Plan Review Details - Permit 04111389
Plan Review Stops For Permit 04111389
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-04-13 Cont ID  
Sent By jwitmer Date 2005-04-13 Time 15:46 Rev Time 1.11
Received By jwitmer Date 2005-04-13 Time 15:46 Sent To B
Notes
2005-04-13 00:00:00REVISIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-14 Cont ID  
Sent By lmartine Date 2005-01-18 Time 15:52 Rev Time 0.00
Received By adarroug Date 2005-02-02 Time 10:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-12 Cont ID  
Sent By jwitmer Date 2005-01-12 Time 16:19 Rev Time 1.11
Received By jwitmer Date 2005-01-12 Time 16:19 Sent To  
Notes
2005-01-12 00:00:00BUILDING 2ND REVIEW
 01-12-05
  
 PLANS ARE CODE COMPLIANT FOR BUILDING
 PLAN REVIEW WITH PROVISO RED LINED AS
 PER CONVERSATION WITH KEITH SPINA
 CONFERENCE ROOM & ANTE ROOM DOUBLE
 DOORS
 TO SWING IN THE DIRECTION OF EGRESS,
 SEE 1012.1.1.
  
 PLANS WILL REQUIREP. B. COUNTY IMPACT
 FEE REVIEW.
  
 SHELL PERMIT (04041477) NEVER PAID STATE
  
 RADON FEES, OWES $ 634.30.
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-04 Cont ID  
Sent By jwitmer Date 2005-01-04 Time 13:46 Rev Time 8.80
Received By jwitmer Date 2005-01-04 Time 13:46 Sent To  
Notes
2005-01-04 00:00:00BUILDING PLAN REVIEW
 PERMIT:04111389
 ADD: 1661 WORHTINGTON RD
 CONT: LEIGHTON MCGINN
 TEL: (561)767-7521
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEET SP-1 BUILDING DATAINDICATES
 A
 FACTORY/ INDUSTRIAL USAGE, WHAT WILL BE
 MANUFACTURED?
 2A) IF THE USAGE WILL BE OFFICES THEN
 THE OCCUPANCY WILL BE CONSIDERED
 BUSINESS, THE PLAN NEED TO REFLECT
 THIS.
 THIS RECLASSIFICATION MAY RESULT IN
 ADDITIONAL FEES:
 (1) COUNTY IMPACT FEES
 (2) ADDITIONAL PERMIT FEES TO THE
 SHELL AND TENANT BUILD OUT.
  
 3) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL
 J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 4) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 5) CORRECTION, CODE REFRENCE, SEE A-3
 NOTE# 3, REFRENCE TO THE S.F.B.C.
  
 6) A2.4 BOARDROOM 768 SQ FT/ 52 OCC
 LOAD, 1004.1.2 > 50 OCCUPANT LOAD
 REQUIRES 2 EGRESSES, 1/3 DIAGONALL FOR
 FIRE SPRINKLERED BUILDINGS.
  
 7) A2.4 DETAIL OF ANTEROOM SINK TO
 COMPLY WITH:11-4.24.2 SINKS, HEIGHT.
 SINKS SHALL BE MOUNTED WITH THE COUNTER
 NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 8) FL BLD CODE 104.2.1.2*
 ADDITIONAL INFORMATION REQUIRED, A2.4
 THE BOARDROOM DETAILS INDICATE THE USE
 OF GYPSUM BOARD SOFFITS, PROVIDE
 DETAILS
  
 GYPSUM THICKNESS, STUD SIZE &SPACING
 DETAILS HOW TOATTACH TO STRUCTURE
 ABOVE.
  
 9)FL BLD CODE 104.2.1.2*
 ADDITIONAL INFORMATION REQUIRED,
 A-1.8 PROVIDE THE WIDTH OF THE AISLE
 DIRECTLY IN FRONT OF OFFICE# 175?
  
 10) A-1.8 THE DOOR LEADING INTO
 CORRIDOR
 171 SWINGS AGAINST THE PATH OF EXITING
 SEE 1012.1.2 DOORS TO SWING IN THE
 EXITINGWHEN > 50 OCC LOAD.
  
 11) A-1.8 IT APPEARS THAT THERE IS SOME
 "BOTTLENECKING" WITH THE DOORS LEADING
 TO THE CORRIDOR AND VESTIBULE. SEE
 1003,2,3,2, ALSO PROVIDE A LIFE SAFETY
 PLAN.
  
 12) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, SEE
 E3.3 DETAIL FOR THE RAISED FLOOR,
 12A) PROVIDE THE LOCATION OF WHICH ROOMS
 WILL HAVE THE RAISED FLOOR?
 12A) WHAT MATERIALS WILL BE FOR THE
 FRAMING AND FLOOR?
 12B) INDICATE CONFORMANCE WITH
 ACCESSIBILITY RAMPS:
 12C) 11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
 12D) 11-4.8.3. CLEAR WIDTH. THE MINIMUM
 CLEAR WIDTH OF A RAMP SHALL BE 36".
 EXCEPTION: RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE
 LESS THAN 44 INCHES WIDE.
 12E) 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
 12F) 11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 13) E5.1 INDICATES THE USE OF
 BATTERIES,
 PROVIDE INFORMATION SHOWING COMPLIANCE
 WITH 308.2(9) H-4 OCCUPANCY.
  
 14) E5.1ALSO INDICATES THE USE OF A
 GENERATOR AND FUEL TANK, THE SITE PLAN
 DOES NOT INDICATE LOCATION?
  
 15) M7.2 HVAC UNIT DETAIL HANGS THE UNIT
 FROM THE BOTTOM OF THE BAR JOIST,
 PROVIDE ENGINEER OF RECORD THAT THIS
 DESIGN WILL BE ACCEPTABLE.
  
 16) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 WILL THERE BE ANY ELECTRIC LOCKS ON THE
 EXTERIOR DOORS, THERE IS NO INDICATION?
  
 17) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-04-20 Cont ID  
Sent By jleahy Date 2005-04-20 Time 23:26 Rev Time 1.00
Received By jleahy Date 2005-04-20 Time 23:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-04-11 Cont ID  
Sent By dpalmer Date 2005-04-11 Time 19:00 Rev Time 0.33
Received By dpalmer Date 2005-04-11 Time 19:00 Sent To  
Notes
2005-04-11 00:00:00 
  
 ************ UNSAT ****************
  
  
 *** PLEASE SEE NOTES BELOW.***
  
 1)NOTE: PLEASE SEE REVIEW DATED 12/15/04
 PLEASE SEE THE BELOW COMMENTS FOR GEN
 AND ASSCOIATED EQUIPMENT.
  
  
  
 1)NOTE: PLEASE SUBMIT ALLMANUFACTURE
 SPEC SHEETS SHOWING ALL INFORMATION FOR
 NEW PROPOSED GENERATOR, ATS. PLEASE
 PROVIDE PRIME MOVER INFORMATION.
 PLEASE ALSO PLANS WILL NOW BE CHECKED
 FOR ZONING REVIEW AS THIS WAS PREVIOUSLY
 A COMMENT FROM ZOING FOR LOCATION OF
 GENERATOR.
  
  
 2)NOTE: PLEASE SEE MAIN FOR GENERATOR IS
 SHOWN IN TENANT SPACE AND NOT GROUPED OR
 IN CLOSE PROXIMITY OF MAIN ELECTRICAL
 ROOM OR OTHER MAINS. PLEASE SEE MAIN FOR
 GENERATOR "WILL BE " REQUIRED IN CLOSE
 PROXIMITY OF EXISTING MAINS 1OF 2 AND
 2OF 2.
 THIS WAS PREVIOUSLY NOTED AND NOT
 ACCEPPTABLE BY THIS OFFICE OR FIRE
 MARSHAL'S OFFICE.
 PLEASE PROVIDE MORE INFORMATION ON
 THIS.
 230.72,230.76,230.79.ETC.
  
 3)NOTE: PLEASE SEE 700.7D, 230.95,240.13
 FOR GROUND FAULT REQUIREMNETS AND
 SIGNALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-04-11 Cont ID  
Sent By dpalmer Date 2005-04-11 Time 18:55 Rev Time 0.20
Received By dpalmer Date 2005-04-11 Time 18:55 Sent To  
Notes
2005-04-11 00:00:00REV TO REMOVE CEILING IN ELECTRICAL RM
 AND ADD SUSPENDED LIGHT FIXTURES.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-15 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 07:35 Rev Time 0.30
Received By dpalmer Date 2005-02-15 Time 07:35 Sent To  
Notes
2005-02-15 00:00:00REV'S.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-13 Cont ID  
Sent By dpalmer Date 2005-01-13 Time 09:11 Rev Time 1.00
Received By dpalmer Date 2005-01-13 Time 09:11 Sent To  
Notes
2005-01-13 00:00:00***** NOTES REDLINED ****
  
  
 GENERATOR MAIN/ ANN PANEL ATS STILL
 INDICATED ON E2.1,3.1,3.3
 NOTED AS GEN/ATS ETC REMOVED FROM SCOPE
 OF WORK AND DESIGN.
  
  
 PLEASE SEE REDLINED MISSING EQUIPMENT
 GRNDS FROM MAIN 2OF 2 TO PANEL DP.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By dpalmer Date 2004-12-15 Time 09:00 Rev Time 3.00
Received By dpalmer Date 2004-12-15 Time 08:36 Sent To  
Notes
2004-12-15 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT MANUFACTURE SPECS
 FOR GENERATOR, ATS, AND FUEL TANKS.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE.
 PLEASE SEE THERE ARE SOME MISSING.
 PLEASE SEE 700.12E FOR CIRCUITING EM/EXT
 LTS.
  
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 4)NOTE: PLEASE SEE 110.26 FOR ELECTRICAL
 RM CLERENCE. (153)
 PLEASE IDENTIFY PANELS ON PLANS, ELECT
 RM.
  
 5)NOTE: PLEASE SEE MAIN FOR GENERATOR IS
 SHOWN IN TENANT SPACE AND NOT GROUPED OR
 IN CLOSE PROXIMITY OF MAIN ELECTRICAL
 ROOM OR OTHER MAINS.
 PLEASE PROVIDE MORE INFORMATION ON
 THIS.
 230.72,230.76,230.79.
  
 6)NOTE: PLEASE SEE 700.7D, 230.95,240.13
 FOR GROUND FAULT REQUIRED ON GENERATOR
 ALSO.
 IT IS NOTED FOR DP BUT NOT FOR MAIN 1 OF
 2? OR GEN MAIN?
  
 7)NOTE: PLEASE SHOW TRANSFORMER
 GROUNDING PER 250.30.
  
 8)NOTE: PLEASE CLARIFY RMS 168,169,
 APPEAR TO BE SHOWN AS ONLY "SHOWERS"??
 ARE THESE ALSO BATH RMS?
  
 9)NOTE: PLEASE ALSO SUBMIT SPECS ON UPS
 SYSTEM.
 MUST SHOW A LISTING FROM A NRTL.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-01-04 Cont ID  
Sent By lmartine Date 2005-01-04 Time 14:05 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-01-13 Cont ID  
Sent By nmccray Date 2005-01-13 Time 15:03 Rev Time 0.00
Received By nmccray Date 2005-01-13 Time 15:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-28 Cont ID  
Sent By nmccray Date 2004-12-28 Time 11:30 Rev Time 0.00
Received By nmccray Date 2004-12-28 Time 09:29 Sent To  
Notes
2004-12-28 00:00:00FIRE REVIEW
  
 1) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 2) PLEASE REF NFPA 101 LIFE SAFETY CODE
 2000 EDITION CHAPTER 38.3.3.2 INTERIOR
 WALL AND CEILING FINISH.
  
 3) PLEASE INDICATE THE LOCATION OF FIRE
 EXTINGUISHERS ON FLOOR PLAN. (COULD NOT
 LOCATE)
  
 4) SHEET FA0.1 NOTE #17, SHOULD READ
 HVAC DUCT SMOKE DETECTORS SHALL BE
 CONNECTED TO THE FIRE ALARM CONTROL
 PANEL AND INITIATE A GENERAL FIRE ALARM
 NOT A SUPERVISORY.
  
 5) THE FIRE ALARM SYSTEM SHALL BE
 MONITORED BY A LICENSE UL LISTED FIRE
 ALARM COMPANY FOR CENTRAL STATION
 SERVICE.
  
 6) SEPARATE SHOP DRAWINGS AND PERMIT
 APPLICATION ARE REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER SYSTEMS REMODEL.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 11 Status P Date 2005-05-18 Cont ID  
Sent By pkrauss Date 2005-05-18 Time 14:16 Rev Time 0.30
Received By pkrauss Date 2005-05-18 Time 14:16 Sent To  
Notes
2005-05-18 00:00:00SUBMITTAL LETTER

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-04-20 Cont ID  
Sent By adarroug Date 2005-04-20 Time 15:13 Rev Time 0.00
Received By adarroug Date 2005-04-20 Time 15:13 Sent To E
Notes
2005-04-20 00:00:00TO "JLEAHY" DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-04-14 Cont ID  
Sent By adarroug Date 2005-04-14 Time 17:03 Rev Time 0.00
Received By adarroug Date 2005-04-14 Time 17:03 Sent To M
Notes
2005-04-14 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-04-05 Cont ID  
Sent By adarroug Date 2005-04-05 Time 14:17 Rev Time 0.00
Received By adarroug Date 2005-04-05 Time 14:17 Sent To  
Notes
2005-04-05 00:00:00TO "COMM" BD#25

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-29 Cont ID  
Sent By adarroug Date 2005-03-29 Time 10:06 Rev Time 0.00
Received By adarroug Date 2005-03-29 Time 10:06 Sent To B
Notes
2005-03-29 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-02-02 Cont ID  
Sent By adarroug Date 2005-02-02 Time 10:21 Rev Time 0.00
Received By adarroug Date 2005-02-02 Time 10:21 Sent To E
Notes
2005-02-02 00:00:00TO "E"BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-02 Cont ID  
Sent By adarroug Date 2005-02-02 Time 10:17 Rev Time 0.00
Received By adarroug Date 2005-02-02 Time 10:17 Sent To M
Notes
2005-02-02 00:00:00TO "M" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-24 Cont ID  
Sent By mjacobs Date 2005-01-24 Time 17:44 Rev Time 0.00
Received By mjacobs Date 2005-01-24 Time 17:44 Sent To P
Notes
2005-01-24 00:00:00TO "P" BOX./REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-14 Cont ID  
Sent By mjacobs Date 2005-01-14 Time 12:44 Rev Time 0.00
Received By mjacobs Date 2005-01-14 Time 12:44 Sent To B
Notes
2005-01-14 00:00:00TO "JW" DESK./RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-07 Cont ID  
Sent By mjacobs Date 2005-01-07 Time 15:16 Rev Time 0.00
Received By mjacobs Date 2005-01-07 Time 15:16 Sent To  
Notes
2005-01-07 00:00:00TO "COMM BD#45"/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mjacobs Date 2004-11-30 Time 13:07 Sent To  
Notes
2004-11-30 00:00:00SENT TO COMM BD#37. 12-7-04 SUBMITTALS
 WERE ADDED TO PACKAGE.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2005-04-19 Cont ID  
Sent By pkrauss Date 2005-04-19 Time 14:36 Rev Time 0.35
Received By pkrauss Date 2005-04-19 Time 14:36 Sent To  
Notes
2005-04-19 00:00:00LETTER FROM KAMM RE-LOCATING FIRE DAMPER
 FROM THE CEILING TO THE WALL
 PENETRATION.DUCT REVISION IS FROM
 SQUARE DUCT TO ROUND DUCT WITH NO DUCT
 SIZE OR CFM INDICATED.PROVIDE AS-BUILT
 DRAWING INDICATING SIZE OF ROUND DUCT
 AND TO WHAT EXTENT THE ROUND DUCT
 REPLACES SQUARE DUCT I.E., MAIN TRUNK
 RUN, BRANCH DUCT RUN, ETC.
  
 SUBMITTAL FOR TIE DOWN OF THE RTU &
 UPLIFT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-03-01 Cont ID  
Sent By pkrauss Date 2005-03-01 Time 07:45 Rev Time 1.20
Received By pkrauss Date 2005-03-01 Time 07:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-14 Cont ID  
Sent By pkrauss Date 2005-01-14 Time 07:31 Rev Time 0.55
Received By pkrauss Date 2005-01-14 Time 06:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-04 Cont ID  
Sent By pkrauss Date 2005-01-04 Time 07:44 Rev Time 3.50
Received By pkrauss Date 2005-01-03 Time 15:09 Sent To  
Notes
2005-01-04 00:00:00DENIED:
 1.PLAN SHEET C-1 INDICATES OCCUPANCY
 AS 410 PEOPLE WHEREAS THE O.A.
 CALCULATIONS PROVIDED (M0.1) IS ONLY
 DESIGNED FOR 292 PEOPLE.
  
 2.PLAN SHEET SP-1 BUILDING DATA
 SPECIFICATIONS, CLASSIFICATION AS
 FACTORY-INDUSTRIAL; PLEASE PROVIDE THE
 FOLLOWING INFORMATION:
 1) WHAT WILL BE MANUFACTURED
 2) INDICATE ANY HAZARDOUS CHEMICALS
 THAT
 MAY BE PRESENT OR STORED.
  
 3.THE FOLLOWING ROOMS ARE INDICATED
 AS
 HAVING A FIRE RESISTANCE RATING: 144,
 147, 147A, 148, 149, 151, 152, 154E,
 162, 163, 165B, 167, 168, 169, 172,
 195A.PLAN SHEET M2.1 DOES NOT
 INDICATE
 FIRE DAMPERS ON ANY PENETRATIONS.PER
 2001 FBC(M)607.6, PLANS SHALL PROVIDE
 SPECIFIC LOCATIONS FOR EACH FIRE DAMPER
 & ACCESS DOOR.
  
 4.PLAN SHEET M7.2 THE HVAC SUPPORT
 DETAIL INDICATES UNIT SUPPORT FROM THE
 BOTTOM OF THE BAR JOIST.PROVIDE A
 LETTER FROM THE STRUCTURAL ENGINEER
 INDICATING THAT JOIST IS DESIGNED FOR
 THIS APPLICATION FOR EQUIPMENT, PIPING
 DUCTS, ETC..
  
 5.PLAN SHEET M7.2 AUXILIARY DRAIN
 NOTE
 REFERENCES PLUMBING PLANS.PLAN SHEET
 P2.1 ONLY INDICATES THE PRIMARY DRAIN.
 PER 2001 FBC(M)307.2.3, AUXILIARY DRAIN
 IS TO TERMINATE AT A CONSPICUOUS POINT
 TO SERVE AS AN ALARM.PLEASE CLARIFY
 TERMINATION.
  
 6.PLAN SHEET E3.3 ROOM 152 SHOWS UPS
 BATTERY ROOM.PROVIDE NUMBER OF
 BATTERIES TO BE STORED IN THIS AREA.
 SHOW COMPLIANCE WITH 2002 NEC 480.9
 THROUGH 480.10.
  
 7.PLAN SHEET E3.3 INDICATES RAISED
 FLOOR.PLEASE CLARIFY PURPOSE AND WILL
 THIS AREA BE VENTED?
  
 PLEASE NOTE, ADDITIONAL COMMENTS MAY
 FOLLOW PENDING RESPONSE TO REVIEW
 COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-26 Cont ID  
Sent By jleech Date 2005-01-26 Time 16:18 Rev Time 1.00
Received By jleech Date 2005-01-26 Time 16:18 Sent To  
Notes
2005-01-26 00:00:00CHANGED PLANS FROM FLOOR MONTED W/C TO
 CHAIR CARRIERS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By pschmitz Date 2005-01-05 Time 09:26 Rev Time 0.00
Received By pschmitz Date 2005-01-05 Time 09:26 Sent To PC
Notes
2005-01-05 00:00:00PLUMBING PLAN REVIEW,PROVISO:
 BACKFLOW PREVENTER REQUIRED ON WATER
 SERVICE.
 ORDINANCE #2853-95
 END OF COMMENTS QUESTIONS CONTACT,
 PAUL SCHMITZ 561-805-6692

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-12-22 Cont ID  
Sent By jroach Date 2004-12-22 Time 08:32 Rev Time 0.00
Received By jroach Date 2004-12-22 Time 08:32 Sent To  
Notes
2004-12-22 00:00:0012/22/04 - ***PASSED***
  
 IMPROVEMENTS LIMITED TO THE INTERIOR OF
 THE BUILDING, THE ADDITION OF A
 HANDICAP RAMP ON THE WEST SIDE OF THE
 BUILDING AND A GENERATOR PAD.JOHN
 ROACH, PLANNER (561)
 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By jroach Date 2004-12-15 Time 13:02 Rev Time 0.00
Received By jroach Date 2004-12-15 Time 13:02 Sent To  
Notes
2004-12-15 00:00:0012/15/04 - ***FAILED***
  
 1) NEED TO APPLY FOR A MINOR PD
 AMENDMENT TO AMEND THE PREVIOUSLY
 APPROVED SITE PLAN AND LANDSCAPE PLAN.
 SUBMITTED PLANS SHOWS THE FOLLOWING
 MODIFICATIONS:
  
 1A) RECONFIGURATION OF THE DUMPSTER
 ENCLOSURE.
  
 1B) ADDITION OF PEDESTRIAN RAMP WHICH
 IMPEDES INTO APPROVED PARKING SPACES.
  
 1C) ELECTRICAL PLANS INDICATE THE
 ADDITION OF AN OUTDOOR GENERATOR WITH
 UNDERGROUND STORAGE TANK.SITE PLAN AND
 LANDSCAPE PLAN DOES NOT REFLECT THE
 LOCATION OF THE GENERATOR.
  
 PLEASE CALL JOHN ROACH, PLANNER AT (561)
 822-1435 FOR QUESTIONS/COMMENTS.