Plan Review Details - Permit 04111278
Plan Review Stops For Permit 04111278
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2006-02-28 Cont ID  
Sent By alange Date 2006-02-28 Time 13:59 Rev Time 0.33
Received By alange Date 2006-02-28 Time 13:59 Sent To  
Notes
2006-02-28 00:00:00BBQ AND SLAB OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2006-02-27 Cont ID  
Sent By alange Date 2006-02-27 Time 10:39 Rev Time 0.50
Received By alange Date 2006-02-27 Time 10:39 Sent To  
Notes
2006-02-27 00:00:00DENIED
  
 1.HOOD SPECS SUBMITTED ARE NOT RATED
 FOR A GAS BBQ.
 SUBMIT DETAILED SPECIFICATION DOCUMENTS
 SHOWING U.L. APPROVAL FOR AN OUTDOOR
 HOOD.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2006-01-24 Cont ID  
Sent By alange Date 2006-01-24 Time 16:15 Rev Time 0.50
Received By alange Date 2006-01-24 Time 16:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-11-30 Cont ID  
Sent By jwitmer Date 2005-11-30 Time 16:48 Rev Time 0.77
Received By jwitmer Date 2005-11-30 Time 16:47 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-09-12 Cont ID  
Sent By jwitmer Date 2005-09-12 Time 10:53 Rev Time 0.55
Received By jwitmer Date 2005-09-12 Time 10:43 Sent To PC
Notes
2005-09-12 00:00:00REVISION DATED 8-11-05

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-06-22 Cont ID  
Sent By jwitmer Date 2005-06-22 Time 07:34 Rev Time 1.22
Received By jwitmer Date 2005-06-22 Time 07:34 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 2.22
Received By jwitmer Date 2005-06-17 Time 12:36 Sent To PC
Notes
2005-06-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111278
 ADD: 6659 AUDABON TRACE
 CONT:DENNIS MARCUS
 TEL: (561)346-5667
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 5TH REVIEW
 ACTION: DENIED
  
  
 1)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
  
 A) TRUSS ANCHORS
 B) ROOFING ASSEMBLIES
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-05-23 Cont ID  
Sent By jgomez Date 2005-05-23 Time 15:31 Rev Time 1.00
Received By jgomez Date 2005-05-23 Time 14:13 Sent To PC
Notes
2005-05-23 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- TRUSS ANCHOR SCHEDULE STILL DOESN'T
 MATCH USP AND SIMPSON LATEST CATALOGUES.
 SEE CATALOGUE AND REVISE UPLIFT LOADS
 AND NUMBER OF NAILS USED. CHECK
 CONNECTOR BY CONNECTOR WITH CATALOGUE.
 OTHERWISE, PROVIDE COMPLETE ENGINEERING
 CALCULATIONS FOR NUMBER OF NAILS AND
 UPLIFT VALUES THAT DIFFER FROM THOSE
 TESTED & PUBLISHED BY THE MANUFACTURER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001 AND SEC. 1609.4.3 FBC 2001.
  
 2- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) CONNECTORS SPECIFIED ON TRUSS ANCHOR
 SCHEDULE AND PLANS AS REQUIRED BY RULE
 9B-72. GO TO WWW.FLORIDABUILDING.ORG TO
 FIND OUT ABOUT PRODUCT APPROVALS.
  
 B) AWNING WINDOW AS SHOWN ON NEW
 BATHROOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-04-13 Cont ID  
Sent By jgomez Date 2005-04-13 Time 14:14 Rev Time 1.00
Received By jgomez Date 2005-04-13 Time 14:14 Sent To E
Notes
2005-04-13 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR (NOTE: DADE COUNTY NOA
 ALONE IS NOT AUTOMATICALLY A FL.PRODUCT
 APPROVAL. STILL NEEDS FLORIDA PRODUCT
 APPROVAL OR APPLY FOR LOCAL PRODUCT
 APPROVAL AS REQ'D BY RULE 9B-72):
 A) FIXED WINDOWS. PROVIDE FLORIDA COVER
 PAGE OR APPLY FOR LOCAL PRODUCT
 APPROVAL.
 **NOTE: ALSO, NEED PRODUCT APPROVAL FOR
 72"X72" FIXED WINDOW. DADE COUNTY NOA
 SUBMITTED DOESN'T COVER THIS SIZE.
  
 B) SLIDING GLASS DOOR. NEED FLORIDA
 APPROVAL OR APPLY FOR LOCAL APPROVAL.
  
 C) TRUSS CONNECTORS SPECIFIED ON PLANS.
  
 D) CASEMENT WINDOWS ASSEMBLIES WITH
 WINDOWS TALLER THAN 63" TO MATCH THOSE
 SPECIFIED ON PLANS. PRODUCT APPROVAL
 SUBMITTED ONLY COVERS ASSEMBLIES UP TO
 63" HIGH. ALSO, PROVIDE FLORIDA APPROVAL
 OR APPLY FOR LOCAL APPROVAL.
  
 2- UPDATE TRUSS ANCHOR SCHEDULE. SEE USP
 OR SIMPSON LATEST CATALOGUEFOR TYPE
 AND NUMBER OF NAILS TO BE USED THAT WERE
 REVISED TO COMPLY WITH SEC. 1609.4.3 FBC
 2001. ALSO, CHECK UPLIFT VALUES SHOWN ON
 CATALOGUE. OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS THAT COMPLY WITH
 SEC. 1609.4.3 FBC WHEN TYPE AND NUMBER
 OF NAILS DON'T MATCH THOSE TESTED AND
 PUBLISHED BY THE MANUFACTURER.
  
 3- ENERGY CALCULATIONS STILL SHOW UNDER
 ATTIC AREA WITHOUT BEING REVISED TO
 COMPLY WITH SEC. 604.1.A.1 CHAPTER 13
 FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-24 Cont ID  
Sent By jgomez Date 2005-02-24 Time 11:48 Rev Time 0.00
Received By jgomez Date 2005-02-24 Time 11:48 Sent To M
Notes
2005-02-24 00:00:00CHECKLIST:
 1- PROVIDE COPY OF IMPACT FEES PAID
 RECEIPT.
  
 2- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) FIXED WINDOWS. SEE PLANS (PRODUCT
 APPROVAL SUBMITTED IS FOR SINGLE HUNG
 WINDOWS)
 B) SLIDING GLASS DOORS WITH IMPACT
 GLAZING IF USING IMPACT GLASS. OR NEED
 COMPLETE STORM SHUTTERS INFORMATION.
 C) STRUCTURAL CONNECTORS USED (SIMPSON
 AND USP). SEE PLANS.
 D) WINDOW MULLIONS.
 E) AWNING WINDOWS. SEE PLANS.
  
 3- BBQ ARE GENERALLY DESIGNED TO BE
 INSTALLED OUTDOORS. NEED MANUFACTURER'S
 SPECS CERTIFYING THAT BBQ WILL BE OK TO
 INSTALL IN PORCH.
 **NOTE: SAME COMMENT APPLIES TO HOOD.
  
 4- CLARIFY IF USING DOORS AND WINDOWS
 WITH IMPACT GLAZING OR SHUTTERS. PROVIDE
 COMPLETE INFORMATION FOR EITHER OPTION.
  
 5- CLARIFY CONNECTOR #3 SPECIFIED ON THE
 CONNECTOR SCHEDULE. WHERE IS USP HC-10
 AND 10-2 FOUND?. UNABLE TO LOCATE IN USP
 2005 CATALOGUE TO VERIFY CAPACITY AND
 FASTENERS.
  
 6- ENERGY CALCULATIONS: A) REVISE UNDER
 ATTIC AREA. SEE SEC. 604.1.A.1 CHAPTER
 13 FBC 2001.
 B) COMPLETE INFORMATION ON TOP OF FORM.
  
 7- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS. NEED RE-RECORDED NOC.
  
  
 IF YOU HAVE ANY AUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By jgomez Date 2004-12-15 Time 13:44 Rev Time 0.00
Received By jgomez Date 2004-12-15 Time 13:44 Sent To Z
Notes
2004-12-15 00:00:00BUILDING REVIEW CHECKLIST:
 1-BRING DRAWINGS TO PALM BEACH COUNTY
 TO
 VERIFY IF IMPACT FEES ARE DUE OR NOT.
 BRING BACK STAMPED DWGS & PAID RECEIPT.
  
 2-SPECIFY CONCRETE SLAB JOINTS OR WWM
 SUPPORTS AND SPACING AS REQ'D BY SEC.
 1909.3 FBC 2001.
  
 3-WINDOW BUCK NOTES CALL FOR BEVELED
 BUCK. BEVELED BUCK IS NOT ALLOWED. SEE
 SEC. 1707.4.4.2 FBC 2001 FOR REQUIRED
 INSTALLATION OF BUCKS.
  
 4-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR:
 A) CASEMENT WINDOWS (SEE SHEET A1
 SPECS)
 B) FIXED WINDOWS
 C) SLIDING GLASS DOORS.(SEE SHEET A1).
 D) FIREPLACE UL LISTING AND COMPLETE
 SPECS AS REQUIRED BY SEC. 2806 FBC
 2001.
 E) BBQ AS REQUIRED BY SEC. 2808 FBC
 2001
 AND OPTIONAL HOOD.
 F) STRUCTURAL CONNECTORS USED (SIMPSON
 OR USP).
 G) WINDOW MULLIONS.
 H) AWNING WINDOWS.
  
 5-CLARIFY IF USING STORM SHUTTERS OR
 MISSILE IMPACT GLAZING ON DOORS AND
 WINDOWS (SEE WINDOW NOTES SHEET A1 AND
 DESIGN CRITERIA AND NOTES ON SHEE A2).
  
 6-IF PROVIDING STORM SHUTTERS, THEN
 PROVIDE COMPLETE INFORMATION: KEY PLAN
 &
 COMPLETE INSTALLATION SCHEDULE (SEE
 SAMPLE). ALSO, INDICATE ON SHUTTER DWGS
 SPECIFIC MOUNTING CONDITIONS AND ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING
 TO
 THE DESIGN PRESSURES, EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (MASONRY OR
 CONCRETE).
  
 7-UPDATE TRUSS ANCHOR SCHEDULE. SEE
 CURRENT USP OR SIMPSON CATALOGUE FOR
 REVISED FASTENER TYPE AND NUMBER TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001
 REGARDING THE STRESS INCREASE. OR
 PROVIDE COMPLETE ENGINEERING ANALYSIS
 FOR NUMBER AND TYPE OF FASTENER
 DIFFERENT THAN THOSE TESTED AND
 PUBLISHED BY THE MANUFACTURER.
  
 8-A) SIZE OF FOOTING SPECIFIED ON TYP.
 WALL SECTION DOESN'T MATCH SIZE
 SPECIFIED ON FOUNDATION PLAN REVISE AS
 REQUIRED.
 B) FOOTING TO BE 12" MIN. BELOW GRADE
 AS
 REQUIRED BY SEC. 1804.1.3 FBC 2001.
  
 9-ENERGY CALCULATIONS: A) COMPLETE
 OWNER
 AND CONTRACTOR INFORMATION.
 B) CLARIFY IF USING METHOD A JUST FOR
 THE ADDITION OR FOR ENTIRE BUILDING.
 SEE
 SEC. 600 CHAPTER 13, FBC 2001.
 B) WHERE IS THE ADJACENT FRAMED WALL?
 C) REVISE UNDER ATTIC AREA. SEE SEC.
 604.1.A.1 CHAPTER 13 FBC 2001.
 D) OWNER/AGENT TO SIGN AND DATE FORM.
  
 10-REVISE SPECS FOR MONO PAD AT STEEL
 COLUMN. IT CALLS FOR #5 BARS AT 6 FEET
 OFF CENTER EACH WAY.
  
 11-REVISE DESIGN CRITERIA SPECS ON
 SHEET
 A2. IT CALL FOR 130MPH 3 SECOND GUST.
 WE
 ARE IN 140 MPH 3 SECOND GUST.
 ALSO, CLARIFY IF USING SHUTTERS OR
 DOORS
 AND WINDOWS WITH MISSILE IMPACT GLASS.
 NOTE CALLS FOR SHUTTERS AND OTHER NOTES
 ON SAME PLANS CALL FOR MISSILE IMPACT
 GLAZING FOR SOME TYPE OF WINDOWS.
  
 12-ARCHITECT TO INCLUDE IN HIS TITLE
 BLOCK ALL INFORMATION AS REQUIRED BY
 CHAPTER 481 FLORIDA STATUTES AND CHAPTER
  
 61G1-16.004 FLORIDA ADMINISTRATIVE
 CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-06-02 Cont ID  
Sent By btrobaug Date 2005-06-02 Time 15:03 Rev Time 0.50
Received By btrobaug Date 2005-06-02 Time 14:48 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-05-18 Cont ID  
Sent By btrobaug Date 2005-05-18 Time 16:29 Rev Time 0.50
Received By btrobaug Date 2005-05-18 Time 13:44 Sent To P
Notes
2005-05-18 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW. THE REDLINED ITEMS ON FROM THE
 PRIOR REVIEW WERE NOT CORRECTED.
  
 1} THE OCP AND FEEDERS FOR " NEW
 SUBPANEL" ARE NOT LISTED IN THE
 ORIGINATING PANEL("B").
  
 2} THE PANEL SCHEDULE SHOWS 100AMP MAINS
 IN THE "SUB-PANEL". THE RISER SHOWS #6
 FEEDER CONDUCTORS, SEE 310.16. PLEASE
 CORRELATE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-13 Cont ID  
Sent By btrobaug Date 2005-04-13 Time 17:29 Rev Time 0.50
Received By btrobaug Date 2005-04-13 Time 16:57 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-10 Cont ID  
Sent By btrobaug Date 2005-02-10 Time 14:14 Rev Time 0.50
Received By btrobaug Date 2005-02-10 Time 13:10 Sent To P
Notes
2005-02-10 00:00:00 
 PROVISO
 ~~~~~~~
  
 1} PROVIDE 60AMP OCP IN PANEL "B" TO
 PROTECT #6 FEEDERS TO NEW SUB PANEL.
  
 2} RECEPTACLE IN THE LAUNDRY ROOM WITHIN
 6' OF SINK TO BE GFI.
  
 3} PENINSULAR RECEPTACLE REQUIRED PER
 210.52(C)(3)
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-02 Cont ID  
Sent By btrobaug Date 2004-12-02 Time 12:54 Rev Time 0.50
Received By btrobaug Date 2004-12-02 Time 12:32 Sent To P
Notes
2004-12-02 00:00:00 
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
 2} PROVIDE A PANEL SCHEDULE FOR THE NEW
 PANELS BEING INSTALLED, ALSO SHOW
 LOCATION ON PLAN.
  
 3} PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8(A)(6).
  
 4} PLEASE SEE MISSING RECEPT REQ'D FOR
 A/C EQUIPMENT. 210.63.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 6} THE A/C DISCONNECT MUST COMPLY WITH
 110.26, IT CANNOT BE LOCATED BEHIND THE
 UNIT AS SHOWN.
  
 7} IF THERE IS NO SMOKE DETECTOR IN THE
 MASTER BEDROOM, ONE MUSTBE ADDED PER
 905.2.2 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-02-09 Cont ID  
Sent By adarroug Date 2006-02-09 Time 15:45 Rev Time 0.00
Received By adarroug Date 2006-02-09 Time 15:45 Sent To P
Notes
2006-02-09 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-01-18 Cont ID  
Sent By adarroug Date 2006-01-18 Time 16:32 Rev Time 0.00
Received By adarroug Date 2006-01-18 Time 16:32 Sent To P
Notes
2006-01-18 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 11:08 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 11:08 Sent To B
Notes
2005-11-15 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 09:43 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 09:43 Sent To B
Notes
2005-10-22 00:00:00TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-09-09 Cont ID  
Sent By adarroug Date 2005-09-09 Time 10:15 Rev Time 0.00
Received By adarroug Date 2005-09-09 Time 10:15 Sent To B
Notes
2005-09-09 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 16:42 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 16:41 Sent To B
Notes
2005-08-30 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 13:26 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 13:26 Sent To E
Notes
2005-05-31 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-05-09 Time 09:08 Rev Time 0.00
Received By adarroug Date 2005-05-09 Time 09:08 Sent To B
Notes
2005-05-09 00:00:00TO "PKRAUSS" BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 13:19 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 13:19 Sent To Z
Notes
2005-05-03 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-29 Cont ID  
Sent By adarroug Date 2005-03-29 Time 13:38 Rev Time 0.00
Received By adarroug Date 2005-03-29 Time 13:38 Sent To P
Notes
2005-03-29 00:00:00TO "KSTEVENS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-07 Cont ID  
Sent By adarroug Date 2005-02-07 Time 13:43 Rev Time 0.00
Received By adarroug Date 2005-02-07 Time 13:43 Sent To E
Notes
2005-02-07 00:00:00TO BTROBAUG DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-29 Cont ID  
Sent By mjacobs Date 2004-11-29 Time 16:45 Rev Time 0.00
Received By mjacobs Date 2004-11-29 Time 16:45 Sent To E
Notes
2004-11-29 00:00:00SENT TO "E" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-02-28 Cont ID  
Sent By tgordon Date 2006-02-28 Time 14:15 Rev Time 0.20
Received By tgordon Date 2006-02-28 Time 14:15 Sent To  
Notes
2006-02-28 00:00:00REVISION FOR GRILL.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2006-02-14 Cont ID  
Sent By tgordon Date 2006-02-14 Time 11:54 Rev Time 0.30
Received By tgordon Date 2006-02-14 Time 11:54 Sent To B
Notes
2006-02-14 00:00:00*** DENIED ***
 1)NEED DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS SHOWING U.L. APPROVAL AND
 HOOD IS FOR OUT DOOR USE (SEE ATTACHED
 SAMPLE).
  
 2) HOOD SUBMITTED IS FOR A RANGE NOT A
 GRILL.
  
 3) CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2005-05-19 Cont ID  
Sent By pkrauss Date 2005-05-19 Time 13:23 Rev Time 0.25
Received By pkrauss Date 2005-05-19 Time 13:23 Sent To  
Notes
2005-05-19 00:00:00PRE PHONE CONVERSATION WITH DENIS MARCUS
 (BUILDING CONTRACTOR); MECHANICAL
 CONTRACTOR TO APPLY SEPARATELY FOR
 PERMIT & WILL PROVIDE MECHANICAL PLANS
 AT THAT TIME.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date   Cont ID  
Sent By   Date 2005-05-10 Time   Rev Time 0.00
Received By hmoser Date 2005-05-10 Time 17:41 Sent To B
Notes
2005-05-10 00:00:00PLEASE PROVIDE MECHANICAL PLANS.PLEASE
 RESPONED TO COMMITS ABOUT LAST
 REVIEW4/14/05.
 PLAN REVIEW BY HAROLD MOSER 561-805-6719

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-04-14 Cont ID  
Sent By pkrauss Date 2005-04-14 Time 08:28 Rev Time 0.00
Received By pkrauss Date 2005-04-14 Time 06:41 Sent To  
Notes
2005-04-14 00:00:00DENIED:
 NO MECHANICAL PLANS SUBMITTED FOR REVEW.
 SEE COMMENT #3 BY JULIO GOMEZ, BUILDING
 PLANS EXAMINER.
  
 1.PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE GAS DRYER LOCATED IN THE LAUNDRY
 ROOM.
  
 2.PLAN SHEET A-2 INDICATES A PRE-FAB
 FIREPLACEWITH OUTSIDE AIR FOR
 COMBUSTION.TWO DIFFERENT PRE-FAB
 FIERPLACES WERE SUBMITTED.ONE OF THE
 SUBMITTALS INDICATE THE FIREPLACE IS
 VENTED ANDHAS MAKE UP AIR BUT THE OTHER
 SUBMITTAL IS A VENTLESS.PLEASE
 SUBMITTED ONLY ONE TYPE.PLEASE NOTE
 FOR THE VENTLESS FIREPLACE, COMBUSTION
 AIR CALCS ARE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-03-03 Cont ID  
Sent By pkrauss Date 2005-03-03 Time 15:24 Rev Time 0.30
Received By pkrauss Date 2005-03-03 Time 15:24 Sent To P
Notes
2005-03-03 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.ENERGY/MANUAL J CALCS (SEE
 BUILDING REVIEW FOR COMMENTS ON THE
 ENERGY CALCULATIONS).
  
 BBQ GRILLE & HOOD - THE MANUFACTURER'S
 SPECIFICATION SUBMITTED DOES NOT
 INDICATE APPROVAL FOR INSTALLATION OF
 THE GRILLE & HOOD IN A PARTIALLY
 ENCLOSED PATIO.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2004-12-14 Time   Rev Time  
Received By   Date 2004-12-14 Time   Sent To B
Notes
2004-12-14 00:00:00NO MECHANICAL PLANS

Review Stop P PLUMBING
Rev No 7 Status P Date 2006-02-14 Cont ID  
Sent By mperson Date 2006-02-14 Time 08:20 Rev Time 0.33
Received By mperson Date 2006-02-14 Time 08:19 Sent To M
Notes
2006-02-14 00:00:00REVISION:INSTALL BBQ GRILL WITH HOOD
 (NOTE ON GAS PERMIT #05071095 BBQ GRILL
 IS INDICATED AS FUTURE THIS REVISION
 ESTABLISHES A LOCATION)

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-01-23 Cont ID  
Sent By pschmitz Date 2006-01-23 Time 08:51 Rev Time 0.00
Received By pschmitz Date 2006-01-23 Time 08:51 Sent To B
Notes
2006-01-23 00:00:00REVISION
 ADD WASHER AND DRIP DRY IN LAUNDRY ROOM.

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-06-15 Cont ID  
Sent By kstevens Date 2005-06-15 Time 15:55 Rev Time 0.34
Received By kstevens Date 2005-06-15 Time 15:55 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-05-23 Cont ID  
Sent By kstevens Date 2005-05-23 Time 06:53 Rev Time 0.50
Received By kstevens Date 2005-05-23 Time 06:53 Sent To B
Notes
2005-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA STATUTES
  
 1) SHT A-1 SANITARY RISER DIAGRAM. THIS
 SAME RISER DIAGRAM HAS BEEN DENIED
 PREVIOUSLY. AN EXAMPLE OF A SANT. RISER
 DIAGRAM THAT WOULD MEET CODE
 REQUIREMENTS AND REFLECT THE FLOOR PLAN
 HAS BE SUBMITTED TO YOU TO HELP IN
 DRAWING A RISER FOR THIS PROJECT, BUT IT
 HAS BE DISREGARDED. CORRECT THE
 FOLLOWING:
 A. THE SHOWER UPSTREAM OF THE W/C IS
 NOT VENTED. SECTION 901.2.1.
 2) SEE ATTACHED SHEET CONCERNING FS
 533.80(2)(B) AND 4 TIMES THE FEE PLAN
 REVIEW CHARGED TO THE DESIGN
 PROFESSIONAL. THIS WILL BE CHARGED IF
 THE PLANS COME IN FOR THE SAME ITEM
 AGAIN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-04-09 Cont ID  
Sent By jleech Date 2005-04-09 Time 12:58 Rev Time 0.33
Received By jleech Date 2005-04-09 Time 12:58 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-05 Cont ID  
Sent By kstevens Date 2005-03-05 Time 12:12 Rev Time 0.46
Received By kstevens Date 2005-03-05 Time 12:12 Sent To  
Notes
2005-03-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A-1 FROM PREVIOUS REVIEW, SANT.
 RISER DIAGRAM DOES NOT MEET CODE
 REQUIREMENTS. SHOWER UPSTREAM OF THE
 WATER CLOSET IS NOT VENTED. SECTION
 901.2.1. - (SEE EXAMPLE OF RISER DIAGRAM
 THAT MEETS CODE ATTACHED TO COMMENT
 SHEET).
 2) A SEPARATE GAS PERMIT WITH PLANS IS
 REQUIRED.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By pkrauss Date 2005-03-03 Time 15:38 Rev Time 0.00
Received By jleech Date 2004-12-11 Time 09:01 Sent To  
Notes
2004-12-11 00:00:00DENIED;
 KITCHEN SINK IS NOT SHOWN ON PLUMBING
 RISER DLGRAM.
 BATHROOM VENT SHOULD BE UP STREAM OF
 W/C.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2005-11-14 Cont ID  
Sent By mmclean Date 2005-11-14 Time 07:30 Rev Time 0.00
Received By mmclean Date 2005-11-14 Time 07:29 Sent To I
Notes
2005-11-14 00:00:00APPROVING FOR A 8"WALL ON EXISTING POOL
 DECK ONLY. (1.5FT)

Review Stop Z ZONING
Rev No 3 Status F Date 2005-09-08 Cont ID  
Sent By mmclean Date 2005-09-08 Time 17:07 Rev Time 0.00
Received By mmclean Date 2005-09-08 Time 17:07 Sent To I
Notes
2005-09-08 00:00:00DENIED, - REVISION
 1. NEED TO PROVIDE DIMENSION OF THE (B)
 WALL SCALED.
 2. NEED TO SHOW THE LOCATION TO THE (B)
 WALL ON A FULL SIZE SURVEY/SITEPLAN.
 NEED TO MAKE SURE ALL SETBACKS ARE MET
 BASE ON THE IBIS GUIDELINES.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2005-05-06 Cont ID  
Sent By mmclean Date 2005-05-06 Time 18:51 Rev Time 0.00
Received By mmclean Date 2005-05-06 Time 18:51 Sent To I
Notes
2005-05-06 00:00:00APPROVING CBS ADDITION.MEETS SIDE
 SETBACKS AND REAR SETBACKS.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-04-14 Cont ID  
Sent By mmclean Date 2004-12-17 Time 11:09 Rev Time 0.45
Received By mmclean Date 2004-12-17 Time 11:09 Sent To  
Notes
2005-04-14 00:00:00DENIED:
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.SEE COMMENT #3 BY JULIO GOMEZ,
 BUILDING PLAN REVIEW.REVISE
 ACCORDINGLY.
  
 1.PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE LAUNDRY ROOM .
  
 2.PLAN SHEET A-2 INDICATES A PRE-FAB
 FIREPLACE WITH VENTING & OUTSIDE AIR FOR
 PRODUCTS OF COMBUSTION.TWO DIFFERENCT
 SUBMITTALS FOR THE FIREPLACE WERE
 SUBMITTED.PLEASE CLARIFY WHICH IS THE
 CORRECT SUBMITTAL.PLEASE NOTE, THE
 "VENTLESS" FIRE PLACE, PROVIDE
 COMBUSTION AIR CALCS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.