Plan Review Details - Permit 04111257
Plan Review Stops For Permit 04111257
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-11-30 Cont ID  
Sent By btrobaug Date 2004-11-30 Time 17:55 Rev Time 0.33
Received By btrobaug Date 2004-11-30 Time 17:47 Sent To  
Notes
2004-11-30 00:00:00 
  
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5.
  
 PLANS MUST HAVE DESIGNER OF RECORD PRINT
 NAME & SIGN PLANS PER 104.2.1, F.B.C.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-24 Cont ID  
Sent By mjacobs Date 2004-11-24 Time 13:23 Rev Time 0.00
Received By mjacobs Date 2004-11-24 Time 13:23 Sent To E
Notes
2004-11-24 00:00:00SENT TO "E" BOX.