Plan Review Stops For Permit 04111278 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
11 |
Status |
P |
Date |
2006-02-28 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-02-28 |
Time |
13:59 |
Rev Time |
0.33 |
Received By |
alange |
Date |
2006-02-28 |
Time |
13:59 |
Sent To |
|
|
Notes |
2006-02-28 00:00:00 | BBQ AND SLAB OK |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
10 |
Status |
F |
Date |
2006-02-27 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-02-27 |
Time |
10:39 |
Rev Time |
0.50 |
Received By |
alange |
Date |
2006-02-27 |
Time |
10:39 |
Sent To |
|
|
Notes |
2006-02-27 00:00:00 | DENIED | | | | 1.HOOD SPECS SUBMITTED ARE NOT RATED | | FOR A GAS BBQ. | | SUBMIT DETAILED SPECIFICATION DOCUMENTS | | SHOWING U.L. APPROVAL FOR AN OUTDOOR | | HOOD. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
9 |
Status |
P |
Date |
2006-01-24 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-01-24 |
Time |
16:15 |
Rev Time |
0.50 |
Received By |
alange |
Date |
2006-01-24 |
Time |
16:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
P |
Date |
2005-11-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-11-30 |
Time |
16:48 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2005-11-30 |
Time |
16:47 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2005-09-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-09-12 |
Time |
10:53 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2005-09-12 |
Time |
10:43 |
Sent To |
PC |
|
Notes |
2005-09-12 00:00:00 | REVISION DATED 8-11-05 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2005-06-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-06-22 |
Time |
07:34 |
Rev Time |
1.22 |
Received By |
jwitmer |
Date |
2005-06-22 |
Time |
07:34 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2005-06-17 |
Time |
12:36 |
Sent To |
PC |
|
Notes |
2005-06-17 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 04111278 | | ADD: 6659 AUDABON TRACE | | CONT:DENNIS MARCUS | | TEL: (561)346-5667 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 5TH REVIEW | | ACTION: DENIED | | | | | | 1)PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 2)FL BLD CODE 1606.1.5: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORTS,MISSING REPORTS ARE AS | | FOLLOWS: | | | | A) TRUSS ANCHORS | | B) ROOFING ASSEMBLIES | | | | | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2005-05-23 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-05-23 |
Time |
15:31 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2005-05-23 |
Time |
14:13 |
Sent To |
PC |
|
Notes |
2005-05-23 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | 1- TRUSS ANCHOR SCHEDULE STILL DOESN'T | | MATCH USP AND SIMPSON LATEST CATALOGUES. | | SEE CATALOGUE AND REVISE UPLIFT LOADS | | AND NUMBER OF NAILS USED. CHECK | | CONNECTOR BY CONNECTOR WITH CATALOGUE. | | OTHERWISE, PROVIDE COMPLETE ENGINEERING | | CALCULATIONS FOR NUMBER OF NAILS AND | | UPLIFT VALUES THAT DIFFER FROM THOSE | | TESTED & PUBLISHED BY THE MANUFACTURER. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC | | 2001 AND SEC. 1609.4.3 FBC 2001. | | | | 2- PROVIDE FLORIDA OR LOCAL PRODUCT | | APPROVAL FOR: | | A) CONNECTORS SPECIFIED ON TRUSS ANCHOR | | SCHEDULE AND PLANS AS REQUIRED BY RULE | | 9B-72. GO TO WWW.FLORIDABUILDING.ORG TO | | FIND OUT ABOUT PRODUCT APPROVALS. | | | | B) AWNING WINDOW AS SHOWN ON NEW | | BATHROOM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT (561)805-6712. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2005-04-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-04-13 |
Time |
14:14 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2005-04-13 |
Time |
14:14 |
Sent To |
E |
|
Notes |
2005-04-13 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- PROVIDE FLORIDA OR LOCAL PRODUCT | | APPROVAL FOR (NOTE: DADE COUNTY NOA | | ALONE IS NOT AUTOMATICALLY A FL.PRODUCT | | APPROVAL. STILL NEEDS FLORIDA PRODUCT | | APPROVAL OR APPLY FOR LOCAL PRODUCT | | APPROVAL AS REQ'D BY RULE 9B-72): | | A) FIXED WINDOWS. PROVIDE FLORIDA COVER | | PAGE OR APPLY FOR LOCAL PRODUCT | | APPROVAL. | | **NOTE: ALSO, NEED PRODUCT APPROVAL FOR | | 72"X72" FIXED WINDOW. DADE COUNTY NOA | | SUBMITTED DOESN'T COVER THIS SIZE. | | | | B) SLIDING GLASS DOOR. NEED FLORIDA | | APPROVAL OR APPLY FOR LOCAL APPROVAL. | | | | C) TRUSS CONNECTORS SPECIFIED ON PLANS. | | | | D) CASEMENT WINDOWS ASSEMBLIES WITH | | WINDOWS TALLER THAN 63" TO MATCH THOSE | | SPECIFIED ON PLANS. PRODUCT APPROVAL | | SUBMITTED ONLY COVERS ASSEMBLIES UP TO | | 63" HIGH. ALSO, PROVIDE FLORIDA APPROVAL | | OR APPLY FOR LOCAL APPROVAL. | | | | 2- UPDATE TRUSS ANCHOR SCHEDULE. SEE USP | | OR SIMPSON LATEST CATALOGUEFOR TYPE | | AND NUMBER OF NAILS TO BE USED THAT WERE | | REVISED TO COMPLY WITH SEC. 1609.4.3 FBC | | 2001. ALSO, CHECK UPLIFT VALUES SHOWN ON | | CATALOGUE. OTHERWISE, PROVIDE COMPLETE | | ENGINEERING ANALYSIS THAT COMPLY WITH | | SEC. 1609.4.3 FBC WHEN TYPE AND NUMBER | | OF NAILS DON'T MATCH THOSE TESTED AND | | PUBLISHED BY THE MANUFACTURER. | | | | 3- ENERGY CALCULATIONS STILL SHOW UNDER | | ATTIC AREA WITHOUT BEING REVISED TO | | COMPLY WITH SEC. 604.1.A.1 CHAPTER 13 | | FBC 2001. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ (561)805-6712. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-02-24 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-02-24 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2005-02-24 |
Time |
11:48 |
Sent To |
M |
|
Notes |
2005-02-24 00:00:00 | CHECKLIST: | | 1- PROVIDE COPY OF IMPACT FEES PAID | | RECEIPT. | | | | 2- PROVIDE FLORIDA OR LOCAL PRODUCT | | APPROVAL FOR: | | A) FIXED WINDOWS. SEE PLANS (PRODUCT | | APPROVAL SUBMITTED IS FOR SINGLE HUNG | | WINDOWS) | | B) SLIDING GLASS DOORS WITH IMPACT | | GLAZING IF USING IMPACT GLASS. OR NEED | | COMPLETE STORM SHUTTERS INFORMATION. | | C) STRUCTURAL CONNECTORS USED (SIMPSON | | AND USP). SEE PLANS. | | D) WINDOW MULLIONS. | | E) AWNING WINDOWS. SEE PLANS. | | | | 3- BBQ ARE GENERALLY DESIGNED TO BE | | INSTALLED OUTDOORS. NEED MANUFACTURER'S | | SPECS CERTIFYING THAT BBQ WILL BE OK TO | | INSTALL IN PORCH. | | **NOTE: SAME COMMENT APPLIES TO HOOD. | | | | 4- CLARIFY IF USING DOORS AND WINDOWS | | WITH IMPACT GLAZING OR SHUTTERS. PROVIDE | | COMPLETE INFORMATION FOR EITHER OPTION. | | | | 5- CLARIFY CONNECTOR #3 SPECIFIED ON THE | | CONNECTOR SCHEDULE. WHERE IS USP HC-10 | | AND 10-2 FOUND?. UNABLE TO LOCATE IN USP | | 2005 CATALOGUE TO VERIFY CAPACITY AND | | FASTENERS. | | | | 6- ENERGY CALCULATIONS: A) REVISE UNDER | | ATTIC AREA. SEE SEC. 604.1.A.1 CHAPTER | | 13 FBC 2001. | | B) COMPLETE INFORMATION ON TOP OF FORM. | | | | 7- NOTICE OF COMMENCEMENT IS EXPIRED | | AFTER 90 DAYS. NEED RE-RECORDED NOC. | | | | | | IF YOU HAVE ANY AUESTIONS, PLEASE CALL | | JULIO GOMEZ AT (561)805-6712. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2004-12-15 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2004-12-15 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2004-12-15 |
Time |
13:44 |
Sent To |
Z |
|
Notes |
2004-12-15 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1-BRING DRAWINGS TO PALM BEACH COUNTY | | TO | | VERIFY IF IMPACT FEES ARE DUE OR NOT. | | BRING BACK STAMPED DWGS & PAID RECEIPT. | | | | 2-SPECIFY CONCRETE SLAB JOINTS OR WWM | | SUPPORTS AND SPACING AS REQ'D BY SEC. | | 1909.3 FBC 2001. | | | | 3-WINDOW BUCK NOTES CALL FOR BEVELED | | BUCK. BEVELED BUCK IS NOT ALLOWED. SEE | | SEC. 1707.4.4.2 FBC 2001 FOR REQUIRED | | INSTALLATION OF BUCKS. | | | | 4-PROVIDE COMPLETE FLORIDA OR LOCAL | | PRODUCT APPROVAL FOR: | | A) CASEMENT WINDOWS (SEE SHEET A1 | | SPECS) | | B) FIXED WINDOWS | | C) SLIDING GLASS DOORS.(SEE SHEET A1). | | D) FIREPLACE UL LISTING AND COMPLETE | | SPECS AS REQUIRED BY SEC. 2806 FBC | | 2001. | | E) BBQ AS REQUIRED BY SEC. 2808 FBC | | 2001 | | AND OPTIONAL HOOD. | | F) STRUCTURAL CONNECTORS USED (SIMPSON | | OR USP). | | G) WINDOW MULLIONS. | | H) AWNING WINDOWS. | | | | 5-CLARIFY IF USING STORM SHUTTERS OR | | MISSILE IMPACT GLAZING ON DOORS AND | | WINDOWS (SEE WINDOW NOTES SHEET A1 AND | | DESIGN CRITERIA AND NOTES ON SHEE A2). | | | | 6-IF PROVIDING STORM SHUTTERS, THEN | | PROVIDE COMPLETE INFORMATION: KEY PLAN | | & | | COMPLETE INSTALLATION SCHEDULE (SEE | | SAMPLE). ALSO, INDICATE ON SHUTTER DWGS | | SPECIFIC MOUNTING CONDITIONS AND ANCHOR | | TYPE AND SPACING TO BE USED ACCORDING | | TO | | THE DESIGN PRESSURES, EDGE DISTANCE, | | PANEL SPAN, CONNECTION TYPE AND | | STRUCTURE TO BE ATTACHED TO (MASONRY OR | | CONCRETE). | | | | 7-UPDATE TRUSS ANCHOR SCHEDULE. SEE | | CURRENT USP OR SIMPSON CATALOGUE FOR | | REVISED FASTENER TYPE AND NUMBER TO | | COMPLY WITH SEC. 1609.4.3 FBC 2001 | | REGARDING THE STRESS INCREASE. OR | | PROVIDE COMPLETE ENGINEERING ANALYSIS | | FOR NUMBER AND TYPE OF FASTENER | | DIFFERENT THAN THOSE TESTED AND | | PUBLISHED BY THE MANUFACTURER. | | | | 8-A) SIZE OF FOOTING SPECIFIED ON TYP. | | WALL SECTION DOESN'T MATCH SIZE | | SPECIFIED ON FOUNDATION PLAN REVISE AS | | REQUIRED. | | B) FOOTING TO BE 12" MIN. BELOW GRADE | | AS | | REQUIRED BY SEC. 1804.1.3 FBC 2001. | | | | 9-ENERGY CALCULATIONS: A) COMPLETE | | OWNER | | AND CONTRACTOR INFORMATION. | | B) CLARIFY IF USING METHOD A JUST FOR | | THE ADDITION OR FOR ENTIRE BUILDING. | | SEE | | SEC. 600 CHAPTER 13, FBC 2001. | | B) WHERE IS THE ADJACENT FRAMED WALL? | | C) REVISE UNDER ATTIC AREA. SEE SEC. | | 604.1.A.1 CHAPTER 13 FBC 2001. | | D) OWNER/AGENT TO SIGN AND DATE FORM. | | | | 10-REVISE SPECS FOR MONO PAD AT STEEL | | COLUMN. IT CALLS FOR #5 BARS AT 6 FEET | | OFF CENTER EACH WAY. | | | | 11-REVISE DESIGN CRITERIA SPECS ON | | SHEET | | A2. IT CALL FOR 130MPH 3 SECOND GUST. | | WE | | ARE IN 140 MPH 3 SECOND GUST. | | ALSO, CLARIFY IF USING SHUTTERS OR | | DOORS | | AND WINDOWS WITH MISSILE IMPACT GLASS. | | NOTE CALLS FOR SHUTTERS AND OTHER NOTES | | ON SAME PLANS CALL FOR MISSILE IMPACT | | GLAZING FOR SOME TYPE OF WINDOWS. | | | | 12-ARCHITECT TO INCLUDE IN HIS TITLE | | BLOCK ALL INFORMATION AS REQUIRED BY | | CHAPTER 481 FLORIDA STATUTES AND CHAPTER | | | | 61G1-16.004 FLORIDA ADMINISTRATIVE | | CODE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT (561)805-6712. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2005-06-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-06-02 |
Time |
15:03 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-06-02 |
Time |
14:48 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2005-05-18 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-05-18 |
Time |
16:29 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-05-18 |
Time |
13:44 |
Sent To |
P |
|
Notes |
2005-05-18 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. THE REDLINED ITEMS ON FROM THE | | PRIOR REVIEW WERE NOT CORRECTED. | | | | 1} THE OCP AND FEEDERS FOR " NEW | | SUBPANEL" ARE NOT LISTED IN THE | | ORIGINATING PANEL("B"). | | | | 2} THE PANEL SCHEDULE SHOWS 100AMP MAINS | | IN THE "SUB-PANEL". THE RISER SHOWS #6 | | FEEDER CONDUCTORS, SEE 310.16. PLEASE | | CORRELATE. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2005-04-13 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-04-13 |
Time |
17:29 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-04-13 |
Time |
16:57 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2005-02-10 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-02-10 |
Time |
14:14 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-02-10 |
Time |
13:10 |
Sent To |
P |
|
Notes |
2005-02-10 00:00:00 | | | PROVISO | | ~~~~~~~ | | | | 1} PROVIDE 60AMP OCP IN PANEL "B" TO | | PROTECT #6 FEEDERS TO NEW SUB PANEL. | | | | 2} RECEPTACLE IN THE LAUNDRY ROOM WITHIN | | 6' OF SINK TO BE GFI. | | | | 3} PENINSULAR RECEPTACLE REQUIRED PER | | 210.52(C)(3) | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2004-12-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2004-12-02 |
Time |
12:54 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2004-12-02 |
Time |
12:32 |
Sent To |
P |
|
Notes |
2004-12-02 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | | | 1} PLEASE PROVIDE A CALCULATION | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | EXISTING LOADS AND THE EXISTING OR | | PROPOSED SERVICE SPECIFICATIONS PER | | 215.15. | | | | 2} PROVIDE A PANEL SCHEDULE FOR THE NEW | | PANELS BEING INSTALLED, ALSO SHOW | | LOCATION ON PLAN. | | | | 3} PLEASE SHOW ALL RECEPTS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | -ED PER 210.8(A)(6). | | | | 4} PLEASE SEE MISSING RECEPT REQ'D FOR | | A/C EQUIPMENT. 210.63. | | | | 5} PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CURCUIT(S) ON PANEL | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | IN BEDROOMS ARE TO BE PROTECTED , | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | 6} THE A/C DISCONNECT MUST COMPLY WITH | | 110.26, IT CANNOT BE LOCATED BEHIND THE | | UNIT AS SHOWN. | | | | 7} IF THERE IS NO SMOKE DETECTOR IN THE | | MASTER BEDROOM, ONE MUSTBE ADDED PER | | 905.2.2 FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
12 |
Status |
N |
Date |
2006-02-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-02-09 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-02-09 |
Time |
15:45 |
Sent To |
P |
|
Notes |
2006-02-09 00:00:00 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2006-01-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-01-18 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-01-18 |
Time |
16:32 |
Sent To |
P |
|
Notes |
2006-01-18 00:00:00 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2005-11-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-11-15 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-11-15 |
Time |
11:08 |
Sent To |
B |
|
Notes |
2005-11-15 00:00:00 | TO "JWITMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2005-10-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-10-22 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-10-22 |
Time |
09:43 |
Sent To |
B |
|
Notes |
2005-10-22 00:00:00 | TO "JWITMER" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2005-09-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-09-09 |
Time |
10:15 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-09-09 |
Time |
10:15 |
Sent To |
B |
|
Notes |
2005-09-09 00:00:00 | TO "JWITMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2005-08-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-08-30 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-08-30 |
Time |
16:41 |
Sent To |
B |
|
Notes |
2005-08-30 00:00:00 | TO "JWITMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2005-05-31 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-05-31 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-05-31 |
Time |
13:26 |
Sent To |
E |
|
Notes |
2005-05-31 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2005-05-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-05-09 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-05-09 |
Time |
09:08 |
Sent To |
B |
|
Notes |
2005-05-09 00:00:00 | TO "PKRAUSS" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-05-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-05-03 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-05-03 |
Time |
13:19 |
Sent To |
Z |
|
Notes |
2005-05-03 00:00:00 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-03-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-03-29 |
Time |
13:38 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-03-29 |
Time |
13:38 |
Sent To |
P |
|
Notes |
2005-03-29 00:00:00 | TO "KSTEVENS" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-02-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-02-07 |
Time |
13:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-02-07 |
Time |
13:43 |
Sent To |
E |
|
Notes |
2005-02-07 00:00:00 | TO BTROBAUG DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-11-29 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2004-11-29 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2004-11-29 |
Time |
16:45 |
Sent To |
E |
|
Notes |
2004-11-29 00:00:00 | SENT TO "E" BOX. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
7 |
Status |
P |
Date |
2006-02-28 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-02-28 |
Time |
14:15 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2006-02-28 |
Time |
14:15 |
Sent To |
|
|
Notes |
2006-02-28 00:00:00 | REVISION FOR GRILL. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
F |
Date |
2006-02-14 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-02-14 |
Time |
11:54 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-02-14 |
Time |
11:54 |
Sent To |
B |
|
Notes |
2006-02-14 00:00:00 | *** DENIED *** | | 1)NEED DETAILED MANUFACTURE'S | | SPECIFICATION'S AND INSTALLATION | | INSTRUCTIONS SHOWING U.L. APPROVAL AND | | HOOD IS FOR OUT DOOR USE (SEE ATTACHED | | SAMPLE). | | | | 2) HOOD SUBMITTED IS FOR A RANGE NOT A | | GRILL. | | | | 3) CONSTRUCTION DOCUMENTS SHALL BE OF | | SUFFICIENT CLARITY. PER 2004 FBC 106.1.1 | | . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
N |
Date |
2005-05-19 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-05-19 |
Time |
13:23 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2005-05-19 |
Time |
13:23 |
Sent To |
|
|
Notes |
2005-05-19 00:00:00 | PRE PHONE CONVERSATION WITH DENIS MARCUS | | (BUILDING CONTRACTOR); MECHANICAL | | CONTRACTOR TO APPLY SEPARATELY FOR | | PERMIT & WILL PROVIDE MECHANICAL PLANS | | AT THAT TIME. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2005-05-10 |
Time |
|
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-05-10 |
Time |
17:41 |
Sent To |
B |
|
Notes |
2005-05-10 00:00:00 | PLEASE PROVIDE MECHANICAL PLANS.PLEASE | | RESPONED TO COMMITS ABOUT LAST | | REVIEW4/14/05. | | PLAN REVIEW BY HAROLD MOSER 561-805-6719 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2005-04-14 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-04-14 |
Time |
08:28 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2005-04-14 |
Time |
06:41 |
Sent To |
|
|
Notes |
2005-04-14 00:00:00 | DENIED: | | NO MECHANICAL PLANS SUBMITTED FOR REVEW. | | SEE COMMENT #3 BY JULIO GOMEZ, BUILDING | | PLANS EXAMINER. | | | | 1.PROVIDE COMBUSTION AIR CALCULATIONS | | FOR THE GAS DRYER LOCATED IN THE LAUNDRY | | ROOM. | | | | 2.PLAN SHEET A-2 INDICATES A PRE-FAB | | FIREPLACEWITH OUTSIDE AIR FOR | | COMBUSTION.TWO DIFFERENT PRE-FAB | | FIERPLACES WERE SUBMITTED.ONE OF THE | | SUBMITTALS INDICATE THE FIREPLACE IS | | VENTED ANDHAS MAKE UP AIR BUT THE OTHER | | SUBMITTAL IS A VENTLESS.PLEASE | | SUBMITTED ONLY ONE TYPE.PLEASE NOTE | | FOR THE VENTLESS FIREPLACE, COMBUSTION | | AIR CALCS ARE REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2005-03-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-03-03 |
Time |
15:24 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2005-03-03 |
Time |
15:24 |
Sent To |
P |
|
Notes |
2005-03-03 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR | | REVIEW.ENERGY/MANUAL J CALCS (SEE | | BUILDING REVIEW FOR COMMENTS ON THE | | ENERGY CALCULATIONS). | | | | BBQ GRILLE & HOOD - THE MANUFACTURER'S | | SPECIFICATION SUBMITTED DOES NOT | | INDICATE APPROVAL FOR INSTALLATION OF | | THE GRILLE & HOOD IN A PARTIALLY | | ENCLOSED PATIO.PLEASE CLARIFY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2004-12-14 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2004-12-14 |
Time |
|
Sent To |
B |
|
Notes |
2004-12-14 00:00:00 | NO MECHANICAL PLANS |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
7 |
Status |
P |
Date |
2006-02-14 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-02-14 |
Time |
08:20 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2006-02-14 |
Time |
08:19 |
Sent To |
M |
|
Notes |
2006-02-14 00:00:00 | REVISION:INSTALL BBQ GRILL WITH HOOD | | (NOTE ON GAS PERMIT #05071095 BBQ GRILL | | IS INDICATED AS FUTURE THIS REVISION | | ESTABLISHES A LOCATION) |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
P |
Date |
2006-01-23 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-01-23 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-01-23 |
Time |
08:51 |
Sent To |
B |
|
Notes |
2006-01-23 00:00:00 | REVISION | | ADD WASHER AND DRIP DRY IN LAUNDRY ROOM. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2005-06-15 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-06-15 |
Time |
15:55 |
Rev Time |
0.34 |
Received By |
kstevens |
Date |
2005-06-15 |
Time |
15:55 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2005-05-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-05-23 |
Time |
06:53 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2005-05-23 |
Time |
06:53 |
Sent To |
B |
|
Notes |
2005-05-23 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FLORIDA STATUTES | | | | 1) SHT A-1 SANITARY RISER DIAGRAM. THIS | | SAME RISER DIAGRAM HAS BEEN DENIED | | PREVIOUSLY. AN EXAMPLE OF A SANT. RISER | | DIAGRAM THAT WOULD MEET CODE | | REQUIREMENTS AND REFLECT THE FLOOR PLAN | | HAS BE SUBMITTED TO YOU TO HELP IN | | DRAWING A RISER FOR THIS PROJECT, BUT IT | | HAS BE DISREGARDED. CORRECT THE | | FOLLOWING: | | A. THE SHOWER UPSTREAM OF THE W/C IS | | NOT VENTED. SECTION 901.2.1. | | 2) SEE ATTACHED SHEET CONCERNING FS | | 533.80(2)(B) AND 4 TIMES THE FEE PLAN | | REVIEW CHARGED TO THE DESIGN | | PROFESSIONAL. THIS WILL BE CHARGED IF | | THE PLANS COME IN FOR THE SAME ITEM | | AGAIN. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2005-04-09 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-04-09 |
Time |
12:58 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2005-04-09 |
Time |
12:58 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2005-03-05 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-03-05 |
Time |
12:12 |
Rev Time |
0.46 |
Received By |
kstevens |
Date |
2005-03-05 |
Time |
12:12 |
Sent To |
|
|
Notes |
2005-03-05 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) SHT A-1 FROM PREVIOUS REVIEW, SANT. | | RISER DIAGRAM DOES NOT MEET CODE | | REQUIREMENTS. SHOWER UPSTREAM OF THE | | WATER CLOSET IS NOT VENTED. SECTION | | 901.2.1. - (SEE EXAMPLE OF RISER DIAGRAM | | THAT MEETS CODE ATTACHED TO COMMENT | | SHEET). | | 2) A SEPARATE GAS PERMIT WITH PLANS IS | | REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-03-03 |
Time |
15:38 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2004-12-11 |
Time |
09:01 |
Sent To |
|
|
Notes |
2004-12-11 00:00:00 | DENIED; | | KITCHEN SINK IS NOT SHOWN ON PLUMBING | | RISER DLGRAM. | | BATHROOM VENT SHOULD BE UP STREAM OF | | W/C. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2005-11-14 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-11-14 |
Time |
07:30 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-11-14 |
Time |
07:29 |
Sent To |
I |
|
Notes |
2005-11-14 00:00:00 | APPROVING FOR A 8"WALL ON EXISTING POOL | | DECK ONLY. (1.5FT) |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2005-09-08 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-09-08 |
Time |
17:07 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-09-08 |
Time |
17:07 |
Sent To |
I |
|
Notes |
2005-09-08 00:00:00 | DENIED, - REVISION | | 1. NEED TO PROVIDE DIMENSION OF THE (B) | | WALL SCALED. | | 2. NEED TO SHOW THE LOCATION TO THE (B) | | WALL ON A FULL SIZE SURVEY/SITEPLAN. | | NEED TO MAKE SURE ALL SETBACKS ARE MET | | BASE ON THE IBIS GUIDELINES. | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2005-05-06 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-05-06 |
Time |
18:51 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-05-06 |
Time |
18:51 |
Sent To |
I |
|
Notes |
2005-05-06 00:00:00 | APPROVING CBS ADDITION.MEETS SIDE | | SETBACKS AND REAR SETBACKS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2005-04-14 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2004-12-17 |
Time |
11:09 |
Rev Time |
0.45 |
Received By |
mmclean |
Date |
2004-12-17 |
Time |
11:09 |
Sent To |
|
|
Notes |
2005-04-14 00:00:00 | DENIED: | | NO MECHANICAL PLANS SUBMITTED FOR | | REVIEW.SEE COMMENT #3 BY JULIO GOMEZ, | | BUILDING PLAN REVIEW.REVISE | | ACCORDINGLY. | | | | 1.PROVIDE COMBUSTION AIR CALCULATIONS | | FOR THE LAUNDRY ROOM . | | | | 2.PLAN SHEET A-2 INDICATES A PRE-FAB | | FIREPLACE WITH VENTING & OUTSIDE AIR FOR | | PRODUCTS OF COMBUSTION.TWO DIFFERENCT | | SUBMITTALS FOR THE FIREPLACE WERE | | SUBMITTED.PLEASE CLARIFY WHICH IS THE | | CORRECT SUBMITTAL.PLEASE NOTE, THE | | "VENTLESS" FIRE PLACE, PROVIDE | | COMBUSTION AIR CALCS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|