Plan Review Details - Permit 04111180
Plan Review Stops For Permit 04111180
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-04 Cont ID  
Sent By nmccray Date 2005-04-04 Time 11:06 Rev Time 0.00
Received By nmccray Date 2005-04-04 Time 11:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-09 Cont ID  
Sent By nmccray Date 2004-12-09 Time 10:22 Rev Time 0.00
Received By nmccray Date 2004-12-09 Time 10:22 Sent To  
Notes
2004-12-09 00:00:00FIRE REVIEW
  
 1) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 2) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR
 TO
 FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 3) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
 REVIEW NOTES FOR PERMITS
 04111181
 04111182
 04111184
 04111185
 04111186
 04111187
 04111188
 04111190
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-15 Cont ID  
Sent By adarroug Date 2005-03-15 Time 10:56 Rev Time 0.00
Received By adarroug Date 2005-03-15 Time 10:56 Sent To FIRE
Notes
2005-03-15 00:00:00TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-23 Cont ID  
Sent By mjacobs Date 2004-11-23 Time 08:53 Rev Time 0.00
Received By mjacobs Date 2004-11-23 Time 08:53 Sent To FIRE
Notes
2004-11-23 00:00:00SENT TO "FIRE" BOX.