Plan Review Stops For Permit 04111257 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2004-11-30 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2004-11-30 |
Time |
17:55 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2004-11-30 |
Time |
17:47 |
Sent To |
|
|
Notes |
2004-11-30 00:00:00 | | | | | NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5. | | | | PLANS MUST HAVE DESIGNER OF RECORD PRINT | | NAME & SIGN PLANS PER 104.2.1, F.B.C. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2004-11-24 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2004-11-24 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2004-11-24 |
Time |
13:23 |
Sent To |
E |
|
Notes |
2004-11-24 00:00:00 | SENT TO "E" BOX. |
|
|
|