Plan Review Details - Permit 04111262
Plan Review Stops For Permit 04111262
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2004-12-03 Cont ID  
Sent By jhiggins Date 2004-12-03 Time 16:40 Rev Time 0.00
Received By jwitmer Date 2005-06-17 Time 14:03 Sent To  
Notes
2004-12-03 00:00:00ADDRESS OK,LOT/BLOCK= 14TH FL, PH 4
2004-12-02 00:00:00OWNER UPDATE

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-07-11 Cont ID  
Sent By shill Date 2005-07-11 Time 12:01 Rev Time 0.50
Received By shill Date 2005-07-11 Time 12:01 Sent To PC
Notes
2005-07-11 00:00:00REVISED SHEET D2 (2A, 2B, D3 ALREADY
 REVIEWED BY JW)

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-06-17 Cont ID  
Sent By jwitmer Date 2005-06-17 Time 14:09 Rev Time 0.77
Received By jwitmer Date 2005-06-17 Time 14:03 Sent To  
Notes
2005-06-17 00:00:00REVISION 6-02-05JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-06-03 Cont ID  
Sent By jwitmer Date 2005-06-03 Time 09:50 Rev Time 0.33
Received By jwitmer Date 2005-06-03 Time 09:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-06-03 Cont ID  
Sent By jwitmer Date 2005-06-03 Time 09:32 Rev Time 0.33
Received By jwitmer Date 2005-06-03 Time 09:29 Sent To PC
Notes
2005-06-03 00:00:0006-03-05 RE: FLOOR X-RAYS (8)JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-08 Cont ID  
Sent By jwitmer Date 2005-02-08 Time 08:22 Rev Time 0.00
Received By jwitmer Date 2005-06-03 Time 09:29 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By jwitmer Date 2004-12-15 Time 09:55 Rev Time 1.11
Received By jwitmer Date 2004-12-15 Time 08:58 Sent To  
Notes
2004-12-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111262
 ADD: 622 N FLAGLER PH 4
 CONT:FIRST CONSTRUCTION
 TEL: (561)358-9289
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY, BETWEEN SHEETS 2A, 2B &
 D-1. SEE THE REQUIREMENT 1007.8.3 FOR
 TREAD DEPTH NOT BEING LESS THAN 11"
 MEASURED 12" FROM THE SMALL RADIUS.
  
 2) PROVIDE WHAT MATERIALS THE STRINGERS
 WILL BE MANUFACTURED FROM. SEE 1007.1.1
 NONCOMBUSTIBLE MATERIALS FOR A TYPE I OR
 TYPE II BLDGS.
  
 3) SHEET D-1 PROVIDE THE SPACING BETWEEN
 THE UPRIGHT PICKETS,
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 4) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5) TYPE I /II BLDG NO COMBUSTIBLES IN
 WALLS 609.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-06-30 Cont ID  
Sent By dpalmer Date 2005-06-30 Time 17:44 Rev Time 0.30
Received By dpalmer Date 2005-06-30 Time 17:41 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-20 Cont ID  
Sent By dpalmer Date 2005-06-20 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2005-06-20 Time 15:41 Sent To  
Notes
2005-06-20 00:00:00****** UNSAT ******
  
 1)NOTE: PLEASE SEE ALL NEW CIRCUITING
 FOR BATH GFI RECEPTS. THESE MUST BE 20A
 AND #12. 210.52D,210.11C3
  
 2)NOTE: PLEASE SEE A MIN OF 1.5KW
 REQUIRED FOR LAUNDRY/WASHER CIRCUIT.
 220.16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-12-01 Cont ID  
Sent By dpalmer Date 2004-12-01 Time 07:12 Rev Time 0.33
Received By dpalmer Date 2004-12-01 Time 07:11 Sent To  
Notes
2004-12-01 00:00:00REMODEL/RELOCATION OF EXISTING
 ELECTRICAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-07-05 Cont ID  
Sent By nmccray Date 2005-07-05 Time 13:22 Rev Time 0.00
Received By nmccray Date 2005-07-05 Time 13:21 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-02-07 Cont ID  
Sent By nmccray Date 2005-02-07 Time 12:48 Rev Time 0.00
Received By nmccray Date 2005-02-07 Time 12:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-22 Cont ID  
Sent By nmccray Date 2004-12-22 Time 14:56 Rev Time 0.00
Received By nmccray Date 2004-12-22 Time 14:56 Sent To  
Notes
2004-12-22 00:00:00FIRE REVIEW REF NFPA 101 LIFE SAFETY
 CODE 2000 EDITION
  
 1) NFPA 101 CODE TABLE 7.2.2.2.1 (A) NEW
 STAIRS
  
 2) NFPA 101 CODE 30.3.3.2 INTERIOR
 FINISH FOR WALLS AND CEILINGS SHALL BE
 MINIMUM OF CLASS "C".
  
 3) SEPARATE PLANS AND PERMIT
 APPLICATIONS ARE REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 14:30 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 14:30 Sent To P
Notes
2005-07-20 00:00:00TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-07-08 Cont ID  
Sent By pkrauss Date 2005-07-08 Time 14:03 Rev Time 0.00
Received By pkrauss Date 2005-07-08 Time 14:02 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 09:35 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 09:35 Sent To B
Notes
2005-07-06 00:00:00TO "JWITMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-28 Cont ID  
Sent By adarroug Date 2005-06-28 Time 10:09 Rev Time 0.00
Received By adarroug Date 2005-06-28 Time 10:09 Sent To E
Notes
2005-06-28 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 15:09 Rev Time 0.00
Received By shill Date 2005-06-08 Time 15:09 Sent To  
Notes
2005-06-16 00:00:00COMM BOARD #55
  
2005-06-08 00:00:00WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 16:05 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 16:05 Sent To B
Notes
2005-05-24 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-26 Cont ID  
Sent By mjacobs Date 2005-01-26 Time 10:53 Rev Time 0.00
Received By mjacobs Date 2005-01-26 Time 10:53 Sent To  
Notes
2005-01-26 00:00:00TO "COMM BD#11/RESUB."

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By mjacobs Date   Time   Rev Time  
Received By mjacobs Date 2004-11-24 Time 12:18 Sent To  
Notes
2004-11-24 00:00:00SENT TO "AD"BOX FOR PCN CLARIFICATION.
 PLANS COMM BD#11

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-03-14 Cont ID  
Sent By pkrauss Date 2006-02-02 Time 08:12 Rev Time 0.00
Received By pkrauss Date 2006-02-02 Time 08:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-08 Cont ID  
Sent By pkrauss Date 2005-07-08 Time 14:28 Rev Time 0.30
Received By pkrauss Date 2005-07-08 Time 14:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-02-08 Cont ID  
Sent By jwitmer Date 2005-02-08 Time 08:22 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-29 Cont ID  
Sent By pschmitz Date 2005-01-29 Time 13:41 Rev Time 0.00
Received By pschmitz Date 2005-01-29 Time 13:41 Sent To FIRE
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-23 Cont ID  
Sent By kstevens Date 2004-12-23 Time 17:54 Rev Time 0.33
Received By kstevens Date 2004-12-23 Time 17:54 Sent To  
Notes
2004-12-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT D1 SANITARY RISER DIAGRAM. THIS
 IS A SOVENT SYSTEM AND AS SUCH IS AN
 ENGINEERED SYSTEM. THE STACK THAT THE
 NEW BATHROOM IS BEING TIED INTO SHALL BE
 SHOWN AS EXISTING. SHOW WHERE THE NEW
 BATHROOM IS CONNECTED TO THE SOVENT
 STACK. INDICATE THE DEVELOPED LENGTH OF
 THE PIPING FROM THE STACK TO THE
 FIXTURES. SHOW THE AERATOR AND IF THERE
 IS AN OFFSET THE DEAERATOR REQUIRED FOR
 THIS ADDED BATHROOM. SECTION 104.2.1
 2) SUBMIT A WATER RISER DIAGRAM SHOW THE
 CONNECTION TO THE EXISTING WATER IN THE
 UNIT AND ALL PIPE SIZES, WATER HAMMER
 ARRESTORS ECT. SECTION 104.3.1.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]