Plan Review Details - Permit 04120741
Plan Review Stops For Permit 04120741
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 15:56 Rev Time 0.00
Received By prafter Date 2005-01-04 Time 13:25 Sent To M
Notes
2004-12-14 00:00:00SENT TO "M/AC" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-04 Cont ID  
Sent By prafter Date 2005-01-04 Time 13:34 Rev Time 0.00
Received By prafter Date 2005-01-04 Time 13:34 Sent To  
Notes
2005-01-04 00:00:00PRIVISO"
 1. CONDENSATE MUST CONFORM WITH 2001
 FBC/M307.2.3 .
 2. SECONDARY DRAIN PAN UNDER A.H.U.
 WITH FLOAT S.W. MUST COMPLY WITH 2001
 FBC/M 307.2.3 .
  
 PAT RAFTER 561/805/6725 OR 805/6719 .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-21 Cont ID  
Sent By prafter Date 2004-12-21 Time 13:15 Rev Time 0.45
Received By prafter Date 2004-12-21 Time 12:35 Sent To  
Notes
2004-12-21 00:00:00RETURN AIR OUT OF SECOND FLOOR BEDROOM
 MUST COMPLY WITH 2001 FBC/M 604.1 .
  
 RETURN AIR BACK TO A.H.U. IS NOT
 REFLECTED ON A/C PLAN .
  
 CONDENSATE FROM A.H.U. IS NOT REFLECTED
 ON A/C PLAN .
  
 SECONDARY DRAIN PAN UNDER A.H.U. WITH
 FLOAT S.W. MUST COMPLY WITH 2001 FBC/M
 307.2.3..