Plan Review Details - Permit 04120898
Plan Review Stops For Permit 04120898 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-01-31 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2005-01-31 |
Time |
13:30 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2005-01-31 |
Time |
13:30 |
Sent To |
M |
|
Notes |
2005-01-31 00:00:00 | TO "M/AC" BOX/REV. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-12-17 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2004-12-17 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
prafter |
Date |
2005-02-03 |
Time |
09:01 |
Sent To |
M |
|
Notes |
2004-12-17 00:00:00 | SENT TO "M/AC" BOX. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2005-03-08 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-03-08 |
Time |
15:44 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2005-03-08 |
Time |
15:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2005-01-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-01-03 |
Time |
10:28 |
Rev Time |
0.55 |
Received By |
pkrauss |
Date |
2005-01-03 |
Time |
10:28 |
Sent To |
|
|
Notes |
2005-01-03 00:00:00 | DENIED: | | 1.PROVIDE OUTSIDE AIR CALCULATIONS | | PER | | 2001 FBC(M) TABLE 430.3. | | | | 2.PROVIDE OUTSIDE AIR DUCT SIZE, | | MATERIAL, AND INTAKE.PLEASE NOTE | | INTAKES SHALL NOT BE LOCATED WITHIN 10 | | FT FROM LOT LINES OR BUILDINGS ONTHE | | SAME LOT.INTAKES SHALL BE LOCATED AS | | NOT TO RECIRCULATE NOXIOUS CONTAMINANTS | | FROM PARKING LOTS, LOADING DOCKS STREETS | | AND ALLEYS, | | | | 3.PLAN INDICATES AHU 3 LOCATED IN AN | | ELECTRICAL ROOM.DOES THIS ROOM HAVE A | | FIRE RESISTANCE RATING?SHOULD THIS BE | | THE FPL VAULT, NO AHU WILLNOT BE | | ALLOWED.PROVIDE MANUFACTURER SUBMITTAL | | & INSTALLATION INSTRUCTIONS FOR THE FIRE | | DAMPERS ON THE JOBSITE AT THE TIME OF | | INSPECTION. | | | | 4.CLARIFY ELECTRICAL ROOM OFF THE | | STAIRWELL.IS THIS BELOW THE STAIRS? | | | | 5. PROVIDE CONDENSATE LAYOUT, PIPE | | MATERIAL, SIZE AND TERMINATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
|