Plan Review Details - Permit 04120702
Plan Review Stops For Permit 04120702
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-02-22 Cont ID  
Sent By kstevens Date 2005-02-22 Time 17:44 Rev Time 0.60
Received By kstevens Date 2005-02-22 Time 17:44 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2004-12-29 Cont ID  
Sent By kstevens Date 2004-12-29 Time 06:59 Rev Time 0.75
Received By kstevens Date 2004-12-29 Time 06:50 Sent To  
Notes
2004-12-29 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 5. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 9. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 2) ALL DRAWINGS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-10 Cont ID  
Sent By adarroug Date 2005-02-10 Time 16:50 Rev Time 0.00
Received By adarroug Date 2005-02-10 Time 16:50 Sent To P
Notes
2005-02-10 00:00:00TO "P"BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2004-12-29 Cont ID  
Sent By kstevens Date 2004-12-29 Time 17:44 Rev Time 0.00
Received By kstevens Date 2005-02-07 Time 09:12 Sent To  
Notes
2005-02-07 00:00:00TO KSTEVENS DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 11:32 Rev Time 0.00
Received By mjacobs Date 2004-12-14 Time 11:32 Sent To G
Notes
2004-12-14 00:00:00SENT TO "GAS" BOX./