Plan Review Details - Permit 04120177
Plan Review Stops For Permit 04120177
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-16 Cont ID  
Sent By jwitmer Date 2005-02-15 Time 09:43 Rev Time 3.33
Received By jwitmer Date 2005-02-03 Time 13:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By jwitmer Date 2004-12-15 Time 10:31 Rev Time 0.00
Received By jwitmer Date 2002-12-15 Time 11:57 Sent To  
Notes
2004-12-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04120177
 ADD: 504 24TH ST
 CONT: MTC REMODELING, INC
 TEL: (561)719-0725
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE NEW OPENING FORTHE OVERHEAD
 SECTIONAL DOOR, PLANS INDICATE A
 EXISTING LINTEL, PROVIDEIF EXISTING
 COLUMN, OPENING SIZE?
  
 2) PRODUCT SUBMITTAL, MODEL HIGHLIGHTED
 IS LOW ON THE PRESSURES. ALSO PROVIDE
 THE ROOF PITCH, SEE TABLE 1606.2E.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-08 Cont ID  
Sent By btrobaug Date 2005-06-08 Time 14:25 Rev Time 0.50
Received By btrobaug Date 2005-06-08 Time 12:47 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-12-10 Cont ID  
Sent By jleahy Date 2004-12-10 Time 14:09 Rev Time 1.00
Received By jleahy Date 2004-12-10 Time 14:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-12-27 Cont ID  
Sent By mcarsill Date 2004-12-27 Time 14:13 Rev Time 0.00
Received By mcarsill Date 2004-12-27 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 16:26 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 16:26 Sent To E
Notes
2005-05-31 00:00:00TO "JLEAHY" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-08 Time 16:21 Rev Time 0.00
Received By adarroug Date 2005-03-08 Time 16:21 Sent To P
Notes
2005-03-08 00:00:00TO KSTEVENS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 15:47 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 15:37 Sent To  
Notes
2005-01-31 00:00:00TO "COMM BD#44/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2004-12-27 Time 15:25 Rev Time 0.00
Received By mjacobs Date 2004-12-06 Time 10:19 Sent To  
Notes
2004-12-06 00:00:00SENT TO COMM BD#51

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-05 Cont ID  
Sent By pkrauss Date 2005-01-05 Time 06:30 Rev Time 0.30
Received By pkrauss Date 2005-01-05 Time 06:23 Sent To  
Notes
2005-01-05 00:00:00NO MECHANICAL CONTRACTOR OR PLANS
 SUBMITTED WITH PERMIT APPLICATION.PLAN
 SHEET E-1 NOTE #2 INDICATES CORRDINATION
 WITH DUCKWORK.PLEASE PROVIDE PLANS
 WITH MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-03-30 Cont ID  
Sent By kstevens Date 2005-03-30 Time 11:06 Rev Time 1.00
Received By kstevens Date 2005-03-30 Time 11:06 Sent To  
Notes
2005-03-30 00:00:00SANITARY RISER DIAGRAM AND WATER RISER
 DIAGRAM SUBMITTED BY PLUMBING CONTRACTOR
 AND APPROVED. PERMIT # 05021211

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-02-22 Cont ID  
Sent By kstevens Date 2005-02-22 Time 16:32 Rev Time 1.00
Received By kstevens Date 2005-02-22 Time 16:32 Sent To  
Notes
2005-02-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMGING
  
 1) FROM PREVIOUS REVIEW:
 SUBMIT A SANITARY RISER DIAGRAM AND A
 WATER RISER DIAGRAM SHOWING ALL PIPE
 SIZES, VENTS, WATER HAMMER ARRESTORS,
 (REQUIRED BY SEC. 604.9) AND POINTS OF
 CONNECTIONS.
  
 2) NEW COMMENT:
 A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. ALSO SEE SECTION 410.1
  
 3) NEW COMMENT:
 PLANS SHOW A DARK ROOM. INDICATE TYPE OF
 CHEMICALS WILL BE USED IN THE DARK ROOM.
 A NEUTRALIZER TANK MIGHT BE REQUIRED.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-06 Cont ID  
Sent By jleech Date 2005-01-06 Time 09:22 Rev Time 0.75
Received By jleech Date 2005-01-06 Time 09:22 Sent To  
Notes
2005-01-06 00:00:00DENIED;
 NOT ENOUGH INFORMATION TO DO A PLAN
 REVIEW. SANITARY RISER DIAGRAM IS
 REQUIRED. SHOW PIPE SIZES, VENTS, ANDTIE
 IN POINTS. MAKE A NOTE THAT BACKFLOW
 PROTECTIONIS REQUIRED ON WATER
 SERVICE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695