafter Date 2005-02-03 Time 09:01 Sent To M
Notes
2004-12-17 00:00:00SENT TO "M/AC" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-03-08 Cont ID  
Sent By pkrauss Date 2005-03-08 Time 15:44 Rev Time 0.40
Received By pkrauss Date 2005-03-08 Time 15:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-03 Cont ID  
Sent By pkrauss Date 2005-01-03 Time 10:28 Rev Time 0.55
Received By pkrauss Date 2005-01-03 Time 10:28 Sent To  
Notes
2005-01-03 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATIONS
 PER
 2001 FBC(M) TABLE 430.3.
  
 2.PROVIDE OUTSIDE AIR DUCT SIZE,
 MATERIAL, AND INTAKE.PLEASE NOTE
 INTAKES SHALL NOT BE LOCATED WITHIN 10
 FT FROM LOT LINES OR BUILDINGS ONTHE
 SAME LOT.INTAKES SHALL BE LOCATED AS
 NOT TO RECIRCULATE NOXIOUS CONTAMINANTS
 FROM PARKING LOTS, LOADING DOCKS STREETS
 AND ALLEYS,
  
 3.PLAN INDICATES AHU 3 LOCATED IN AN
 ELECTRICAL ROOM.DOES THIS ROOM HAVE A
 FIRE RESISTANCE RATING?SHOULD THIS BE
 THE FPL VAULT, NO AHU WILLNOT BE
 ALLOWED.PROVIDE MANUFACTURER SUBMITTAL
 & INSTALLATION INSTRUCTIONS FOR THE FIRE
 DAMPERS ON THE JOBSITE AT THE TIME OF
 INSPECTION.
  
 4.CLARIFY ELECTRICAL ROOM OFF THE
 STAIRWELL.IS THIS BELOW THE STAIRS?
  
 5. PROVIDE CONDENSATE LAYOUT, PIPE
 MATERIAL, SIZE AND TERMINATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.