Plan Review Details - Permit 04120830
Plan Review Stops For Permit 04120830
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-19 Cont ID  
Sent By shill Date 2005-09-19 Time 13:42 Rev Time 5.00
Received By shill Date 2005-09-19 Time 09:21 Sent To  
Notes
2005-09-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 THE FOLLOWING COMMENTS ARE FROM THE
 PREVIOUS REVIEW.NUMBERING WILL REMAIN
 THE SAME TO MAINTAIN CONSISTENCY.
  
 ALL CHANGES TO THE PLAN ARE TO BE
 CLOUDED.
  
 1.)SEE PROPERTY APPRAISER VALUATION
 ATTACHED.THIS IS AN OVER 50%
 IMPROVEMENT AND MUST COMPLY WITH
 FBC3401.7.2.6.THIS SECTION AFFECTS
 OTHER COMMENTS ON THIS LIST. (WAS
 ACKNOWLEDGED.)
  
 2.)ADDRESSED.
  
 3.)THIS APPEARS TO BE TWO UNITS; ONE
 UPSTAIRS, ONE DOWNSTAIRS.2ND FLOOR IS
 TO BE IMPACT GLASS, CITY OF WEST PALM
 BEACH IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION,
 ITEM #13, SEE ATTACHED.SUBMIT A
 HURRICANE INSTALLATION PLAN INCLUDING
 WHERE THE SHUTTERS WILL BE STORED FOR
 SHUTTERS USED ON THE FIRST FLOOR.
  
 SECOND REVIEW COMMENT - THIS WAS
 ADDRESSED BY CHANGING THE
 SECOND FLOOR TO IMPACT AND A NOTE
 STATING THAT THE FIRST FLOOR SHUTTERS
 WOULD BE STORED IN THE UTILITY ROOM
 BELOW THE STAIRS.ONLY THE BUILDING
 OFFICIAL CAN APPROVE THE USE OF SHUTTERS
 ON A COMMERCIAL BUILDING.PLEASE SUBMIT
 A HURRICANE SHUTTER INSTALLATION PLAN
 FOR REVIEW.THIS IS TO INCLUDE ALL
 PERTINENT INFORMATION SUCH AS STORAGE
 LOCATION, SIZE OF STORAGE AREA, WHERE
 THEY ARE STORED IN THAT AREA, HOW THEY
 ARE SECURED IN THAT LOCATION; WHO IS TO
 INSTALL THEM; TIME ESTIMATE FOR
 INSTALLATION; WHEN THE SHUTTERS WILL BE
 INSTALLED, ETC.THIS MAY BE SUBMITTED
 SEPARATELY FROM PLAN REVIEW (NO FEE).
  
 PLAN WAS NOT CHANGED, STILL SHOWS
 SHUTTERS ON THE FIRST FLOOR, AND AN
 INSTALLATION WAS NOT SUBMITTED FOR
 REVIEW.
  
 4.)THE BALCONY (MEANS OF EGRESS FOR
 2ND FLOOR UNIT) IS TO COMPLY WITH
 FBC1014.1.SHOW FIRE RESISTANCE (UL
 ASSEMBLY OR CALCULATED FBC CHAPTER 7),
 PROVIDE DOOR FIRE RATING INFORMATION.
  
 SECOND REVIEW COMMENT - THE FIRE RATING
 FOR THE DOOR WAS
 PROVIDED.I BELIEVE THAT THIS WAS
 ADDRESSED BY SHOWING TWO LAYERS OF
 DRYWALL ON THE CEILING OF THE FIRST
 FLOOR UNIT.PROVIDE CALCULATED FIRE
 RESISTANCE FOR THE FLOOR/CEILING
 ASSEMBLY FBC709 (EACH COMPONENT AND
 TIME, SHOW TOTAL).
  
 UL L504 WAS SHOWN ON THE PLAN.PLEASE
 INCORPORATE A DETAIL INTO THE PLAN.
  
 5.)THE EXTERIOR STAIR IS TO COMPLY
 WITH FBC1006.2.4.SHOW FIRE RESISTANCE
 OF THE WALL.OPENINGS WITHIN 10' ARE
 TO BE 3/4 HR.INDICATE ON THE PLAN.
  
 SECOND REVIEW COMMENT - FIRE RESISTANCE
 OF THE WALL REQUIRED BY
 FBC1006.2.4 WAS NOT SHOWN.THERE IS A
 NOTE ON THE PLAN REGARDING OPENINGS.IT
 IS THE RESPONSIBILITY OF THE DESIGNER TO
 DETERMINE WHICH OPENINGS ARE TO BE
 PROTECTED.INDICATE ON THE ELEVATIONS,
 FLOOR PLAN OR A SCHEDULE. ALSO INCLUDE
 THE REAR BUILDING.SHOW RATED WALL
 REQUIREMENT ON THE FLOOR PLAN AS WELL AS
 A DETAIL SHOWING HOW IT COMPLIES.
  
 UL DESIGN U301 WAS SPECIFIED FOR THE NEW
 WALL.INCORPORATE THE DESIGN FOR FIRE
 RESISTANT WALLS INTO YOUR PLAN.YOUR
 WALL SECTION IS IN CONFLICT WITH THIS
 DETAIL.ALSO U301 HAS DRYWALL ON BOTH
 SIDES; APPEARS TO BE AN INTERIOR BEARING
 WALL, YOUR PLAN REQUIRES AN EXTERIOR
 APPLICATION WHICH MUST ALSO HAVE
 STRAPPING TO COMPLY WITH WIND
 REQUIREMENTS.PLEASE CLARIFY.
  
 HOW DOES THE EXISTING WALL COMPLY WITH
 THIS REQUIREMENT?ACCORDING TO THE
 ENERGY CALCS, THIS IS A FRAME WALL.
 PROVIDE A DETAIL AND SHOW COMPLIANCE.
  
 NOTE THAT FIRE RESISTANT WINDOWS REQUIRE
 IMPACT PROTECTION.THIS OPENING SHOULD
 BE INCLUDED IN THE PROPOSAL TO THE
 BUILDING OFFICIAL, INCLUDING HOW THE
 SECOND FLOOR WILL BE ACCESSED FOR
 INSTALLATION.
  
 6.)ADDRESSED.
  
 7.)ADDRESSED.
  
 8.)ADDRESSED.
  
 9.)FOR THE MODIFIED ROOF, INDICATE
 WHICH METHOD OF INSTALLATION YOU ARE
 USING.
  
 SECOND REVIEW - THIS SHOULD BE DONE BY
 CHOOSING ONE OF
 THE APPROVED ASSEMBLIES ON THE PRODUCT
 APPROVAL.
  
 NOT ADDRESSED.IF THIS IS NOT ADDRESSED
 CORRECTLY PRIOR TO PERMIT ISSUANCE, THE
 ROOF PERMIT NUMBER WILL BE VOIDED AND A
 SEPARATE PERMIT WITH SEPARATE FEES AND
 REVIEW WILL BE REQUIRED.
  
 10.)ADDRESSED.
  
 11.)BATHROOM DOOR ON THE FIRST FLOOR
 IS TO COMPLY WITH FBC11-11(1), CLEAR
 OPENING OF AT LEAST 29IN.
  
 NEW COMMENT - THIS IS REQUIRED ON SECOND
 FLOOR BATHROOMS AS WELL.PLEASE REVISE.
  
 12.)THE ELEVATIONS AND WALL SECTION DO
 NOT MATCH.IS THERE A PARAPET WALL?IF
 THERE IS, SHOW DRAINAGE FBC1503.4.
  
 NOT ADDRESSED.A NOTE WAS SENT THAT
 THIS IS EXISTING.PLEASE SEE COMMENT
 #1.SHOW ALL REQUIRED DRAINAGE WITH
 CALCULATIONS.
  
 13.)SUBMIT PRODUCT APPROVALS AND FIRE
 RESISTANCE INFORMATION IF APPLICABLE FOR
 THE FOLLOWING:
  
 EXTERIOR DOOR, FIRE RATED
 SINGLE HUNG WINDOW, FIRE RATED
 IMPACT SINGLE HUNG WINDOWS
  
 14.)THE ENERGY CALCS FOR THE FRONT
 BUILDING, 1ST FLOOR GIVES A SQUARE FOOT
 AREA OF1203, THE LETTER FROM THE
 ENGINEER GIVES AN AREA OF 1483.SECOND
 FLOOR ENERGY CALCS GIVES AN AREA OF 965,
 LETTER FROM ENGINEER STATES 685 AFTER
 THE ADDITION.PROVIDE AREA CALCS FOR
 THE REAR BUILDING, 1ST AND 2ND FLOORS.
 PLEASE COMPARE WITH ENERGY CALCS PRIOR
 TO RESUBMITTAL.
  
 15.)THE LETTERHEAD FOR THE ENGINEER IS
 REQUIRED TO HAVE THE CERTIFICATE OF
 AUTHORIZATION, FAC61G15.
  
 16.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS ARE NOT ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-21 Cont ID  
Sent By shill Date 2005-07-21 Time 07:53 Rev Time 4.00
Received By shill Date 2005-07-20 Time 18:36 Sent To PC
Notes
2005-07-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 THE FOLLOWING COMMENTS ARE FROM THE
 PREVIOUS REVIEW.
  
 1.)SEE PROPERTY APPRAISER VALUATION
 ATTACHED.THIS IS AN OVER 50%
 IMPROVEMENT AND MUST COMPLY WITH
 FBC3401.7.2.6.THIS SECTION AFFECTS
 OTHER COMMENTS ON THIS LIST. (WAS
 ACKNOWLEDGED.)
  
 2.)PROVIDE A COPY OF THE SURVEY FOR
 THIS PROPERTY.
  
 THE SURVEY SHOWS A 1 STORY GARAGE ON THE
 PROPERTY LINE.PROVIDE INFORMATION IN
 REGARDS TO THIS BUILDING AND SHOW FBC
 TABLE 600 COMPLIANCE.
  
 3.)THIS APPEARS TO BE TWO UNITS; ONE
 UPSTAIRS, ONE DOWNSTAIRS.2ND FLOOR IS
 TO BE IMPACT GLASS, CITY OF WEST PALM
 BEACH IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION,
 ITEM #13, SEE ATTACHED.SUBMIT A
 HURRICANE INSTALLATION PLAN INCLUDING
 WHERE THE SHUTTERS WILL BE STORED FOR
 SHUTTERS USED ON THE FIRST FLOOR.
  
 THIS WAS ADDRESSED BY CHANGING THE
 SECOND FLOOR TO IMPACT AND A NOTE
 STATING THAT THE FIRST FLOOR SHUTTERS
 WOULD BE STORED IN THE UTILITY ROOM
 BELOW THE STAIRS.ONLY THE BUILDING
 OFFICIAL CAN APPROVE THE USE OF SHUTTERS
 ON A COMMERCIAL BUILDING.PLEASE SUBMIT
 A HURRICANE SHUTTER INSTALLATION PLAN
 FOR REVIEW.THIS IS TO INCLUDE ALL
 PERTINENT INFORMATION SUCH AS STORAGE
 LOCATION, SIZE OF STORAGE AREA, WHERE
 THEY ARE STORED IN THAT AREA, HOW THEY
 ARE SECURED IN THAT LOCATION; WHO IS TO
 INSTALL THEM; TIME ESTIMATE FOR
 INSTALLATION; WHEN THE SHUTTERS WILL BE
 INSTALLED, ETC.THIS MAY BE SUBMITTED
 SEPARATELY FROM PLAN REVIEW (NO FEE).
  
 4.)THE BALCONY (MEANS OF EGRESS FOR
 2ND FLOOR UNIT) IS TO COMPLY WITH
 FBC1014.1.SHOW FIRE RESISTANCE (UL
 ASSEMBLY OR CALCULATED FBC CHAPTER 7),
 PROVIDE DOOR FIRE RATING INFORMATION.
  
 THE FIRE RATING FOR THE DOOR WAS
 PROVIDED.I BELIEVE THAT THIS WAS
 ADDRESSED BY SHOWING TWO LAYERS OF
 DRYWALL ON THE CEILING OF THE FIRST
 FLOOR UNIT.PROVIDE CALCULATED FIRE
 RESISTANCE FOR THE FLOOR/CEILING
 ASSEMBLY FBC709 (EACH COMPONENT AND
 TIME, SHOW TOTAL).
  
 5.)THE EXTERIOR STAIR IS TO COMPLY
 WITH FBC1006.2.4.SHOW FIRE RESISTANCE
 OF THE WALL.OPENINGS WITHIN 10' ARE
 TO BE 3/4 HR.INDICATE ON THE PLAN.
  
 FIRE RESISTANCE OF THE WALL REQUIRED BY
 FBC1006.2.4 WAS NOT SHOWN.THERE IS A
 NOTE ON THE PLAN REGARDING OPENINGS.IT
 IS THE RESPONSIBILITY OF THE DESIGNER TO
 DETERMINE WHICH OPENINGS ARE TO BE
 PROTECTED.INDICATE ON THE ELEVATIONS,
 FLOOR PLAN OR A SCHEDULE. ALSO INCLUDE
 THE REAR BUILDING.SHOW RATED WALL
 REQUIREMENT ON THE FLOOR PLAN AS WELL AS
 A DETAIL SHOWING HOW IT COMPLIES.
  
 6.)THIS PROPERTY IS ON THE DEMO LIST.
 AN ORDER FROM THE BOARD FOR REPAIRS
 MUST BE GRANTED BEFORE A PERMIT CAN BE
 ISSUED.
  
 AN ORDER WAS GRANTED, BUT IT IS MY
 UNDERSTANDING THAT ALL BUILDINGS ARE TO
 BE BROUGHT TO 100% CODE COMPLIANCE.THE
 REAR BUILDING AND GARAGE ARE ALSO TO BE
 INCLUDED IN THIS PERMIT, ALTHOUGH A
 SEPARATE PERMIT NUMBERS AND APPLICATION
 FORMS WILL BE REQUIRED.PLEASE CONTACT
 ME IF YOU FEEL THAT MY UNDERSTANDING IS
 NOT CORRECT.
  
 7.)SHEATHING NAILING IS TO COMPLY
 WITH CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC TABLE 2306.1.SEE ATTACHED.
  
 NOT ADDRESSED.FBC*TABLE 2306.1.NON
 COMPLIANT FOR ZONE 3 (4/6, NOT 6/6).
  
 8.)PROVIDE DESIGN PRESSURES FOR THE
 ROOF.
  
 PLEASE CLARIFY HOW YOU HAVE DETERMINED
 THE PRESSURE TO BE +-38.87, FBC1606.2B.
 SHOULDN?T THIS BE -89?
  
 9.)FOR THE MODIFIED ROOF, INDICATE
 WHICH METHOD OF INSTALLATION YOU ARE
 USING.
  
 THIS SHOULD BE DONE BY CHOOSING ONE OF
 THE APPROVED ASSEMBLIES ON THE PRODUCT
 APPROVAL.
  
 10.)SPECIFY THE STRAPS.FASTENING
 MUST BE CONSISTENT WITH THE
 MANUFACTURER'S SPECIFICATIONS.
  
 SOME STRAPS WERE SPECIFIED, OTHERS HAD
 ONLY A SIZE.THIS IS A STRUCTURAL
 COMPONENT REQUIRING TESTING OR
 ENGINEERING AND STATE OR LOCAL PRODUCT
 APPROVAL FAC9B72.SPECIFY STRAP,
 MANUFACTURER AND NUMBER, AND FASTENING
 IN ACCORDANCE WITH MANUFACTURER
 INSTRUCTIONS.
  
 NEW COMMENTS
  
 11.)BATHROOM DOOR ON THE FIRST FLOOR
 IS TO COMPLY WITH FBC11-11(1), CLEAR
 OPENING OF AT LEAST 29IN.
  
 12.)THE ELEVATIONS AND WALL SECTION DO
 NOT MATCH.IS THERE A PARAPET WALL?IF
 THERE IS, SHOW DRAINAGE FBC1503.4.
  
 13.)THREE DIFFERENT NOAS ARE INCLUDED
 IN THE DOOR PRODUCT APPROVAL PACKAGE
 SUBMITTED.PLEASE SUBMIT ONLY THE DOOR
 YOU ARE USING.
  
 14.)PROVIDE ENERGY CALCS FOR THE REAR
 BUILDING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-28 Cont ID  
Sent By shill Date 2004-12-28 Time 13:59 Rev Time 3.00
Received By shill Date 2004-12-28 Time 13:34 Sent To  
Notes
2004-12-28 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
  
 1.)SEE PROPERTY APPRISER VALUATION
 ATTACHED.THIS IS AN OVER 50%
 IMPROVEMENT AND MUST COMPLY WITH
 FBC3401.7.2.6.THIS SECTION AFFECTS
 OTHER COMMENTS ON THIS LIST.
  
 2.)PROVIDE A COPY OF THE SURVEY FOR
 THIS PROPERTY.
  
 3.)THIS APPEARS TO BE TWO UNITS; ONE
 UPSTAIRS, ONE DOWNSTAIRS.2ND FLOOR IS
 TO BE IMPACT GLASS, CITY OF WEST PALM
 BEACH IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION,
 ITEM #13, SEE ATTACHED.SUBMIT A
 HURRICANE INSTALLATION PLAN INCLUDING
 WHERE THE SHUTTERS WILL BE STORED FOR
 SHUTTERS USED ON THE FIRST FLOOR.
  
 4.)THE BALCONY (MEANS OF EGRESS FOR
 2ND FLOOR UNIT) IS TO COMPLY WITH
 FBC1014.1.SHOW FIRE RESISTANCE (UL
 ASSEMBLY OR CALCULATED FBC CHAPTER 7),
 PROVIDE DOOR FIRE RATING INFORMATION.
  
 5.)THE EXTERIOR STAIR IS TO COMPLY
 WITH FBC1006.2.4.SHOW FIRE RESISTANCE
 OF THE WALL.OPENINGS WITHIN 10' ARE
 TO
 BE 3/4 HR.INDICATE ON THE PLAN.
  
 6.)PROVIDE TENANT SEPARATION FIRE
 RESISTANCE INFORMATION FBC704.3.
  
 7.)A 24 WINDOW DOES NOT COMPLY WITH
 EMERGENCY EGRESS REQUIREMENTS
 FBC1005.4.
  
 8.)THIS PROPERTY IS ON THE DEMO LIST.
 AN ORDER FROM THE BOARD FOR REPAIRS
 MUST
 BE GRANTED BEFORE A PERMIT CAN BE
 ISSUED.
  
 9.)PROVIDE MULLION PRODUCT APPROVALS.
  
 10.) PROVIDE AREA CALCULATIONS
 (EXISTING, PROPOSED, NEW TOTAL).THIS
 PROJECT INVOLVES AN ADDITION.
  
 11.)PROVIDE ELEVATIONS.
  
 12.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 13.)SHEATHING NAILING IS TO COMPLY
 WITH CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC TABLE 2306.1.SEE ATTACHED.
  
 14.)PROVIDE DESIGN PRESSURES FOR THE
 ROOF.
  
 15.)FOR THE MODIFIED ROOF, INDICATE
 WHICH METHOD OF INSTALLATION YOU ARE
 USING.
  
 16.)HOW HAVE YOU DETERMINED THE
 DESIGN
 PRESSURE FOR THE WINDOWS?FBC TABLE
 1606.2B, 140MPH, EXPOSURE B, ZONE 5
 LESS
 THAN 10SF HAS A REQUIREMENT OF -47.2.
 YOU HAVE DECLARED AN EXPOSURE C, SO THE
 NEGATIVE PRESSURE SHOULD BE -67.2.
 YOUR
 PLAN STATES -44.
  
 17.)SPECIFY THE STRAPS.FASTENING
 MUST
 BE CONSISTENT WITH THE MANUFACTURER'S
 SPECIFICATIONS.
  
 18.)ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 IS TO BE ON THE TITLE
 BLOCK.CA NUMBER REQUIRED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-11 Cont ID  
Sent By dpalmer Date 2005-09-11 Time 09:52 Rev Time 0.55
Received By dpalmer Date 2005-09-11 Time 09:32 Sent To  
Notes
2005-09-11 00:00:00************ PROVISO/ REVISION ********
  
  
 1)NOTE: PLEASE SEE RISER DIAGRAM SHOWS
 ONE 125A DISCONNECT AT MAIN SERVICE
 LOACTION FEEDING ONLY ONE DISCONNECT AT
 DETACHED BLDG. PLEASE SEE THE ONE
 DISCONNECT FEED BOTH PANELS.
 PLEASE SEE OTHER DISC AT MAIN SERVICE
 DOES NOT FEED ANYTHING.???
 PLEASE CORRELATE AND LABEL EACH.
 UNIT, A
  
 2)NOTE: PLEASE SEE SERVICE ENT
 CONDUCTORS SHALL BE A MIN OF 400 MCM,
 310.15B6, 240.4, 90.8, 90.4.
  
  
 3)NOTE: PLEASE SEE SOME RECEPTS MISSING
 PER 210.52
  
  
 PLEASE SUBMIT THE ABOVE REVISED PLANS
 BEFORE ANY INSPECTION IS CALLED IN SO
 THE PLANS CAN BE REVIEWED, STAMPED AND
 BACK TO CONTRACTOR FOR THE FIRST
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-11 Cont ID  
Sent By dpalmer Date 2005-07-11 Time 17:42 Rev Time 0.75
Received By dpalmer Date 2005-07-11 Time 17:31 Sent To  
Notes
2005-07-11 00:00:00********* UNSAT 2ND REVIEW **********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1, OK, AIC CALCS SHOWN.
  
 2)NOTE: NOTE #2 NO,
 PLEASE SEE 310.16,240.4, AND 250.66 FOR
 SIZING.
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 NO, SERVICE IS NOW SHOWN
 TO BE LOCATED ON FRONT BLDG, HOWEVER NO
 INFORMATION FOR MAINS AT DETACHED BLDG.
 PLEASE SEE 225.32, 225.34
 GROUNDING PER 250.32
  
 5)NOTE: NOTE #5 OK, HOWEVER PLEASE SEE
 NEWNOTE;
  
 6)NOTE: NOTE #6 NO, CU'S AND CU'S DISC'S
 SHOWN, HOWEVER PLEASE SEE AHU'S AND
 MISSING AHU'S DISC'S.
  
 7)NOTE: NOTE #7 NO, PLEASE SEE PREVIOUS.
 310.16,240.4
  
 8)NOTE: NOTE #8 OK.
 SEE NOTE #4 FOR GROUNDING AT DETACHED
 BLDGS.
  
 9)NOTE: NOTE #9 OK, HOWEVER PLEASE SEE
 NOTE MENTIONS DEVICES TO BE ARC FAULT
 TYPE? PLEASE SEE THESE DEVICES ARE NOT
 MADE AS ARC FAULT PROTECTIVE TYPES.
 PLEASE SEE 210.12 UNDER 2002 NEC, THIS
 REQUIRES THE ENTIRE BRANCH CIRCUIT TO
 HAVE ARC FAULT PROTECTION. THE BREAKER
 AT PANEL IS THE ONLY WAY ARC FAULT
 PROTECTION CAN BE PROVIDED.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 OK.
  
 NEW NOTES.
  
 1)NOTE: PLEASE SEE MISSING KITCHEN
 COUNTERSPACE GFI PER 210.52C1, PLEASE
 SEE LOWERE AND UPPER UNITS.
  
 2)NOTE: PLEASE SEE MISSING SD EITHER
 INSIDE OR OUTSIDE BEDRM #1 ON FIRST FLR
 UNIT. PLEASE SEE NFPA-72 8-1.4.1.6.2,
 WHICH REQUIRES SD'S IN THE IMMEDIATE
 VICINITY OUTSIDE BEDRMS.
  
 3)NOTE: PLEASE SEE MISSING RECEPT FOR 2'
 OF WALL SPACE IN LIV RM FIRST FLR.
 210.52
  
 4)NOTE: PLEASE SEE ANY HAND WRITTEN
 CHANGES TO PLANS AND SCOPE SHOULD BE
 SIGNED AND DATED BY ENGINEER ALSO. FS
 471.025
  
 5)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSSIONAL(S) AND PLANS WITH REPEAT
 COMMENTS THREE OR MORE TIMES. THIS IS A
 NOTICE ONLY GIVEN AT THIS TIME.
  
 6)NOTE: PLEASE SEE NOC HAS EXPIRED AND
 NEEDS TO BE RE-RECORDED. PLEASE SEE FS
 713.13(2) IF WORK HAS NO COMMENCED
 WITHIN 90 DAYS OF RECORDING, NOC
 EXPIRES.
  
 PLEASE SEE SOME OF THESE ITEMS HAVE
 BEEN REDLINED AT LOCATIONS OF NOTES.
  
 PLEASE BE SURE ANY OLD/VOIDED SHEETS ARE
 REMOVED AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 11:52 Rev Time 0.50
Received By dpalmer Date 2004-12-23 Time 11:52 Sent To  
Notes
2004-12-23 00:00:00**************** UNSAT *************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO
 BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SEE 250.66 FOR SIZING OF
 GROUNDING ELECTRODE CONDUCTOR.
  
 3)NOTE: PLEASE CLARIFY WHICH LOCATION
 SERVICE IS GOING TO BE?
 SHOWN ON REAR BLDG AND MAIN FRONT
 BLDG??
 PLEASE SEE 230.72 FOR REQUIRED GROUPING
 OF MAINS.
  
 4)NOTE: PLEASE SEE 225.31,32.36 FOR
 MEANS OF DISC AT DETACHED BLDGS. PLEASE
 ALSO SEE 250.32 FOR GROUNDING.
  
  
  
 5)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT-
 -ED PER 210.8A-6
  
 6)NOTE: PLEASE SHOW ALL AC/ EQUIPMENT
 ON
 PLANS ALONG WITH REQUIRED DISC'S,
 RECEPTS PER . 215.5,440.11,210.63
  
 7)NOTE: PLEASE SEE 310.16 FOR SIZING OF
 SEC'S PER 240.4B
  
 8)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDIG FROM MAINS TO PANELS.
 LOCAL AMENDMENTS:
  
 9)NOTE:PLEASE SEE 2002 NEC 210.12 FOR
 ARC FAULT PROTECTION.
  
 10)NOTE: PLEASE SEE FAC 61G15-23.002
 FOR
 MISSING REQUIRED INFORMATION ON TITLE
 BLOCK.
 REQUIRED UNDER FS 471.023
  
 11)NOTE: PLEASE SEE #12 AWG ON 30A OCP
 FOR WATER HEATER.
 PLEASE SEE 310.16/240.4B
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By nmccray Date 2005-01-03 Time 10:19 Rev Time 0.00
Received By nmccray Date 2005-01-03 Time 10:10 Sent To  
Notes
2005-01-03 00:00:00FIRE REVIEWS ARE NOT REQUIRED ON SINGLE
 OR TWO FAMILY DWELING.
  
 NATE MCCRAY, CAPTAIN

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 17:21 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 17:21 Sent To  
Notes
2005-09-08 00:00:00TO "COMM" BD#41

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 13:53 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 13:53 Sent To  
Notes
2005-07-11 00:00:00TO "COMM" BD#57
2005-07-05 00:00:00WAITING FOR SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-04 Cont ID  
Sent By mjacobs Date 2005-01-04 Time 09:03 Rev Time 0.00
Received By mjacobs Date 2004-12-15 Time 16:30 Sent To  
Notes
2004-12-15 00:00:00SENT TO "COMM BD#14

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-13 Cont ID  
Sent By pkrauss Date 2005-09-13 Time 10:43 Rev Time 0.25
Received By pkrauss Date 2005-09-13 Time 10:42 Sent To  
Notes
2005-09-13 00:00:00PLAN SHEET 1 0F 8 & THE PERMIT
 APPLICATION INDICATE THE MECHANICAL IS
 NOT INCLUDED WITH THIS SUBMITTAL.
 ENERGY CALCULATIONS & MANUAL J WERE
 SUBMITTED (MULTI-FAMILY)
  
 ***************************************
 MECHANICAL PERMIT REQUIRED.PLEASE
 PROVIDE PLANS & EQUIPMENT SCHEDULE WITH
 MECHANICAL PERMIT APPLICATION.
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-10-01 Cont ID  
Sent By jleech Date 2005-10-01 Time 12:30 Rev Time 1.25
Received By jleech Date 2005-10-01 Time 12:30 Sent To  
Notes
2005-10-01 00:00:00DENIED;
 1.WATER RISER DIAGRAMS;
 ,
 SHOCK ARRESTORS REQ. ON KITCHEN AND
 WASHING MACHINE SEC.604.9 (ALL 4 RD'S)
 THERMAL EXPANSION TANKES, PER.
 MANUFACTUES INSTALLATION INSTRUCTIONS
 TANK TO BE ON COLD WATER. ALL (4RD'S)
 SHUTOFF VALVES REQUIRED FOR EACH UNIT
 SHOW ON RISER DIAGRAM
 WATER RISER DIAGRAM 2ND FLOOR REAR W/M
 NOT SHOWN. ONE PLAN MARKED IN RED
 2. SANITARY RISER DIAGRAMS;
 W/C FIRST FL NOT IN BATHROOM GROUP.
 2ND FL. ONLY A SHOWER ON FL PLAN NO
 TUB.
 1ST AND 2ND FL MISSING W/M'S
 BACK BUILDING, 4 BATHROOMS SHOWN ONLY
 TWO ON FLOOR PLAN.
 W/M'S NOT SHOWN ON RISER DIAGRAM.
 3.WATER HEATERS ON PLANS 5 ARE SHOWN
 PLEASE DELETE ONE.
 4. SEE NOTE 15 BUILDING PLAN REVIEW.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-07-12 Cont ID  
Sent By jleech Date 2005-07-12 Time 12:57 Rev Time 1.00
Received By jleech Date 2005-07-12 Time 12:57 Sent To  
Notes
2005-07-12 00:00:00DENIED;
 1. SANITARY RISER DIAGRAM CANNOT BE
 INSTALLED AS DRAWN. DISHWASHER SHALL BE
 INDIRECTLY DISPOSED THRU THE KITCHEN
 SINK TRAP. RISER DIAGRAM DOES MATCH
 FLOOR PLAN.
 2.ONLY ONE WATER HEATER SHOWN AND THAT
 IS ON THE SECOND FLOOR. SHOW WATER RISER
 DIAGRAM. BACKFLOW PREVENTER REQUIRED IF
 BOTH UNITS ARE ON ONE METER. PLEASE SHOW
 ON DRAWINGS.
 PLUMBING PLANREVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-12-23 Cont ID  
Sent By kstevens Date 2004-12-23 Time 17:07 Rev Time 0.45
Received By kstevens Date 2004-12-23 Time 17:06 Sent To  
Notes
2004-12-23 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 PLUMBING
  
 1) MORE INFORMATION IS REQUIRED. HOW
 MANY UNITS ARE IN THE FRONT BUILDING?
 SECTION 104.2.1
 2) ONLY ONE LAUNDRY ROOM IS SHOWN. IS
 THIS LAUNDRY TO BE USED FOR ALL UNITS,
 OR IS THE LAUNDRY ROOM TO BE USED
 EXCLUSIVLY FOR THE FRONT BUILDING FIRST
 FLOOR? COMMENT RESPONSE MAY OR MAY NOT
 CAUSE MORE COMMENTS. SECTION 104.2.1.
 3) IF THERE IS A CENTRAL LAUNDRY ROOM
 FOR ALL UNITS, A FLOOR DRAIN IS REQUIRED
 PER SECTION 412.4.
 4) SUBMIT SANITARY AND WATER RISER
 DIAGRAMS FOR ALL NEW WORK AS REQUIRED BY
 SECTION 104.3.1.1. SHOW ALL PIPE SIZES,
 CLEANOUTS, CONNECTIONS TO EXISTING
 PIPING, WATER HAMMER ARRESTORS ECT.
 SECTIONS 104.2.1, 604.9, CHAPTER 7 ECT.
 5) IF THERE ARE 4 OR MORE UNITS UNDER
 ONE ROOF, THIS MAY REQUIRE FHA-98 DESIGN
 MANUAL GUIDE LINES TO BE CONSIDERED.
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]