Plan Review Details - Permit 04120452
Plan Review Stops For Permit 04120452
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-04 Cont ID  
Sent By btrobaug Date 2005-01-04 Time 09:24 Rev Time 0.25
Received By btrobaug Date 2005-01-04 Time 09:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-10 Cont ID  
Sent By btrobaug Date 2004-12-10 Time 09:46 Rev Time 0.50
Received By btrobaug Date 2004-12-10 Time 09:40 Sent To  
Notes
2004-12-10 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT BEING INSTALLED.
 MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9.
  
 2} INDICATE THE GROUNDING ELECTRODE
 CONDUCTOR SIZE PER 250.66.
  
 3} INDICATE SIZE & TYPE OF CONDUIT USED
 FOR RISER AND NIPPLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-30 Cont ID  
Sent By mjacobs Date 2004-12-30 Time 15:36 Rev Time 0.00
Received By mjacobs Date 2004-12-30 Time 15:36 Sent To E
Notes
2004-12-30 00:00:00TO "BT" DESK./RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-09 Cont ID  
Sent By mjacobs Date 2004-12-09 Time 08:02 Rev Time 0.00
Received By mjacobs Date 2004-12-09 Time 08:02 Sent To E
Notes
2004-12-09 00:00:00SENT TO "E" BOX.