Plan Review Details - Permit 04120838
Plan Review Stops For Permit 04120838
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-01-11 Cont ID  
Sent By nmccray Date 2005-01-11 Time 12:11 Rev Time 0.00
Received By nmccray Date 2005-01-11 Time 12:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-03 Cont ID  
Sent By nmccray Date 2005-01-03 Time 13:06 Rev Time 0.00
Received By nmccray Date 2005-01-03 Time 12:54 Sent To  
Notes
2005-01-03 00:00:00FIRE REVIEW - DENIED
  
 1) WHEN THE FIRE ALARM CONTROL UNIT
 PANEL IS REPLACED IN AN EXISTING SYSTEM,
 IT WILL BE TREATED AS A NEW SYSTEM.
  
 2) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 3) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 4) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By mjacobs Date 2005-01-11 Time 10:52 Rev Time 0.00
Received By mjacobs Date 2005-01-11 Time 10:51 Sent To FIRE
Notes
2005-01-11 00:00:00TO "FIRE" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-16 Cont ID  
Sent By mjacobs Date 2004-12-16 Time 08:06 Rev Time 0.00
Received By mjacobs Date 2004-12-16 Time 08:06 Sent To FIRE
Notes
2004-12-16 00:00:00SENT TO "FIRE" BOX.