Plan Review Details - Permit 04111073
Plan Review Stops For Permit 04111073
Review Stop B BUILDING (STRUCTURAL)
Rev No 86 Status P Date 2009-07-09 Cont ID  
Sent By jwitmer Date 2009-07-09 Time 08:45 Rev Time 1.00
Received By jwitmer Date 2009-07-09 Time 07:45 Sent To PC
Notes
2009-07-09 08:04:24BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL/ REVIEW:
  
 ACTION: REVIEWED
  
 SUBMITTALS: RFI 177-191

Review Stop B BUILDING (STRUCTURAL)
Rev No 85 Status P Date 2009-06-15 Cont ID  
Sent By jwitmer Date 2009-06-15 Time 10:45 Rev Time 0.77
Received By jwitmer Date 2009-06-15 Time 10:00 Sent To  
Notes
2009-06-15 10:46:43BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SHOP DRAWINGS EAST STAIR RAILINGS
  
 ACTION: REVIEWED
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 84 Status P Date 2009-06-15 Cont ID  
Sent By jwitmer Date 2009-06-15 Time 09:55 Rev Time 0.77
Received By jwitmer Date 2009-06-15 Time 09:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 83 Status P Date 2009-05-29 Cont ID  
Sent By jwitmer Date 2009-05-29 Time 16:43 Rev Time 0.77
Received By jwitmer Date 2009-05-29 Time 16:00 Sent To  
Notes
2009-05-29 16:44:31BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:
  
 ACTION: REVIEWED
  
  
 REVISIONS: A0.01 REVISION# 4

Review Stop B BUILDING (STRUCTURAL)
Rev No 82 Status P Date 2009-04-01 Cont ID  
Sent By jwitmer Date 2009-04-01 Time 16:23 Rev Time 0.44
Received By jwitmer Date 2009-04-01 Time 16:23 Sent To  
Notes
2009-04-01 16:25:11BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW:
  
 ACTION: REVIEWED
  
  
 FASCIA FRAMING @ COLONNADE (PHASE 2)

Review Stop B BUILDING (STRUCTURAL)
Rev No 81 Status P Date 2009-03-13 Cont ID  
Sent By jwitmer Date 2009-03-13 Time 15:44 Rev Time 0.55
Received By jwitmer Date 2009-03-13 Time 15:44 Sent To  
Notes
2009-03-13 15:46:35BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 FACIA REVIEW:
  
 ACTION: PROVISO
 1404.1.1 COMBUSTIBLE TRIM ALLOWED FOR THREE STORIES AND
 NOT MORE TTHAN 40'-0".F

Review Stop B BUILDING (STRUCTURAL)
Rev No 80 Status P Date 2009-03-13 Cont ID  
Sent By jwitmer Date 2009-03-13 Time 15:29 Rev Time 0.77
Received By jwitmer Date 2009-03-13 Time 15:29 Sent To PC
Notes
2009-03-13 15:30:24BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SHOP DRAWINGS EAST STAIR# 3
  
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 79 Status P Date 2009-03-13 Cont ID  
Sent By jwitmer Date 2009-03-13 Time 15:18 Rev Time 0.55
Received By jwitmer Date 2009-03-13 Time 15:18 Sent To PC
Notes
2009-03-13 15:20:15BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: STOREFRONT SHEETS 8& 9
  
 ACTION: STOREFRONT REVISED DETAIL 8 &9

Review Stop B BUILDING (STRUCTURAL)
Rev No 78 Status P Date 2009-02-06 Cont ID  
Sent By jwitmer Date 2009-02-06 Time 14:06 Rev Time 0.77
Received By jwitmer Date 2009-02-06 Time 14:06 Sent To  
Notes
2009-02-06 14:07:14STAIR # 4 DESIGN CALCULATIONS FOR STAIR AND RAILING

Review Stop B BUILDING (STRUCTURAL)
Rev No 77 Status F Date 2009-01-23 Cont ID  
Sent By jwitmer Date 2009-01-23 Time 13:31 Rev Time 0.77
Received By jwitmer Date 2009-01-23 Time 13:31 Sent To PC
Notes
2009-01-23 13:37:07BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW:
  
 EAST ROOF FACIA "CONNECTION DETAILS"
 ACTION: DENIED
  
 1) WIND DESIGN LOADS PROVIDED ON 8X11 INDICATE THE WIND
 DESIGN TO THE 2004 FBC AND ASCE 7-02 WHERE AS THE
 PROJECT IS PERMITTED UNDER THE 2001FBC AND REFRENCED
 STANDARD OF ASCE 7-98, PLEASE MAKE THE APPROPRIATE
 CORRECTIONS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 76 Status F Date 2009-01-23 Cont ID  
Sent By jwitmer Date 2009-01-23 Time 13:03 Rev Time 0.77
Received By jwitmer Date 2009-01-23 Time 13:03 Sent To PC
Notes
2009-01-23 13:06:35BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTALS-SHOP DRAWING REVIEW:
 SKYLINE STEEL
 WARREN LIBRARY PHASE IIA
 STAIRS, HANDRAIL, GAURDRAIL AND CALCULATION FOR STAIR#
 4
 ACTION: DENIED
 SHEET# 1
  
 1) COVERSHEET FOR CALCULATIONS: SIGNATURE IS COPIED,
 INDEX SHEEET OR PAGE WILL REQUIRE ORIGINAL SEAL AND
 SIGNATURE.
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 2) CALCULATION SHEET# 1 INDICATES THE STAIRHANDRAIL/
 GUARDRAIL SYSTEM IS DESIGNED TO THE 2004FBC AND CODE
 NOTATIONS WWIWTHIN THE DOCUMENT REFLECT THIS , BUT THIS
 PERMIT 04111073 IS A CURRENT AND ISSUED PERMIT UNDER
 THE 2001 FBC, PLEASE CORRECT ALL NOTATIONS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 75 Status F Date 2009-01-23 Cont ID  
Sent By jwitmer Date 2009-01-23 Time 09:38 Rev Time 1.22
Received By jwitmer Date 2009-01-23 Time 09:38 Sent To PC
Notes
2009-01-23 11:56:12BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTALS-SHOP DRAWING REVIEW:
 SKYLINE STEEL
 WARREN LIBRARY PHASE II
 AREA-B FRONT ENTRY HANDRAILS
  
 ACTION: DENIED
 SHEET# 1
  
 1) THE PLANS SUBMITTED AND WERE ISSUED WILL NEED ALSO
 TO BE UPDATED TO MEET REQUIREMENTS OF 107.5.2 2001 FBC
 STAIRWAYS SHALL HAVE HANDRAILS ON EACH SIDE. BOTH THE
 UPPER STAIRWAY AND LOWER STAIRWAY ARE MISSING
 HANDRAILS. THE UPPER PORTION ARE MISSING HANDRAILS ON
 BOTH OF THE OUTSIDE PARTS OF THE STAIR AND THE LOWER
 STAIR IS MISSING THE HANDRAIL ON ONE SIDE.
 1997 CODE COMMENTARY STATES THAT REQUIREMENTS THAT
 ATRAIRWAYS HAVE HANDRAILS ON BOTH SIDES IS ONE OF THESE
 MAINSTREAMED PROVISIONS (FROM CHAPTER 11). HANDRAILS ON
 BOTH SIDES AFFORDS AN AMBULATORY MOBILITY IMPAIRED
 PERSON A MEANS OF SUPPORT ON HIS/HER PREFERRED SIDE IN
 BOTH ASCENT AND DESCENT. THE 2004 CODE AND COMMENTARY
 ALSO AGREE IN ON THIS CODE SECTION.
  
 2) THE MISSING HANDRAILS SHALL BE CONTIUOUS HANDRAILS
 AT THE INSIDE TURN OF STAIRS 1007.5.5 EXCEPTION# 2.
  
 SHEET# 2
  
 3) SECTION A AT THE BOTTOM OF THE HANDRAIL THE
 HORIZONTAL EXTENSION DOES NOT INDICATE THE ELEVATION OF
 THE LOWER HORIZONTAL MEMBER, MUST BE NO HIGHER THAN 27"
 FROM THE FINISH FLOOR, PLEASE REVIEW
 11-4.4 PROTRUDING OBJECTS. NOTE THE SAME SITUATION
 OCCURS ON SHEET# 1 SECTION-B.
  
 SHEET# 3
  
 4) UPPER DETAIL INDICATES AT THE CURB A HORIZONTAL
 OPENING BETWEEN 5 1/2" TO 6 1/2" DEPENDING ON THE SLOPE
 OF THE CURB. PLEASE REVIEW SECTION 1015.3 2001 FBC
 OPENINGS TO REJECT A 4 " SPHERE.
  
 5) SECTION A DOES NOT PROVIDE A OVER ALL HEIGTH FROM
 THE FINISH FLOOR TO THE TOP OF THE RAIL. IT APPEARS THE
 TOTAL OF ALL MEASUREMENTS DOES NOT THE MINIMUM OF 42"
 IN HEIGHT SEE CIRCLED DIMENSIONS POSSIBLE ERROR?
 SECTION 1015.2 2001 FBC.
  
 6) COVERSHEET FOR CALCULATIONS: SIGNATURE IS COPIED,
 INDEX SHEEET OR PAGE WILL REQUIRE ORIGINAL SEAL AND
 SIGNATURE.
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 7) CALCULATION SHEET# 1 INDICATES THE STAIRHANDRAIL/
 GUARDRAIL SYSTEM IS DESIGNED TO THE 2004FBC AND CODE
 NOTATIONS WWIWTHIN THE DOCUMENT REFLECT THIS , BUT THIS
 PERMIT 04111073 IS A CURRENT AND ISSUED PERMIT UNDER
 THE 2001 FBC, PLEASE CORRECT ALL NOTATIONS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 74 Status P Date 2009-01-02 Cont ID  
Sent By jwitmer Date 2009-01-02 Time 11:11 Rev Time 0.66
Received By jwitmer Date 2009-01-02 Time 11:11 Sent To PC
Notes
2009-01-02 11:20:21BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL: EXTERIOR FRAMING DETAILS (REVISED) REVIEW:
  
 ACTION: REVIEWED
  
 SK-4 REVISION# 1
 SK-6 REVISION# 6
 SK-9 REVISION# 9
 SK-10-12
 EXTERIOR METAL STUD FRAMING SPECIFICATIONS
 WIND DESIGN CRITERIA ASCE 7-98
 ROOF WIND LOAD SCHEDULE AND PLAN
 ROOF WIND LOAD SCHEDULE COMPONENTS & CLADDING REVISION#
 4
 BUILDING ELEVATION WIND REVISION# 1
 CALCS FOR SK10-12
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 73 Status P Date 2009-01-02 Cont ID  
Sent By jwitmer Date 2009-01-02 Time 11:10 Rev Time 0.55
Received By jwitmer Date 2008-12-30 Time 17:05 Sent To  
Notes
2008-12-30 17:08:24BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW:
  
 ACTION: REVIEWED
  
 SUBMITTALS:
 1) LOUVER AT THTE CUPOLA, EXTERIOR FASTENING DETAILS
  
 2) GLASS HANDRAIL ENGINEERING
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 72 Status P Date 2008-12-22 Cont ID  
Sent By jwitmer Date 2008-12-22 Time 15:13 Rev Time 2.22
Received By jwitmer Date 2008-12-22 Time 15:13 Sent To  
Notes
2008-12-22 15:19:48BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW:CCD# 15
  
 ACTION: REVIEWED
  
 BUIULDING PROVISO: SHEET A1.03 ROOM# 03 OR LOBBY AREA
 IS STILL ACTING AS AN EXIT STAIRWAY AND MUST COMPLY
 WITH 1019.1.2 PENETRATIONS
 1019.1.2 PENETRATIONS.PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR
 FIRE DEPARTMENT
 COMMUNICATION AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES
 (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 712. THERE SHALL BE NO
 PENETRATIONS OR COMMUNICATION
 OPENINGS, WHETHER PROTECTED OR NOT, BETWEEN ADJACENT
 EXIT ENCLOSURES. SEE M1.03 .

Review Stop B BUILDING (STRUCTURAL)
Rev No 71 Status P Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 16:04 Rev Time 0.33
Received By jwitmer Date 2008-11-12 Time 16:04 Sent To  
Notes
2008-11-12 16:06:18BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: ROOFING
  
 ACTION: REVIEWED
  
 SUBMITTALS: NOA 07-1203.02 TYPE C92) PAGES 22-23
 REVISIONS:

Review Stop B BUILDING (STRUCTURAL)
Rev No 70 Status P Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 15:56 Rev Time 0.33
Received By jwitmer Date 2008-11-12 Time 15:56 Sent To  
Notes
2008-11-12 15:57:58BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:DAMAGED W18 BEAM AT LEVEL 2.
  
 ACTION: REVIEWED
  
 SUBMITTALS: DAMAGED W18 BEAM AT LEVEL 2

Review Stop B BUILDING (STRUCTURAL)
Rev No 69 Status P Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 15:52 Rev Time 0.33
Received By jwitmer Date 2008-11-12 Time 15:52 Sent To  
Notes
2008-11-12 15:53:52BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: RFI
  
 ACTION: REVIEWED
  
 SUBMITTALS: RFI # 25/ 90
  
 DAMAGE AT FLOOR DECK 2ND LEVEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 68 Status P Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 15:44 Rev Time 0.33
Received By jwitmer Date 2008-11-12 Time 15:44 Sent To  
Notes
2008-11-12 15:45:58BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: RFI# 120
  
 ACTION: REVIEWED
  
 SUBMITTALS: RFI# 120 4TH FLOOR BEAMS L4-B42-WET OR
 SOFFIT BEAMS

Review Stop B BUILDING (STRUCTURAL)
Rev No 67 Status F Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 15:30 Rev Time 0.33
Received By jwitmer Date 2008-11-12 Time 15:30 Sent To  
Notes
2008-11-12 15:38:04BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: RFI# 118
  
 ACTION: DENIED
  
 SUBMITTALS: RFI# 118
 THE HEADING OF THE RFI INDICATES THIS DOCUMENT IS FOR
 THE 2ND FLOOR CONNECTOR BEAM & FLOOR DECK ELEVATION BUT
 THE QUESTION INDICATES THE WORK AREA TO BE ON THE FIFTH
 AND SIXTH FLOOR PLEASE
 COORDINATE WORK AREA WWITHIN THE DOCUMENT.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 66 Status P Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 15:26 Rev Time 0.55
Received By jwitmer Date 2008-11-12 Time 15:26 Sent To  
Notes
2008-11-12 15:27:36BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: RFI# 117
  
 ACTION: REVIEWED
  
 SUBMITTALS: RFI# 117
 NEW W12X16 BEAM @ 2ND FLOOR OPENING

Review Stop B BUILDING (STRUCTURAL)
Rev No 65 Status P Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 15:12 Rev Time 0.55
Received By jwitmer Date 2008-11-12 Time 15:12 Sent To  
Notes
2008-11-12 15:18:21BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: RFI# 108
  
 ACTION: REVIEWED
  
 SUBMITTALS: RFI# 108
 TRUSS CONNECTION AT EXISTING COLUMN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 64 Status P Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 15:09 Rev Time 0.55
Received By jwitmer Date 2008-11-12 Time 15:08 Sent To  
Notes
2008-11-12 15:12:14BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:RFI
  
 ACTION: REVIEWED
  
 SUBMITTALS: RFI# 105
 HSS 8X4 TUBE

Review Stop B BUILDING (STRUCTURAL)
Rev No 63 Status P Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 14:56 Rev Time 0.77
Received By jwitmer Date 2008-11-12 Time 14:56 Sent To PC
Notes
2008-11-12 14:59:10BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: STRUCTURAL RFI
  
 ACTION: REVIEWED
  
 SUBMITTALS: RFI# 092B ADD A TIE-BEAM FOR THEPROPPER
 SLAB SUPPORT

Review Stop B BUILDING (STRUCTURAL)
Rev No 62 Status P Date 2008-11-07 Cont ID  
Sent By jwitmer Date 2008-11-07 Time 12:06 Rev Time 0.55
Received By jwitmer Date 2008-11-07 Time 12:06 Sent To PC
Notes
2008-11-07 12:07:08CUPOLA WINDOW SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 61 Status P Date 2008-10-08 Cont ID  
Sent By jwitmer Date 2008-10-08 Time 13:53 Rev Time 3.33
Received By jwitmer Date 2008-10-08 Time 13:53 Sent To  
Notes
2008-10-08 13:55:21BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ACTION: REVIEWED
  
  
 REVISIONS: ARCHITECTURAL & STRUCTURAL DATED 8-29-08

Review Stop B BUILDING (STRUCTURAL)
Rev No 60 Status F Date 2008-09-30 Cont ID  
Sent By jwitmer Date 2008-09-30 Time 14:27 Rev Time 0.33
Received By jwitmer Date 2008-09-30 Time 14:27 Sent To PC
Notes
2008-09-30 14:31:07BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW:
  
 ACTION: DENIED
  
 SUBMITTALS: 8"X11" REVISIONS TO VARIOUS SHEETS,
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 REVISIONS DO HAVE FEES, PLEASE RESUBMIT WITH THE PROPER
 TITLE BLOCK SIGNED AND SEALED PLANS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 59 Status P Date 2008-09-30 Cont ID  
Sent By jwitmer Date 2008-09-30 Time 14:26 Rev Time 0.88
Received By jwitmer Date 2008-09-30 Time 14:26 Sent To  
Notes
2008-09-30 14:27:293RD & 4TH FLOOR STRUCTURAL STEEL SHOP DRAWINGSFOR ROOF
 EAST SIDE OF ROTUNDA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 58 Status F Date 2008-09-04 Cont ID  
Sent By jwitmer Date 2008-09-04 Time 08:28 Rev Time 2.22
Received By jwitmer Date 2008-09-04 Time 08:28 Sent To  
Notes
2008-09-04 09:44:01BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ACTION: DENIED
  
 REVISION NO: M1.01
  
 THE MECHANICAL REVIEWERS QUESTIONED WHERE THE EXIT FOR
 THE NORTH AND SOUTH BASEMENT STAIR STARTED SINCE THIS
 REVISION INDICATED DUCTWORK THAT WENT TO THE RESTROOMS
 (BB04 & BB07) LOCATED ON
 THE ESTSIDE OF THE STACKS.
  
 WHEN DISCUSSING THIS ISSUE WITH THE MECHANICAL
 REVIEWERS AND MYSELF IT IS EVIDENT THAT TTHE EXIT STAIR
 ENCLOSURE WAS MISSING AND NOT CAUGHT DURING THE PLAN
 REVIEW. FBC 2001 3401.7.2.6 WHEN REPAIRS AND
 ALTERATIONS AMOUNTING MORE THAN 50% OF THE VALUE OF THE
 BUILDING DURING ANY 12 MONTH PERIOD, THE BUILDING OR
 STRUCTURE SHALL BE MADE TO CONFORM TO THE REQUIREMENTS
 FOR A NEW BUILDING OR STRUCTURE.
  
 THERE ARE ACTUALLY THREE CODE ISSUES LOCATED WITHIN THE
 TWO STAIRWAYS THAT LEAD TO THE BASEMENT:
  
 1) 1006.1.3 A STAIRWAY ENCLOSURE SHALL NOT BE USED FOR
 ANY PURPOSE OTHER THAN MEANS OF EGRESS. OPENINGS IN
 EXIT ENCLOSURES OTHER THAN UNEXPOSED EXTERIOR OPENINGS
 SHALL BE LIMITED TO THOSE NECESSARY FOR THE EXIT ACCESS
 TO THE ENCLOSURE FROM NORALLY OCCUPIABLE ROOMS AND FOR
 THE EGRESS FROM THE ENCLOSURE.
  
 2) 1006.1.4 THERE SHALL BE NO ENCLOSED USABLE SPACE
 WITHIN AN EXIT ENCLOSURE, INCLUDING UNDER STAIRS. SEE
 EXCEPTIONS.
  
 3) 1005.6.6 A STAIRWAY IN A SMOKEPROOF ENCLOSURE SHALL
 NOT CONTINUE BELOW GRADE LEVEL UNLESS AN APPROVED
 BARRIER IS PROVIDED AT GROUND LEVEL TO PREVENT PERSONS
 FROM ACCIDENTALLY CONTINUING INTO THE BASEMENT.
  
 PLEASE CALL TO DISCUSS THIS SITUATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 57 Status P Date 2008-08-29 Cont ID  
Sent By jwitmer Date 2008-08-29 Time 14:43 Rev Time 0.00
Received By jwitmer Date 2008-09-04 Time 08:18 Sent To PC
Notes
2008-08-29 14:46:06BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT: THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:
  
 ACTION: REVIEWED
  
 SUBMITTALS: PRESTRESSED JOIST AND SOFFIT BEAM DESIGN
 SHOP DRAWINGS, CALCULATIONS AND SHORING DETAILS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 56 Status P Date 2008-08-25 Cont ID  
Sent By jwitmer Date 2008-08-25 Time 15:32 Rev Time 3.33
Received By jwitmer Date 2008-08-25 Time 15:32 Sent To PC
Notes
2008-08-25 15:39:11BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SUBMITTALS
  
 ACTION: REVIEWED
  
 SUBMITTALS:
 RFI# 09 CONNECTINGLEVEL 2 SLAB TO SPRAYED CONCRETE
 WALL.
  
 RFI# 12-R001
  
 RFI# 14-ROO1 MASONRY OPOENINGS
  
 RFI# 32
  
 RFI# 36
  
 RFI# 75
  
 RFI# 85
  
 RFI# 90
  
 RFI # 93
  
 RFI# 102
  
 RFI# 104
  
 SKYLINE STEEL W18X35 BEAMS @ EL 120'-9" & ALTERNATE
 CONNECTION
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 55 Status P Date 2008-08-25 Cont ID  
Sent By jwitmer Date 2008-08-25 Time 14:14 Rev Time 2.20
Received By jwitmer Date 2008-08-25 Time 14:14 Sent To PC
Notes
2008-08-25 14:17:15BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 SUBMITTALS:
 REVIEW: EXTERIOR FRAMING DETAILS
  
 ACTION: REVIEWED/ PROVISO
  
 SK-9 BUILDING PROVISO: 2001 FBC TABLE 600 FOOTNOTE "E"
 NON- COMBUSTIBLE(4 STORY)

Review Stop B BUILDING (STRUCTURAL)
Rev No 54 Status P Date 2008-08-25 Cont ID  
Sent By jwitmer Date 2008-08-25 Time 13:34 Rev Time 1.55
Received By jwitmer Date 2008-08-25 Time 13:34 Sent To PC
Notes
2008-08-25 13:45:32BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: STRUCTURAL STEEL SHOP DRAWINGS
  
 ACTION: REVIEWED
  
 STRUCTURAL SHOP DRAWINGS - 1ST LEVEL FRAMING, 2ND LEVEL
 FRAMING, EMBED PLATES, DECKING & HIGH ROTUNDA ROOF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 53 Status P Date 2008-07-09 Cont ID  
Sent By jwitmer Date 2008-07-09 Time 11:31 Rev Time 0.55
Received By jwitmer Date 2008-07-09 Time 11:31 Sent To  
Notes
2008-07-09 11:32:49BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW:
  
 ACTION: REVIEWED
  
 SUBMITTALS:
 ALUMINUM STOEFRONT AND ENTRANCES SHOP DRAWINGS AND
 NOA07-0416.02

Review Stop B BUILDING (STRUCTURAL)
Rev No 52 Status P Date 2008-07-09 Cont ID  
Sent By jwitmer Date 2008-07-09 Time 11:28 Rev Time 1.33
Received By jwitmer Date 2008-07-09 Time 10:46 Sent To  
Notes
2008-07-09 11:30:49BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTALREVIEW:
  
 ACTION: REVIEWED
  
 SUBMITTALS:
 RFI #008 ANCHORING INTO EXISTING BRICK STRUCTURE

Review Stop B BUILDING (STRUCTURAL)
Rev No 51 Status P Date 2008-06-26 Cont ID  
Sent By jwitmer Date 2008-06-26 Time 13:11 Rev Time 0.77
Received By jwitmer Date 2008-06-26 Time 13:11 Sent To PC
Notes
2008-06-26 13:18:36BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:
  
 ACTION: REVIEWED
  
 SUBMITTALS: STRUCTURAL STEEL -TEMPORARY BRACE SHOP
 DRAWINGS FOR THE SUPPORT OF ROTUNDA BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 50 Status P Date 2008-06-26 Cont ID  
Sent By jwitmer Date 2008-06-26 Time 12:04 Rev Time 1.11
Received By jwitmer Date 2008-06-26 Time 12:04 Sent To  
Notes
2008-06-26 12:06:20BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:
  
 ACTION: REVIEWED
  
 SUBMITTALS: ROOFING PRODUCT APPROVAL & ENHANCED
 FASTENINGTARGET ENGINEERING
 NOA 03-0403.13
 TYPE/ SYSTEM PAGES 38-39

Review Stop B BUILDING (STRUCTURAL)
Rev No 49 Status F Date 2008-06-26 Cont ID  
Sent By jwitmer Date 2008-06-26 Time 11:20 Rev Time 1.11
Received By jwitmer Date 2008-06-26 Time 11:20 Sent To PC
Notes
2008-06-26 11:34:11BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:
  
 ACTION: DENIED
  
 SUBMITTALS: SINCE THE EXTERIOR METAL FRAMING PORTION OF
 THE PACKAGE IS SEALED INDIVIDUALLY THESE ARE OK, BUT
 THE SECOND HALF OF THE PACKAGE THE DESIGN CRITERIA BY
 THOMAS M. KELAHER HAS A COVER SHEET THAT IS ISGNED AND
 SEALED BUT DOESN'T REFERENECE HOW MANY PAGES ARE WITHIN
 THE DOCUMENT, PLEASE SEE 61G15-23.002(2)FL. ADMIN.
 CODE. A COVER SHEET OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX.
  
 FOR SCIBNERS ERRROR TO PLANS THE ENGINEER TO ITINAL AND
 DATE CHANGE ON PLANS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 48 Status P Date 2008-06-26 Cont ID  
Sent By jwitmer Date 2008-06-26 Time 11:18 Rev Time 1.11
Received By jwitmer Date 2008-06-26 Time 11:18 Sent To  
Notes
2008-06-26 11:20:03BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:
  
 ACTION: REVIEWED
  
 SUBMITTALS: NORR BUILDING CORP FOUNDATION / SOILS
 REPORTS FOR UNDER PINNING OF FOUNDATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 47 Status F Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 08:49 Rev Time 1.11
Received By jwitmer Date 2008-06-03 Time 08:49 Sent To PC
Notes
2008-06-03 08:52:33BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVISIONREVIEW: PHASE II REVISION# 4 CCD#13,
 SHEET S1.01
  
 ACTION: DENIED
  
 SHEET S1.01 CAN NOT BE REVIEWED AS CODE COMPLIANT UNTIL
 THE FOLLOWING BACKUP PAERWORK IS CORRECTED:
  
 1-3)COMPLIED.
  
 4) ALL DOCUMENTS INCLUDING SOILS REPORTS, SPECIALTY
 ENGINEERING REPORTS ANDSHOP DRAWINGS MUST BE REVIEWED
 BY THE ENGINEER OF RECORD FOR THE PROJECT.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW. SUCH ENGINEER OF RECORD
 SHALL STAMP WITH A SHOP DRAWING
 STAMP REVIEWED, OR REVIEWED WITH COMMENTS OR DENIED.
  
 NOTE PLEASE SUBMIT THE S1.01 DOCUMENTS WITH SOILS
 REPORTS AND ASSCIATED A. B. CHANCE FOUNDATION SYSTEM
 INFORMATION TOGETHER IN THE SAME SUMMITTAL. TANK YOU.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 46 Status F Date 2008-05-07 Cont ID  
Sent By jwitmer Date 2008-05-07 Time 12:06 Rev Time 1.50
Received By jwitmer Date 2008-05-07 Time 12:06 Sent To PC
Notes
2008-05-07 14:07:28BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW: PHASE II REVISION# 4 CCD#13, SHEET
 S1.01
  
 ACTION: DENIED
  
 SHEET S1.01 CAN NOT BE REVIEWED AS CODE COMPLIANT UNTIL
 THE FOLLOWING BACKUP PAERWORK IS CORRECTED:
  
 1) NORR BUILDING CORP. ENGINEERED FOUNDATION SOLUTIONS
 IS ADVERTISING THEM SELVES AS A ENGINEERING FIRM,
 EITHER REMOVE THE ENGINEERED FOUNDATION SOLUTIONS FROM
 THE LETTERHEAD OR PRODUCE A CERTIFICATE OF
 AUTHORIZATION INDICATING THAT THIS IS A ENGINEERING
 FIRM THAT IS LICENSED WITH THE STATE.
 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.THIS MAY BE ADDED BY HAND.
  
 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 2) THERE ARE (2) LETTERS SUBMITTED UNDER THE LETTERHEAD
 NORR BUILDING CORP. ENGINEERED FOUNDATION SOLUTIONS AND
 IN BOTH CASES DAVID A NORR HAS INDICATED THAT HE IS A
 ENGINEER / CONTRACTOR.
 PLEASE PROVIDE YOUR FLORIDE ENGINEERS REGISTRATION
 NUMBER, IN SEARCHING YOUR NAME WE CAN ONLY FIND A CBC
 LICENSE. THIS AGAIN IS ADVERTISING YOURSELF AS A
 REGISERED ENGINEER WITH THE STATE.
 61G15-23.002, 471.025.
  
 3) ENCLOSED IN THIS PACKAGE IS PAPERWORK FROM J-W
 ENGINEERING WHICH IS A COPY NOT ORIGINALS, I'MNOT
 QUITE SURE WHY WE HAVE COPIES AND NOT ORIGINALS. (3)
 ORIGINAL DOCUMENTS WILL BE REQUIRED
 WITH RAISED EMBOSSED SEALS AND ORIGINAL SINATURES.
 PLEASE PROVIDE DOCUMENTATION AS TO WHERE THIS REPORT
 STARTS AND ENDS IT APPEARS TO BE PIECE-MEALED TOGETHER
 A CUT AND PASTE JOB.
  
 NOTE: ONE COPY OF THE THREE NORR BUILDING CORP
 ENGINEERED FOUNDATION SOLUTIONS DOCUMENTS ARE BEING
 RETAINED FOR THE POSSIBILITY OF BEING FOWARDED TO THE
 BOARD OF ENGINEERS FOR A PEER REVIEW.
  
 4) ALL DOCUMENTS INCLUDING SOILS REPORTS, SPECIALTY
 ENGINEERING REPORTS ANDSHOP DRAWINGS MUST BE REVIEWED
 BY THE ENGINEER OF RECORD FOR THE PROJECT.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW. SUCH ENGINEER OF RECORD
 SHALL STAMP WITH A SHOP DRAWING
 STAMP REVIEWED, OR REVIEWED WITH COMMENTS OR DENIED.
  
 NOTE PLEASE SUBMIT THE S1.01 DOCUMENTS WITH SOILS
 REPORTS AND ASSCIATED A. B. CHANCE FOUNDATION SYSTEM
 INFORMATION TOGETHER IN THE SAME SUMMITTAL.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status P Date 2008-05-07 Cont ID  
Sent By jwitmer Date 2008-05-07 Time 12:02 Rev Time 5.55
Received By jwitmer Date 2008-05-07 Time 12:02 Sent To PC
Notes
2008-05-07 12:06:14BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW:
  
 ACTION: REVIEWED W/ EXCEPTION TO SHEET S1.01 REVISION 4
 CCD# 13
  
  
 REVISIONS: BOTH REVISIONS #3 PHASE II DATED 5/15/07 &
 REVISION# 4 CCD#13 WITH EXCEPTION TO SHEET S1.01
 REVIEWED
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status P Date 2008-05-06 Cont ID  
Sent By jwitmer Date 2008-05-06 Time 16:20 Rev Time 4.44
Received By jwitmer Date 2008-05-06 Time 16:19 Sent To  
Notes
2008-05-06 16:21:33BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION # CCP# 13
  
 ACTION:REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status P Date 2008-04-30 Cont ID  
Sent By jwitmer Date 2008-04-30 Time 11:48 Rev Time 1.22
Received By jwitmer Date 2008-04-30 Time 11:48 Sent To  
Notes
2008-04-30 11:57:17BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL WARREN LIBRARY
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:
  
 ACTION: REVIEWED
  
 REVISIONS:
 LETTER CONCRETE RESTORATION PROGRAM: USE OF BARSPLICE.
 SK-12 COLUMN DETAIL
 SK-13 BEAM REPAIR
 LETTER COVERAGE OFSTEEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status P Date 2008-03-10 Cont ID  
Sent By jwitmer Date 2008-03-10 Time 12:58 Rev Time 0.77
Received By jwitmer Date 2008-03-10 Time 12:58 Sent To PC
Notes
2008-03-10 13:00:25ROTUNDA BUILDING REINFORCED CONCRETE REPAIRS:
 SK-10
 SK-11

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status P Date 2008-01-29 Cont ID  
Sent By jwitmer Date 2008-01-29 Time 08:46 Rev Time 1.33
Received By jwitmer Date 2008-01-29 Time 08:46 Sent To PC
Notes
2008-01-29 08:48:46DETERIORATED REINFORCED CONCRETE REPAIR FOR ROTUNDA
 SK1-SK9

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status P Date 2008-01-07 Cont ID  
Sent By jwitmer Date 2008-01-07 Time 12:41 Rev Time 1.33
Received By jwitmer Date 2008-01-07 Time 12:41 Sent To  
Notes
2008-01-07 12:49:34300 PEMBROKE PLACEREVISIONS
 PERMIT: 04111073
 ADDRESS: 300 PEMBROKE PLACE
  
 ACTION: REVIEWED
  
 REVISION NO 63: INFILL EXISTING MASONARY OPENINGS
 REVISION NO 64: CONNECTION TO EXISTING 2ND FLOOR TO
 EXTERIOR WALL
 REVISION NO 65: REPAIR DAMAGED MASONARY@ EXTERIOR WALLS

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status F Date 2007-10-31 Cont ID  
Sent By jwitmer Date 2007-10-31 Time 12:43 Rev Time 6.50
Received By jwitmer Date 2007-10-31 Time 12:42 Sent To  
Notes
2007-10-31 13:28:23BUILDING PLAN REVIEW
 PERMIT:04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)687-4807
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW DATED, ARCHITECT 9/28/07STRUCTURAL
 9/27/07
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 3 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 YOUR PROJECT WILL REQUIRE A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE.105.13/ 2001 FBC OR106.1* /2004
 SUBMITTAL DOCUMENTSWEST PALM BEACH ADMINISTRATIVE
 CODE.
 THIS IS A PHASED PERMIT, THE SECOND PHASE WILL ONLY
 REQUIRE A THRESHOLD INSPECTOR UNTIL THE STRUCTURAL
 COMPONENTS
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) NOTE, PRODUCT APPROVALS THAT WERE REVIEWED AS CODE
 COMPLIANT UNDER THE 2001 FBC ARE STILL IN EFFECT
 CURRENT, EVEN THOUGH THE REPORT EXPIRATION DATE MAY
 HAVE PAST, THIS COMMENT HAS BEEN REVIEWED BY B.O. NEIL
 MELICK.
  
 2) ARCHITECT LOYD MEYERS PLEASE SEE FL ADIMISTRATIVE
 CODE 61G1-16.002 SEALS TO BE APPROXIMAATELY 2" IN
 DIAMETER.
  
 3)SHEET A1.01 IS MISSING THE CERTIFICATE OF
 AUTHORIZATION IN THE TITLE BLOCK FOR THE FOLLOWING
 ENGINEERS, 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3A) CIVIL, SHALLOWAY FOY RAYMAN & NEWELL
 3B) STRUCTURAL, SLIDER ENGINEERING GROUP
  
 4) LANDSCAPING WINSTON LEE ASSOCATES, 481.219 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE NUMBER TO
 EACH SHEET.THIS MAY BE ADDED BY HAND.
  
 5) THE ARCHITECTURAL SHEETS HAVE BEEN SEPERATED FROM
 THE MEP SHEETS, UNABLE TO DO A COMPLETE REVIEW!
  
 6)SHEET A4.06 DETAIL# 9 INDICATES TREATED WOOD
 BLOCKING TO BE USED IN THE CUPOLA AS BLOCKING, PLANS DO
 NOT MAKE IT CLEAR THIS IS TO BE FIRE RETARDANT TREATED
 WOOD, TYPE II BUILDING CONCEALED SPACES, 609.2.1.
  
 7)SHEET S4.10 INDICATES THE USE OF HELICAL PIER
 SYSTEM, THE PLANS DO NOT CALL OUT AS TO THE TYPE OF
 HELICAL ANCHOR TO BE USED, THE SIZE OF THE ANCHOR AND
 THE UPLIFT LOADS AND GRAVITY LOADS THAT IT WILL BE
 REQUIRED FOR IT TO RESIST.
 ALSO NO GEOTECHNICAL REPORT HAS BEEN SUBMITTED
 INDICATING THE MINIMUM SAFE BEARING VALUE THAT EACH
 PIEER WILL NEED TO ASSUME.104.1.2/ 1606.1.3. PLANS
 INDICATE THE EXTERIOR WALLS ARE TO BE SPRAYED WITH
 CONCRETE, IS THIS TO BE GUNITE, IN EITHER CASE WHAT IS
 THE MIX TO BE USED?
  
 8) SHEET S4.07 NEEDS THE ENGINEER TO DATE STAMP ONE
 SHEET OF STRUCTURAL PLANS. 102.1* WHERE, IN ANY
 SPECIFIC CASE, DIFFERENT SECTIONS OF THIS CODE SPECIFY
 DIFFERENT MATERIALS, METHODS OF CONSTRUCTION OR OTHER
 REQUIREMENTS, THE MOST RESTRICTIVE SHALL GOVERN. WHERE
 THERE IS A CONFLICT BETWEEN A GENERAL REQUIREMENT AND A
 SPECIFIC REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECODS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status F Date 2007-10-30 Cont ID  
Sent By jwitmer Date 2007-10-30 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2007-10-30 Time 20:17 Sent To  
Notes
2007-10-30 14:34:35BUILDING PLAN REVIEW
 PERMIT:04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)687-4807
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 3 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 YOUR PROJECT WILL REQUIRE A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE.105.13/ 2001 FBC OR106.1* /2004
 SUBMITTAL DOCUMENTSWEST PALM BEACH ADMINISTRATIVE
 CODE.
 THIS IS A PHASED PERMIT, THE SECOND PHASE WILL ONLY
 REQUIRE A THRESHOLD INSPECTOR UNTIL THE STRUCTURAL
 COMPONENTS
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) NOTE, PRODUCT APPROVALS THAT WERE REVIEWED AS CODE
 COMPLIANT UNDER THE 2001 FBC ARE STILL IN EFFECT
 CURRENT, EVEN THOUGH THE REPORT EXPIRATION DATE MAY
 HAVE PAST, THIS COMMENT HAS BEEN REVIEWED BY B.O. NEIL
 MELICK.
  
 2) ARCHITECT LOYD MEYERS PLEASE SEE FL ADIMISTRATIVE
 CODE 61G1-16.002 SEALS TO BE APPROXIMAATELY 2" IN
 DIAMETER.
  
 3)SHEET A1.01 IS MISSING THE CERTIFICATE OF
 AUTHORIZATION IN THE TITLE BLOCK FOR THE FOLLOWING
 ENGINEERS, 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3A) CIVIL, SHALLOWAY FOY RAYMAN & NEWELL
 3B) STRUCTURAL, SLIDER ENGINEERING GROUP
  
 4) LANDSCAPING WINSTON LEE ASSOCATES, 481.219 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE NUMBER TO
 EACH SHEET.THIS MAY BE ADDED BY HAND.
  
 5) THE ARCHITECTURAL SHEETS HAVE BEEN SEPERATED FROM
 THE MEP SHEETS, UNABLE TO DO A COMPLETE REVIEW!
  
 6) A2.03 2J REPLACEMENT WINDOW WITHDOUBLE DOORS
 REVISION 24'-2" VERSES 25'-10"THERE ARE NO STRUCTURAL
 SHEETS SUBMITTED TO INDICATE HOW THE HEIGHT CHANGE
 EFFECTS THE HEAD OFTHE ARCH? ADDITIONAL INFORMATION
 REQUIED 104.1.2.
  
 7) A3.02 FUEL SPILL CONTAINMENT, PLEASE PROVIDE
 ADDITIONAL INFORMATION ON THIS REVISION. 104.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 8) COMMENT NOT CAUGHT IN PREVIOUS REVIEWS, SHEET A1.01
 DOOR NUMBER 2 & 3 PAIRS OF DOORS, OPPOSING DOORS PLEASE
 SEE 11-4.13.7 TWO DOORS IN SERIES.
  
 9) SHEET A6.05 DETAIL# 3 INDICATES A NEW CONCRETE BEAM,
 HOW WILL THE BRICK FACADE BE HELD IN PLACE?THERE ARE
 NO STRUCTURAL PLANS INDICATING THIS REVISION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECODS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status F Date 2007-02-06 Cont ID  
Sent By jwitmer Date 2007-02-06 Time 10:30 Rev Time 0.77
Received By jwitmer Date 2007-02-06 Time 10:30 Sent To PC
Notes
2007-02-06 10:31:47BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)723-2443
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SHOP DRAWING 2ND REVIEW
 ACTION: DENIED
  
 ORNAMENTAL GLASS GUARD/ HANDRAIL SHOP DRAWING
  
 11-4.9.4
 11-4.9.4 HANDRAILS.
 STAIRWAYS SHALL HAVE HANDRAILS AT BOTH SIDES OF ALL
 STAIRS. HANDRAILS SHALL COMPLY WITH SECTION 11-4.26 AND
 SHALL HAVE THE FOLLOWING FEATURES:
  
 (2)IF HANDRAILS ARE NOT CONTINUOUS, THEY SHALL
 EXTEND AT LEAST 12 INCHES (305 MM) BEYOND THE TOP RISER
 AND AT LEAST 12 INCHES (305 MM) PLUS THE WIDTH OF ONE
 TREAD BEYOND THE BOTTOM RISER. AT THE TOP, THE
 EXTENSION SHALL BE PARALLEL WITH THE FLOOR OR GROUND
 SURFACE. AT THE BOTTOM, THE HANDRAIL SHALL CONTINUE TO
 SLOPE FOR A DISTANCE OF THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE EXTENSION SHALL BE
 HORIZONTAL [SEE FIGURE 11-19 (C) AND FIGURE 11-19 (D)].
 HANDRAIL EXTENSIONS SHALL COMPLY WITH SECTION 11-4.4 .
  
 (3)THE CLEAR SPACE BETWEEN HANDRAILS AND WALL
 SHALL BE 1? INCHES (38 MM).
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status F Date 2007-01-25 Cont ID  
Sent By jwitmer Date 2007-01-25 Time 08:52 Rev Time 1.11
Received By jwitmer Date 2007-01-25 Time 08:52 Sent To PC
Notes
2007-01-25 09:02:30BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)723-2443
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SHOP DRAWINGREVIEW
 ACTION: DENIED
  
 ORNAMENTAL GLASS GUARD/ HANDRAIL SHOP DRAWING
  
 11-4.9.4
 11-4.9.4 HANDRAILS.
 STAIRWAYS SHALL HAVE HANDRAILS AT BOTH SIDES OF ALL
 STAIRS. HANDRAILS SHALL COMPLY WITH SECTION 11-4.26 AND
 SHALL HAVE THE FOLLOWING FEATURES:
  
 (2)IF HANDRAILS ARE NOT CONTINUOUS, THEY SHALL
 EXTEND AT LEAST 12 INCHES (305 MM) BEYOND THE TOP RISER
 AND AT LEAST 12 INCHES (305 MM) PLUS THE WIDTH OF ONE
 TREAD BEYOND THE BOTTOM RISER. AT THE TOP, THE
 EXTENSION SHALL BE PARALLEL WITH THE FLOOR OR GROUND
 SURFACE. AT THE BOTTOM, THE HANDRAIL SHALL CONTINUE TO
 SLOPE FOR A DISTANCE OF THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE EXTENSION SHALL BE
 HORIZONTAL [SEE FIGURE 11-19 (C) AND FIGURE 11-19 (D)].
 HANDRAIL EXTENSIONS SHALL COMPLY WITH SECTION 11-4.4 .
  
 (3)THE CLEAR SPACE BETWEEN HANDRAILS AND WALL
 SHALL BE 1? INCHES (38 MM).
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status P Date 2007-01-25 Cont ID  
Sent By jwitmer Date 2007-01-25 Time 08:51 Rev Time 0.55
Received By jwitmer Date 2007-01-25 Time 08:51 Sent To PC
Notes
2007-01-25 08:52:21SUBMITTAL FOR ROOF CRICKET SHOP DRAWINGS- OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2006-10-26 Cont ID  
Sent By jwitmer Date 2006-10-26 Time 07:36 Rev Time 0.55
Received By jwitmer Date 2006-10-26 Time 07:35 Sent To  
Notes
2006-10-26 07:37:16REVISION:ADDED RATED PARTITIONS TO ELECTRICAL &
 MECHANICAL ROOMS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status P Date 2006-10-02 Cont ID  
Sent By jwitmer Date 2006-10-02 Time 10:27 Rev Time 0.55
Received By jwitmer Date 2006-10-02 Time 10:27 Sent To PC
Notes
2006-10-02 00:00:00REV: PARTITION CHANGES IN ELECTRIC
 ROOMS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status F Date 2006-10-02 Cont ID  
Sent By jwitmer Date 2006-10-02 Time 09:47 Rev Time 0.55
Received By jwitmer Date 2006-10-02 Time 09:44 Sent To PC
Notes
2006-10-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL
 CONT: THE WEITZ CO.
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION : ROOF CRICKETS
 ACTION: DENIED
 ENGINEERS SEAL:
 FLORIDA ADMINISTRATIVE CODE
 61G15-23.001
 RULE 61G15-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARANCE
 OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 PURSUANT TO SECTION 471.025 F. S. , THE
 BOARD HEREBY ESTABLISHES AS INDICATED
 BELOW THE FORMS OF EMBOSSING IMPRESSION
 SEALS WHICH ARE ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8"
 IN DIAMETER. ALL ENGINEERS MUST BE
 UTILIZING SEALS AS ILLUSTRATED IN THIS
 RUKE NO LATER THAN JANUARY 1, 2006.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2006-10-02 Cont ID  
Sent By jwitmer Date 2006-10-02 Time 09:39 Rev Time 0.55
Received By jwitmer Date 2006-10-02 Time 09:39 Sent To PC
Notes
2006-10-02 00:00:00ADDITIONAL ROOFING DETAILS:
 REFRENCE NOA# 03-0915.06
  
 REVISED A6.06 THIRD FLOOR REFLECTED
 CEILING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2006-10-02 Cont ID  
Sent By jwitmer Date 2006-10-02 Time 09:17 Rev Time 0.55
Received By jwitmer Date 2006-10-02 Time 09:17 Sent To PC
Notes
2006-10-02 00:00:0010-02-06
 REV: RM 3A16 NON-RATED CEILING REV.OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2006-08-31 Cont ID  
Sent By jwitmer Date 2006-08-31 Time 13:44 Rev Time 2.22
Received By jwitmer Date 2006-08-31 Time 13:44 Sent To PC
Notes
2006-08-31 00:00:00SUBMITTALS:
 ORNAMENTAL GLASS RAILS
 ENGINEERED FRAMING FOR ROOF CRICKET @
 NORTH ENTRY & SOFFIT FRAMING FOR ENTRY
 REVISED ARCHED FRAMING FOR WINDOW TYPE
 "U" & REVISED SOFFIT FRAMING
 SHOP DRAWINGS & CALCULATIONS FOR
 S-1 & S-2.
 FIRE CAULKING SUBMITTALS
 ADD DUCT ENCLOSURE FOR ER-6A : A1.04,
 A1.06& A1.08

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status F Date 2006-08-31 Cont ID  
Sent By jwitmer Date 2006-08-31 Time 13:42 Rev Time 0.33
Received By jwitmer Date 2006-08-31 Time 13:42 Sent To PC
Notes
2006-08-31 00:00:00ENGINEERED FRAMING FOR E & Y WINDOWS,
 SUBMITTED THE SAME SHEETS THAT HAVE
 "VOID" STAMP ON THEM.
 SUBMIT NEW SHEETS WITH THE CORRECT SEAL
 STATING "LICENSE"

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2006-07-10 Cont ID  
Sent By jwitmer Date 2006-07-10 Time 12:00 Rev Time 4.00
Received By jwitmer Date 2006-07-10 Time 12:00 Sent To PC
Notes
2006-07-10 00:00:00WINDOW/ DOOR REVISIONS/ SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2006-07-03 Cont ID  
Sent By jwitmer Date 2006-07-03 Time 16:01 Rev Time 0.55
Received By jwitmer Date 2006-07-03 Time 16:01 Sent To PC
Notes
2006-07-03 00:00:00SHOP DRAWINGS ATRIUM STAIRS

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status F Date 2006-07-03 Cont ID  
Sent By jwitmer Date 2006-07-03 Time 15:37 Rev Time 0.55
Received By jwitmer Date 2006-07-03 Time 15:36 Sent To PC
Notes
2006-07-03 00:00:00PERMIT: 04111073
 ADD: 300 PEMBROKE PL
 CONT: THE WEITZ CO
 TEL: (561)723-2443
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: LTERNATE WINDOW CONNECTION E & Y
 ACTION: DENIED
  
  
 1) RULE 61G155-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARENCE
 OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status F Date 2006-06-15 Cont ID  
Sent By jwitmer Date 2006-06-15 Time 10:33 Rev Time 0.77
Received By jwitmer Date 2006-06-15 Time 10:33 Sent To PC
Notes
2006-06-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL
 CONT: THE WEITZ CO
 TEL: (561)723-2443
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW LIGHT GAUGE WINDOW FRAMING
 ACTION: DENIED
  
  
 1) RULE 61G155-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARENCE
 OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 2) I SPOKE WITH MR. GINSBURG TO SEE IF
 THE 3"X3"X1/4" ANGLE HAD BEEN ELIMENATED
 AT EACH TRUSS. MR. GINSBURG INDICATED
 THIS DETAILOR SK-3 IS INFILL BETWEEN THE
 3" ANGLES. PLEASE PROVIDE A NOTE STATING
  
 THE 3"X3"X1/4" STEEL ANGLE TO BE
 INSTALLED AT EVERY TRUSS, DETAIL TO
 CLARIFY INFILL LIGHT GAUGE STEEL
 FRAMING.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2006-05-05 Cont ID  
Sent By jwitmer Date 2006-05-05 Time 11:27 Rev Time 0.88
Received By jwitmer Date 2006-05-05 Time 11:27 Sent To PC
Notes
2006-05-05 00:00:00SHORING COMPLIANCE LETTERS & SHORING
 SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2006-05-05 Cont ID  
Sent By jwitmer Date 2006-05-05 Time 10:37 Rev Time 2.22
Received By jwitmer Date 2006-05-05 Time 10:37 Sent To PC
Notes
2006-05-05 00:00:00REVISION BULLITEN# 4
 LEVEL 3FLOOR POUR SHOR& RESHORE
 DOCUMENTS AND SHORING LAYOUT SHEETS 4-7

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status F Date 2006-05-05 Cont ID  
Sent By jwitmer Date 2006-05-05 Time 07:36 Rev Time 1.55
Received By jwitmer Date 2006-05-05 Time 07:35 Sent To PC
Notes
2006-05-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561723-2443
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 WALL ANCHOR CALCULATIONS REVIEW
 ACTION:DENIED
  
 1) STANLEY M HAW P.E. RAISED SEAL TO
 READ "LICENSE" SEE ATTACHMENT RULE
 61G15-23.001 FL ADMINISTRATIVE CODE.
  
 2)MISSING, DBPR NOT REGISTERED:
 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 3) SPECIFICATIONS/ SHOP DRAWINGS
 INDICATE THE USE OF POWERS LOC BOLT 1/2"
 DIAMETER AND A 1 1/2" EMBEDMENT INTO
 HOLLOW CMU. POWERS LOC BOLT IS A
 EXPANSION TYPE ANCHOR, IF EMBEDMENT IS
 TO BE 1 1/2 INCHES THE BACK OF THE BLOCK
 WILL BE BLOWN OUT SINCE BLOCK SHELL FACE
 IS 1 1/4", HAAS THIS BEEN CONSIDERED, IS
 THERE TO BE A REDUCTION?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status F Date 2006-05-04 Cont ID  
Sent By jwitmer Date 2006-05-04 Time 13:32 Rev Time 2.22
Received By jwitmer Date 2006-05-04 Time 13:32 Sent To PC
Notes
2006-05-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO.
 TEL: (561)723-2443
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW:
 ACTION: DENIED
 ROOF SHEATHING ASSEMBLIES
 1) THERE ARE 2 SEPERATE PACKAGES (3)SETS
 IN EACH DATED APRIL 26/2006 AND MARCH
 10/2006.
  
 2) MARCH 10TH PACKAGE, DOESN'T PROVIDE
 CALCULATIONS FOR THE FASTENING OF THE
 DENSEDECK AND INSULATION TO THE METAL
 DECK.
  
 3) THE RATIONAL ANALYSIS PROVIDED BY
 SLIDER ENGINEERING IS A COPY NOT AN
 ORIGINAL, NOT A ORIGINAL SIGNATURE
 ,RAISED SEAL OR DATE.
 FL ADMINISTRATIVE CODE, 61G15-23.002(1)
  
 4) MIKE GINSBURG P.E. SIGNED& SEALED A
 COVER PAGE NOT INDEXING WHAT WAS
 INCLUSIVE OF THE DOCUMENT, INDEX PAGE IS
 THE NEXT SHEET. THERE ARE 5 SECTIONS
 NONE INDICATE HOW MANY PAGES ARE IN EACH
 SECTION.
  
 5) INDEX PAGE INDICATES CALCULATION,
 WHERE, ONLY RATIONAL ANYLSIS PROVIDED.
  
 6) HANSON HAS DETAIL SHEETS NOT SIGNED
 OR SEALED.
  
  
 APRIL 26/06 PACKAGE
 7)COVER LETTER ALSO INDICATES
 CALCULATIONS TO BE IN THE PACKAGE BUT
 NONE WERE FOUND.
  
 8) THE OLYMPIC ROOF FASTENER SUBMITTED
 INDICATES A 137.5 STATIC WITHDRAWL
 RESISTANCE WHEN ENBEDDED INTO 1/2"
 PLYWOOD. ALL THE PLYWOOD WAS TO BE
 REMOVED FROM THE DRAWINGS AND DENSEGLASS
 WAS TO BE USED TO BRING THE BUILDING
 BACK INTO COMPLIANCE.THE NEWEST
 ARCHITECTURAL SHEET( DELTA 4)A4.02
 DETAILS 3& 4 STILL INDICATE 1/2"
 EXTERIOR FR SHEATHING TO BE USED, PLEASE
 CORRECT.
 THE VALUE FOR PENETRATING THE 22 GAUGE
 STEEL DECK IS 151.5.
  
 9) THE GAF RUBEROID MODIFIED BITUMEN
 ROOFING REPORT SUBMITTED HAS THE SBS
 SYSTEM HIGHLIGHTED ,WHICH ONLY HAS A
 MAXIMUM DESIGN OF -60. LIMITATION #7
 DOES ALLOW FOR ENHANCE FASTENING WITH
 THE RAS 117 STANDARD. THE STANDARD WAS
 SUBMITTED BUT THE DESIGN PROFESSIONAL
 HASN'T PROVIDED THE CALCULATIONS FOR
 FASTENING IN THE VARIOUS ZONES. THE
 FASTENER EXTRAPOLATION SHEET FOR THE
 BASE SHEET WAS SUBMITTED BUT NOT THE
 CALCS.
 BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION:
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2006-04-20 Cont ID  
Sent By jwitmer Date 2006-04-20 Time 07:10 Rev Time 1.10
Received By jwitmer Date 2006-04-20 Time 07:10 Sent To  
Notes
2006-04-20 00:00:00SUBMITTAL DATED 3-03-06 ANCHOR
 CALCULATIONS FOR PRECAST CONCRETE WINDOW
 SILLS AND HEADER
  
 DATED 4-05-06 STEEL MULLION DETAILS

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2006-04-04 Cont ID  
Sent By jwitmer Date 2006-04-04 Time 10:31 Rev Time 1.11
Received By jwitmer Date 2006-04-04 Time 10:31 Sent To PC
Notes
2006-04-04 00:00:004-04-06 EXTERIOR METAL STUD FRAMING
 PROVISO: AS NOTED ON WIND LOADS FOR
 COMPONENTS AND CLADDING, VERIFY FRAMING
 IS ADEQUATE FOR LOADS SHOWN IN
 STRUCTURAL DWGS.
 JIM WITMER
 BUILDING PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2006-04-04 Cont ID  
Sent By jwitmer Date 2006-04-04 Time 10:18 Rev Time 0.55
Received By jwitmer Date 2006-04-04 Time 10:18 Sent To PC
Notes
2006-04-04 00:00:00REVISION 3-30-06 S1.10 ADD BEAM

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2006-04-04 Cont ID  
Sent By jwitmer Date 2006-04-04 Time 09:34 Rev Time 2.00
Received By jwitmer Date 2006-04-04 Time 09:34 Sent To PC
Notes
2006-04-04 00:00:00SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2006-04-04 Cont ID  
Sent By jwitmer Date 2006-04-04 Time 09:15 Rev Time 4.44
Received By jwitmer Date 2006-04-04 Time 09:15 Sent To PC
Notes
2006-04-04 00:00:00REVISIONS:
 A0.03 # 3
 A1.02 #5
 A1.04 #4
 A1.06 #3
 A1.08 #3
 A2.02 #4
 A3.03 #6
 A7.06 #3

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2005-12-22 Cont ID  
Sent By shill Date 2005-12-22 Time 19:04 Rev Time 0.50
Received By shill Date 2005-12-22 Time 19:04 Sent To  
Notes
2005-12-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)TITLE BLOCK IN CONFORMANCE WITH
 FAC61G15-23.002 REQUIRED FOR THE
 ENGINEER.
  
 2.)ALL SUBMITTALS ARE TO BE REVIEWED
 BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL.
  
 3.)THREE SETS OF ALL DOCUMENTS
 REQUIRED FOR THRESHOLD BUILDINGS.ONLY
 TWO WERE SUBMITTED.ALL THREE ARE TO BE
 SIGNED, SEALED AND DATED ORIGINALS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2005-12-16 Cont ID  
Sent By jwitmer Date 2005-12-16 Time 13:04 Rev Time 0.33
Received By jwitmer Date 2005-12-16 Time 13:04 Sent To PC
Notes
2005-12-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)723-2443
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THESE ARE NOT THE ORIGINAL DOCUMENTS
 BUT COPIES OF THE APPROVALS.
  
 2) THE ORIGINAL DOCUMENTS WITH NO STAMP
 REVIEWED BY ENGINEER ARE SHEETS
 4,4A,5,6& 7. THE COPIES ARE 5,8&
 13.SHEETS DO NOT MATCH.
  
 THE ENGINEER OF RECORD TO STAMP ALL 3
 SETS WITH THE THEIR STAMP AND THE
 CONTRACTOR TO SUBMIT ORIGINALS IF THEY
 REQUIRE ORIGINALS THEN 4 SETS WILL BE
 REQUIRED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2005-12-16 Cont ID  
Sent By jwitmer Date 2005-12-16 Time 12:53 Rev Time 0.55
Received By jwitmer Date 2005-12-16 Time 12:53 Sent To PC
Notes
2005-12-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)723-2443
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SUBMITTAL FOR LOCAL PRODUCT APPROVAL,
 THE MANUFACTURER IS TO FILL OUT FORMS
 FOR LOCAL PRODUCT APPROVAL.
  
 2) PROVIDE INFORMATION AS TO WHERE THESE
 PRODUCTS WILL BE INSTALLED IN THE
 STRUCTURE, SIZES AND PRESSURES.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2005-12-16 Cont ID  
Sent By jwitmer Date 2005-12-16 Time 12:43 Rev Time 0.33
Received By jwitmer Date 2005-12-16 Time 12:42 Sent To PC
Notes
2005-12-16 00:00:00BUILDING PLAN REVIEW
 PERMIT 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)723-2443
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW : LETTER
  
 ACTION: DENIED
  
 THE LETTER SUBMITTED FORTHE 3RD LEVEL
 PRESTRESSED MEMBERS HASA NOT BEEN
 APPROVED BY THE ENGINEER OF RECORD.
 THE ENGINEER OF RECORD IS TO REVIEW SAID
 SHOP DRAWINGS AND STAMP EITHER APPROVED
 , APPROVED WITH RED LINED DRAWING OR
 DENIED.TO DATE NO DRAWINGS INDICATE
 REVIEWED BY THE ENGINEER OF RECORD FOR
 THE THIRD LEVEL. THEY HAVE BEEN
 SUBMITTED TWICE AND DENIED TWICE .
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2005-12-16 Cont ID  
Sent By jwitmer Date 2005-12-16 Time 12:37 Rev Time 0.33
Received By jwitmer Date 2005-12-16 Time 12:37 Sent To PC
Notes
2005-12-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)723-2443
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 SUBMITTALS SHORING DRAWINGS ARE TO BE
 REVIEWED BY THE ENGINEER OF RECORD,
 MIKE GINSBERG AND APPROVED , APPROVED AS
 NOTED OR DENIED BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2005-12-07 Cont ID  
Sent By jwitmer Date 2005-12-07 Time 15:13 Rev Time 0.55
Received By jwitmer Date 2005-12-07 Time 15:13 Sent To PC
Notes
2005-12-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)723-2443
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 SUBMITTALS SHORING DRAWINGS ARE TO BE
 REVIEWED BY THE ENGINEER OF RECORD,
 MIKE GINSBERG AND APPROVED , APPROVED AS
 NOTED OR DENIED BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-11-16 Cont ID  
Sent By jwitmer Date 2005-11-16 Time 14:07 Rev Time 1.66
Received By jwitmer Date 2005-11-16 Time 14:07 Sent To PC
Notes
2005-11-16 00:00:00REVISION BULLETIN # 2 9/30/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-10-14 Cont ID  
Sent By jwitmer Date 2005-10-14 Time 10:36 Rev Time 0.55
Received By jwitmer Date 2005-10-14 Time 10:36 Sent To PC
Notes
2005-10-14 00:00:0010-14-05 #7 SHORING DRAWINGS FOR THE 2ND
 FLOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-09-09 Cont ID  
Sent By jwitmer Date 2005-09-09 Time 13:08 Rev Time 6.55
Received By jwitmer Date 2005-09-09 Time 13:07 Sent To  
Notes
2005-09-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO.
 TEL: (561)723-2443
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 5TH SUBMITTALS
 ACTION:REVIEWED
  
 BUILDING PROVISO FOR A1.04/ A2.07 DETAIL
 # 6 FOR THE GLASS GARDRAIL.SEE SECTIONS
 ON COLUMN GRIDLINE 8, M&N, R&S. THIS
 SECTION OF RAILING IS APPROXIMATELY
 10'-0" LONG SHOW COMPLIANCE WITH SECTION
 2405.5.1.2.
  
 PROVIDE CALCULATIONS FOR 1608.2.1 AND
 1708.2.2 WITH THE REQUIRED SAFETY FACTOR
 OF 4 SEE 2405.1.1.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-09-08 Cont ID  
Sent By jwitmer Date 2005-09-08 Time 15:52 Rev Time 1.33
Received By jwitmer Date 2005-09-08 Time 15:52 Sent To PC
Notes
2005-09-08 00:00:00REVISIONS: A1.04 REV # 3, A2.09 REV# 3 &
 A3.03 REV 5
 S0.00 REV 3,4&5
 S1.04 REV# 2,3&4
 S3.02 REV# 2,3&4
 S3.03 REV# 2&3
 S4.02 REV# 2&3
 S4.05 REV# 2&3
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.77
Received By jwitmer Date 2005-08-20 Time 12:09 Sent To B
Notes
2005-08-20 00:00:008-20-05 SUBMITTALS:
 FLOOD ELEVATION CERTIFICATE
 ENERGY CALCS
 FIRE/ TIMED ANALYSIS PHASE II
 VARIANCE
 SUBMITTAL LETTERS
 BREAK OUT PLUMB & ELEC SUBMITTALS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-06-17 Cont ID  
Sent By jwitmer Date 2005-06-16 Time 09:07 Rev Time 3.33
Received By jwitmer Date 2005-06-16 Time 08:58 Sent To  
Notes
2005-06-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)310-2723
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: REVIEWED
 PLANS APPEAR TO BE CODE COMPLIANT FOR AN
 ENCLOSED BUILDING WITH THE EXCEPTIONS
 LISTED BELOW TO APPLY FOR A PERMIT
 BEFORE THE WINDOW BUCK INSPECTION
 SEE BUILDING PROVISOS 1/2.
  
  
 BUILDING PROVISOS:
  
 1)CURTAIN WALL, WINDOWS AND ROOFING TO
 BE PERMITTED SEPARATELY WITH ASSOCIATED
 FEES AND REVIEWS.
  
 2)1707.4.5.1 MULLIONS OCCURRING BETWEEN
 INDIVIDUAL WINDOW AND GLASS DOOR
 ASSEMBLIES. TESTING REPORTS ARE REQUIRED
 BY AN APPROVED TESTING LABORATORY OR BE
 ENGINEERED.
  
 3)" PARTIAL CERTIFICATE OF OCCUPANCY".
 THE PERMIT WILL BE ISSUED AS PHASE 1 AND
 PHASE 2, ONCE THE PARTIAL CERTIFICATE IS
 ISSUED TO KEEP THE PERMIT FROM EXSPIRING
 ON PHASE 2 AN INSPECTION WILL NEED TO BE
 PREFORMED WITHIN A (6) MONTH PERIOD TO
 KEEP THE LIFE OF THE PERMIT ALIVE, OR
 WRITE A LETTER REQUESTING A EXTENSION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-07 Cont ID  
Sent By jwitmer Date 2005-03-07 Time 14:50 Rev Time 8.50
Received By jwitmer Date 2005-03-07 Time 07:14 Sent To  
Notes
2005-03-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PL
 CONT:THE WEITZ CO
 TEL: (561)468-5511
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT #3A) FROM THE PREVIOUS REVIEW
 DEALS WITH THE " PARTIAL CERTIFICATE OF OCCUPANCY". THE
 PERMIT WILL BE ISSUED AS
  
 PHASE 1 AND PHASE 2, ONCE THE PARTIAL
 CERTIFICATE IS ISSUED TO KEEP THE PERMIT
 FROM EXSPIRING ON PHASE 2 AN INSPECTION
 WILL NEED TO BE PREFORMED WITHIN A (6)
 MONTH PERIOD TO KEEP THE LIFE OF THE
 PERMIT ALIVE, OR WRITE A LETTER
 REQUESTING A EXTENSION.
  
 3) COMMENT #3C) DEALS WITH SMOKE
 CONTROL, THE PHASE II OR RATUNDA IS
 CONSIDERED A ATRIUM ALSO AND REQUIRES
 SMOKE CONTROL AS REQUIRED IN 414.4.2,
 WHEN SUCH ATRIUMS ARE LESS THAN 600,000
 CU FT, SUCH SYSTEMS SHALL EXHAUST
 40,000CFM.
  
 4) COMMENT # 4 FROM THE PREVIOUS REVIEW,
 DEELS WITH A1.02 THE NORTH STAIRWELL
 DOOR 1S1, YOUR RESPONSE WAS TO REVISE
 THE DOOR TO INCLUDE A "C-3/4 HR LABEL",
 TABLE 705.1.2 FOR SHAFTS, 4 STORIES OR
 MORE, OPENING PROTECTIVES OF 1 1/2 HR.
  
 5) DEALS WITH COMMENTS 6& 7 FROM THE
 PREVIOUS REVIEW: BUTT GLAZING, AT ANY
 AND ALL LOCATIONS LOCATED ON THE
 EXTERIOR OF THE BUILDING.
  
 5A) IN THE RESPONSE THERE IS A STATEMENT
  
 THAT STATES " SPECIFICATION 08450
 REQUIRES COMPLIANCE WITH FBC AND NOTE
 REQUIRING COMPLIANCE WITH FBC 2406.2 WAS
 ADDED TO SHEET A2.02.
 104.2.1*W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 5B) THERE ARE (2) ISSUES TO DEAL WITH
 WHEN USING BUTT GLAZING, THE FIRST IS
 THE SITE SPECIFIC ENGINEERING (SIGNED
 AND SEALED, (3) COPIES) THAT IS REQUIRED
 FOR WIND (2406.2 /1606.1.2 , THE SECOND
 WILL BE 1606.1.4 REQUIRING TESTING FOR
 LARGE MISSLE IMPACT. TO DATE WE HAVE
 SEEN NO BUTT GLAZING REPORTS APPROVED
 WITH LARGE MISSLE IMPACT TESTING, THUS
 REQUIRING SHUTTERS.
  
 5C) THERE WAS NO RESPONSE TO COMMENT #29
 FROM THE CONTRACTOR FOR BUTT GLAZING NOR
  
 ANY INFORMATION SUBMITTED FOR STORM
 SHUTTERS. A COPY OF THE CITIES
 IMPLEMENTATION STANDARD FOR HURRICANE
 MISSLE IMPACT PROTECTION HAS BEEN
 INCLUDED, READ THROUGH AND TAKE NOTE TO
 ITEM 13 DEALING WITH LARGE PROJECTS.
 PROVIDE A PRESTORM PEPAREDNESS PLAN SO
 THE BUILDING OFFICIAL MAY REVIEW, ALSO
 PROVIDE THE STORM SHUTTER INFORMATION:
  
 5C(1)PROVIDE STORM PANEL PRODUCT
 APPROVAL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL
 NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 5C(2)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 6) COMMENT # 20 FROM THE PREVIOUS REVIEW
 DEALS WITH THE FRAMING OF THEBARREL
 VAULT. PLEASE SUPPLY THE MANUFACTURERS
 SPEC SHEETS FOR THE FRAMING MEMBERS AND
 HOW THE ACOUSTIC BOARD (1" FIBERGLASS
 BOARD) IS TO BE FASTENED.
  
 7A) COMMENT # 21 FROM THE PREVIOUS
 REVIEW
 DEEL WITH A MISSING PAGE AND DETAILS,
 DETAIL # 4, PROVIDE A 2HR. RATED
 HORIZONTAL SHAFT WALL ASSEMBLY
  
 7B) STOREFRONT BUTT GLAZING, SEE COMMENT
  
 # 5 ABOVE.
  
 8)COMMENT # 29 FROM THE PREVIOUS REVIEW,
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR WINDOWS/ SKYLIGHTS
 B) EXTERIOR GLAZED DOORS
 C) EXTERIOR SOLID DOORS
 D) MULLIONS
 E) LOUVERS
 F) STORM SHUTTERS
 G) SOFFITS
 H)COMPONENTS & CLADDING
 1) TRUSS ANCHORS
 2) EXTERIOR RAILINGS
 I)ROOFING PRODUCT AND ASSEMBLIES
 ****NOTE**** THIS BUILDING (TYPEII BLDG
 1 HR SUPPORTING ROOF ONLY) IS IN A FIRE
 DISTRICT REQUIRING: FBC* F102.2.4ROOF
 COVERINGS, ON BUILDINGS LOCATED IN THE
 FIRE DISTRICT, SHALL CONFORM TO THE
 REQUIREMENTS OF CLASS A OR B ROOF
 COVERINGS, AS DEFINED IN FBC 1505.
  
 9) THE PRODUCT SUBMITTAL INFORMATION
 SUBMITTED FOR ALUMINIUM CURTAIN WALL
 SYSTEM, MANUFACTURER TRAINOR GLASS CO.
 IS TESTINGSUBMITTED TO MIAMI-DADE FOR
 A ONE TIME USE (SITE SPECIFIC) AT
 AVENTURA HOSPITAL, AVENTURA, FL.
 THE SAME INFORMATION WAS SUBMITTED TO
 THE STATE, IT APPEARS THAT THE STATUS IS
  
 APPLIED FOR. A SECOND REPORT WAS DENIED.
 AS STATED IN THE BUTT GLAZING INSTENCE,
 THE PRODUCT HAS TO BE TESTED FOR THE
 LARGE MISSLE IMPACT TESTING. IF THE
 MANUFACTURER WOULD LIKE TO APPLY FOR A
 LOCAL PRODCUT APPROVAL OR SITE SPECIFIC
 APPROVAL WE WILL NEED SIGNED AND SEALED
 TESTING REPORTS, FOR WIND AND LARGE
 MISSLE IMPACT TESTING, AGREEMENTS WITH
 THE THIRD PARTYPRODUCT QUALITY
 ASSURANCE ENTITY REQUIRED BY RULE 9B-72.
 SEE ATTACHMENT FOR LOCAL OR SITE
 SPECIFIC APPROVAL.
  
 10) COMMENTS 31 & 32 DEAL WITH THE
 REQUIREMENTS FOR MULLIONS, UNTIL PRODUCT
 APPROVALS ARE SUBMITTED THESE SAME
 COMMENTS SHALL APPEAR,
  
 10A) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10B) 1707.4.5.2 MULLIONS SHALL BE
 DESIGN- ED TO TRANSFER THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW OR
 DOOR ASSEMBLIES TO THE ROUGH OPENING
 SUBTRATE.
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-22 Cont ID  
Sent By jwitmer Date 2004-12-22 Time 07:21 Rev Time 20.00
Received By jwitmer Date 2004-12-22 Time 07:20 Sent To  
Notes
2004-12-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04111073
 ADD: 300 PEMBROKE PLACE
 CONT: THE WEITZ CO
 TEL: (561)310-2723
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 NOTES: SINCE THIS PROJECT IS A
 THRESHOLD
  
 BUILDING (3) COPIES OF ALL PLANS,
 PRODUCT APPROVALS & SUBMITTALS WILL BE
 REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY
 WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PHASING I/ II. THERE ARE VARIOUS ISSUES
 THAT WILL NEED TO BE ADDRESSED BEFORE
 PHASING WILL BE APPROVED VS. APPROVAL
 FOR A SEPERATE PERMIT FOR A REMODELING
 AND ADDITION PREMIT FOR THE WORK TO BE
 ACCOMPLISHED UNDER PHASE II.
 3A) I DO NOT BELIEVE AFTER THE WORK
 COMPLETED UNDER PHASE I AND A TCO(
 PARTIAL AND OR CONDITIONAL CERTIFICATE
 OF OCCUPANCY)IS ISSUED, THE WORK ON THE
 SECOND PHASE CAN BE COMPLETED WITHIN
 THE
 30 DAYS ALOTTED FOR
 A TCO. TWO 30 DAYS EXTENTIONS MAY BE
 GRANTED ALLOWING A 90 DAY WINDOW TO
 COMPLETE THE 2ND PHASE.
 TWO SEPERATE PERMITS MAY BE THE
 SOLUTION, ONE FOR THE NEW WORK WITH THE
 TWO HR WALL INCLUDED A SECOND FOR THE
 REMODEL OF THE EXISTING BUILDING AND
 ADDITION TO THE EXISTING LIBRARY.
 3B) THE SECOND CONCERN IS WHEN WORK IN
 PHASE I HAS COMMENCED WILL THE EXISTING
 LIBRARY STILL BE USED? IF SO INDICATE
 EGRESS TO AND FROM BUILDING VS WORK AND
 STORAGE AREAS OF PHASE I.
 3C) THE THIRD MAJOR CONCERN WILL BE
 HOW THE SMOKE CONTROL FOR THE ATRIUM
 WILL WORK. PHASE INDICATES THE USE OF
 SMOKE CONTROL, BUTWHEN PHASE II IS
 COMPLETE AND THE TEMPORARY WALL IS DOWN
 THE PHAASE 1 & PHASE II WILL MAKE ONE
 LARGE ATTRIUM WITH NO SMOKE CONTROL
 INDICATED FOR THE OCTOGON PORTION OF
 THE
  
 ATRIUM.
 3D) THE FOURTH CONCERN WOULD BE THAT
 PHASE I BE COMPLETED AND THE COLLEGE
 DECIDE NOT TO DO PHASE II THUS
 REQUIRING
 NOT A 2 HR WALL BUT A 4HR WITH PROBLEMS
  
 DEALING WITH EGRESS. THERE IS NO
 INSURANCE PHASE II WILL HAPPEN.
 POSSIBLY
 POST A BOND FOR PHASE II AGAIN UNDER A
 SEPERATE PERMIT.
  
 4)SHEET A1.02, THE NORTH STAIRWELL DOOR
 1S1,THERE IS NO FIRE RATING.
  
 5) SHEET S-1 NOT SHOWN ON DOOR
 SCHEDULE.
  
 6) SHEET A7.01 DETAILS 1-4 NORTH
 STAIRWELL TOWER: WINDOWS (L&M) REQUIRE
 RATING 1006.1.3.2.
  
 7)SHEET A 2.03 BUTT GLAZING:
 PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 2001 FBC 2406.2.
  
 8) 11-4.4.2 HEAD ROOM. WALKS, HALLS,
 CORRIDORS, PASSAGEWAYS, AILES OR OTHER
 CIRCULATION SPACES SHALL HAVE 80 INCHES
 MINIMUM CLEAR HEAD ROOM (SEE FIGURE
 8(A)). IF VERTICAL CLEARENCE OF AN AREA
 ADJOINING AN ACCESSIBLE ROUTE IS
 REDUCED
 TO LESS THAN 80 IN. (NOMINAL
 DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY IMPARED PERSONS SHALL BE
 PROVIDED. (SEE FIGURE 8(C-1)). SEE
 STAIRWELL# 1 FIRST FLOOR.
  
 9) PLEASE INDICATE THE EXITING FOR
 STAIRWELL# 2, ELEVATOR# 2 AND THE GRAND
 STAIRWAY LEADING TO THE OCTOGON PORTION
 (PHASE II) OF THE BUILDING.
  
 10) A2.00 MISSING WALL CONNECTIONS FOR
 FLOOR TO FLOOR/ ALSO BLOCK CONNECTION
 "SEE STR"? NOT INDICATED WHERE.
  
 11) A7.04 STAIR S-A MISSING THE
 HORIZONTAL HANDRAIL EXTENSION.SEE
 11-4.9.4 HANDRAILS, FIGURE 19(C&D).
  
 12) 1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
  
 13) 2405.5.1.1 RAILINGS, THE PANELS AND
 THEIR SUPPORT SYSTEM SHALL BE DESIGNED
 TO WITHSTAND THE LOADS SPECIIED IN
 1608.2.1 AND 1608.2.2. ASAFETY FACTOR
 OF
 4 SHALL BE USED. PROVIDE CALCULATIONS
  
 14) A1.02/ A7.03 DETAIL O 1007.5.9
 HANDRAILS FOR MONUMENTAL STAIRS,
 HANDRAILS SHALL BE LOCATED ALONG THE
 MOST DIRECT PATH OF EGRESS TRAVEL.
  
 15) S0.02 OCTOGON, BASEMENT , ARE ALL
 OF
 THE COLUMNS REMOVED OR ONLY (2).
  
 16) S0.03 OCTOGON- LEVEL 1 DEMO PLAN
 INDICATES EXISTING HORIZONTAL STEEL
 BEAMS TO REMAIN, BUT HOW DO YOU SPAN
 THE
 GRID AREA WHERE THE STEEL COLUMNS WERE
 REMOVED? HOW DOES THE HORIZONTAL STEEL
 BRIDGE THIS SIMPLE SPAN CONFIGURATION?
  
 17A) S1.09 A) THE AREA BEHIND THE
 OCTOGON STRUCTURE, THERE IS NO FRAMING
 INFORMATION.
 17B) FINISH NOTE: HSS_ _ X_ _X_ _ @
 4'-0" C/C MAX?
  
 18) PLANS TO INDICATE READING, STUDY
 AREAS, CARD CATALOG, MAGAZINE DISPLAY
 AND A MINIMUM OF 42" BETWEEN STACKS-
 FBC 11-8 (1-5).
  
 19) A1.04 ROOM 204, 2" GATE MISSING THE
 18" ON THE LATCH SIDE OF GATE SEE:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING
 CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 20) A1.08 LEVEL 4 NOTE A4.03 DETAIL 8,
 THE PLAN DOES NOT PROVIDE FRAMING
 INFORMATION HOW TO BUILD ARCH? ALSO
 PROVIDE FINISH MATERIAL INFORMATION FOR
 ACOUSTIC BOARD
  
 21) A4.04 DETAILS MISSING PAGE AND
 DETAIL NUMBER.
  
 22) 1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF
 SURFACE.
  
 23) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 24) 1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 25) S0.00 LIVE LOADS J(5) WIND SPEED
 145 CORRECT,FIGURE 1606 WIND-BORNE
 DEBRIS REGION; INDICATES THAT W.P.B.
 CITY OF IS LOCATED IN THE 140 MPH ZONE.
 PLANS ARE TO INDICATE THIS.
  
 26) CORRECT EXPOSURE TO "B"
  
 27) IMPORTANCE FACTOR WHEN OCCUPANT LOAD
 IS OVER 300 INA SINGLE ROOM THE
 IMPORTANCE FACTOR BECOMES 1.15.
  
 28) INDICATE ON ELEVATIONS THE INTERIOR
 ZONES AND END ZONES WITH RESPECTIVE
 POSITIVE AND NEGATIVE PRESSURES.
  
  
 29)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR WINDOWS
 B) EXTERIOR GLAZED DOORS
 C)EXTERIOR SOLID OR LOUVERED DOORS
 D) MULLIONS
 E) LOUVERS
 F)STORM SHUTTERS
 G) SOFFITS
 H) COMPONENTS & CLADDING
 1) TRUSS ANCHORS
 2)RAILINGS
 I) ROOFING PRODUCTS AND ASSEMBLIES
  
 30) 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 31) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 32)1707.4.5.2 MULLIONS SHALL BE
 DESIGN- ED TO TRANSFER THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW OR
 DOOR ASSEMBLIES TO THE ROUGH OPENING
 SUBTRATE.
  
 33) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A2.05 DETAIL# 30 INDICATES THE USE
 OF NAILABLE INSULATION, PROVIDE THE
 PRODUCT APPROVAL AND WHAT THE POSITIVE
 AND NEGATIVEPRESSURESBEFORETILE
 WITHDRAW.
  
 34) ENGINEER TO PROVIDE ATTACHMENT OF
 ROOF SHEATHING FOR VARIOUS ROOF PRESSURE
 ZONES, ZONE 1, 2 &3. IF THE SUBMITTED
 PRODUCT APPROVALS HAVE A LIMITATION FOR
  
 ENHANCED NAILING ZONES THIS INFORMATION
 TO ALSO BE SUBMITTED.
  
 35) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 THE ANSWERS TO THIS REVIEW MAY RESULT IN
  
 ADDTIONAL QUESTIONS NOT ADDRESSED UNDER
 THIS PLAN REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 56 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 55 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 54 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 53 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 52 Status P Date 2009-06-11 Cont ID  
Sent By dpalmer Date 2009-06-11 Time 12:52 Rev Time 0.00
Received By dpalmer Date 2009-06-11 Time 12:52 Sent To PC
Notes
2009-06-11 12:53:172.01,2.03,2.05,3.013.03,3.05,5.02.5.05

Review Stop E ELECTRICAL
Rev No 51 Status P Date 2009-06-11 Cont ID  
Sent By dpalmer Date 2009-06-11 Time 12:49 Rev Time 0.00
Received By dpalmer Date 2009-06-11 Time 12:49 Sent To PC
Notes
2009-06-11 12:50:05E1.01

Review Stop E ELECTRICAL
Rev No 50 Status P Date 2009-06-02 Cont ID  
Sent By dpalmer Date 2009-06-02 Time 14:41 Rev Time 0.00
Received By dpalmer Date 2009-06-02 Time 14:41 Sent To FIRE
Notes
2009-06-02 14:43:20REV, 1.01,2.01,2.05,3.05,5.04

Review Stop E ELECTRICAL
Rev No 49 Status P Date 2009-05-26 Cont ID  
Sent By dpalmer Date 2009-05-26 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2009-05-26 Time 15:43 Sent To PC
Notes
2009-05-26 15:45:26REV 201,203,503

Review Stop E ELECTRICAL
Rev No 48 Status F Date 2009-04-21 Cont ID  
Sent By dpalmer Date 2009-04-21 Time 10:17 Rev Time 0.00
Received By dpalmer Date 2009-04-21 Time 10:17 Sent To  
Notes
2009-04-21 10:17:35** DENIED REVISIONS**
  
  
  
 1) NOTE: ALL LOW VOLTAGE SYSTEMS NEED TO BE PERMITTED.
 ONLY SOME SYSTEM HAVE HAD PERMITS APPLIED. THERE ARE
 ALSO SOME PERMITS FROM PREVIOUS SYSTEMS WHICH WERE
 EXPIRED AND NEED TO BE RE-APPLIED.
 THESE PLANS MAY BE REFERENCED FOR A TURN AROUND
 PERMITS. HOWEVER VALUE FOR SCOPE OF WORK NEEDS TO BE
 VERIFIED ALONG WITH PERMIT VALUATION FEES.
 THE ACCESS CONTROL SYSTEM BEING PROPOSED NEEDS TO BE
 SUBMITTED UNDER SEPARATE PLANS AND PERMITS.
 FBC 105.1
  
 2) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE *DATA
 ROOM*. DOES THIS ROOM MEET 645.4 1-5?. IF NOT, PLEASE
 PLACE NOTE ON PLANS THAT *NOW WIRING METHODS IN NEC 645
 ARE PERMITTED IN THIS ROOM*.
 IT IS RECOMMENDED TO VERIFY WITH ANY IT/MIS PERSONNEL
 FROM PBAC THAT WIRING METHODS IN NEC 645 ARE NOT TO BE
 USED. IF MEETING 645.4 THEN WIRING METHODS OF 645 ARE
 PERMITTED. IF NOT MEETING ALL OF 645.4, 1-5, THEN ALL
 WIRING METHODS IN CHAPTERS 1-4 ARE MANDATORY.
  
  
 3) NOTE: PLEASE PROVIDE INFORMATION OF NEW SYSTEMS
 BEING INSTALLED FROM MANHOLE FOR LV DATA. IS THIS
 UTILITY ENTRANCE OR FROM A SYSTEM ON THE BASE BUILDING
 SITE. IF THIS IS FROM A UTILITY PLEASE SHOW HOW
 GROUNDING/BONDING OF SYSTEMS IS TAKING PLACE. 800.100,
 250
  
  
  
  
  
 NO FURTHER ELECTRICAL REVISIONS TO BE DONE UNTIL
 APPLICATIONS ARE MADE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 47 Status P Date 2009-04-07 Cont ID  
Sent By dpalmer Date 2009-04-07 Time 10:22 Rev Time 0.00
Received By dpalmer Date 2009-04-07 Time 10:22 Sent To  
Notes
2009-04-07 10:22:48REV FROM 3/10

Review Stop E ELECTRICAL
Rev No 46 Status P Date 2009-01-14 Cont ID  
Sent By dpalmer Date 2009-01-14 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2009-01-14 Time 16:37 Sent To  
Notes
2009-01-14 16:38:33E203,207,307,502,505

Review Stop E ELECTRICAL
Rev No 45 Status P Date 2008-12-31 Cont ID  
Sent By dpalmer Date 2008-12-31 Time 10:20 Rev Time 0.00
Received By dpalmer Date 2008-12-31 Time 10:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 44 Status P Date 2008-12-30 Cont ID  
Sent By dpalmer Date 2008-12-30 Time 10:16 Rev Time 0.00
Received By dpalmer Date 2008-12-30 Time 10:16 Sent To PC
Notes
2008-12-30 10:17:45THE ENGINERR CAME IN AND SIGNED, DATED AND SEALED THE
 SHEETS IN TEH SECOND SET FROM PREVIOUS FAILED
 REVISIONS.

Review Stop E ELECTRICAL
Rev No 43 Status F Date 2008-12-17 Cont ID  
Sent By dpalmer Date 2008-12-17 Time 13:54 Rev Time 0.00
Received By dpalmer Date 2008-12-17 Time 13:54 Sent To  
Notes
2008-12-17 13:55:08** TEMPORARY FAILED **
  
 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS HAVE BEEN
 PLACED WITH REVISIONS SUBMITTED 12/5 AS THESE WILL BE
 REQUIRED TO BE REVIEWED BY ALL TRADES.
  
 2) NOTE: THE FOLLOWING SHEETS IN 2ND SET ARE NOT
 SIGNED, DATED OR SEALED BY THE ELECTRICAL ENGINEER.
 ENGINEER WILL NEED TO COME INTO OFFICE TO DO THIS AS
 SOON AS POSSIBLE IN ORDER FOR REVIEW STATUS TO PASS AND
 PLANS RELEASED.
  
 E, 3.01,3.03,3.05,3.07,4.01,5.01,5.02,5.03,5.04,5.05.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 42 Status F Date 2008-06-27 Cont ID  
Sent By dpalmer Date 2008-06-27 Time 14:01 Rev Time 0.00
Received By dpalmer Date 2008-06-27 Time 14:01 Sent To  
Notes
2008-06-27 14:03:10** REVISIONS FOR SHEETS E5.03 AND 2.01 ARE OK HOWEVER
 REVIEW TO REMAIN IN FAILED STATUS UNTIL PREVIOUS REVIEW
 PLANS/COMMENTS ARE ADDRESSED.
  
 REV WHICH CAME IN 6/9 PLACED WITH REV WHICH CAME IN
 5/29

Review Stop E ELECTRICAL
Rev No 41 Status F Date 2008-04-25 Cont ID  
Sent By dpalmer Date 2008-04-25 Time 16:13 Rev Time 0.00
Received By dpalmer Date 2008-04-25 Time 16:13 Sent To  
Notes
2008-04-25 16:14:09** DENIED REVISIONS **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE REVIEW NOTE #4 FROM PREVIOUS REVIEW
 AS THIS REQUESTED AND MENTIONED THAT REVISED ENERGY
 CALCULATIONS WERE NEEDED.
 PLEASE ALSO SEE THE NOTES SPECIFICALLY GAVE CODE
 SECTIONS FROM THE 2001 FBC ALONG WITH MENTION THAT THE
 CALCULATIONS WOULD ALSO BE REQUIRED UNDER THE CODE IN
 EFFECT FOR SAID PROJECT.
 PLEASE SEE THE CALCULATIONS SUBMITTED ARE FROM THE 2006
 REVISIONS TO THE 2004 FBC. THE VERSION 2.5 WAS NOT IN
 THE 2001 FBC.
 PLEASE SEE THE INFORMATION PLACED INTO THE INPUT DATA
 REPORT IS NOT ACCURATE AND DOES NOT COORDINATE WITH THE
 SUBMITTED PLANS. THE FOLLOWING ARE SOME EXAMPLES ONLY
 AND IS NOT AN EXHAUSTED LIST. PLEASE ALSO SEE THAT THE
 INPUT DATA REPORT WILL BE NOTED AS IDR IN THE REMAINDER
 OF THIS REVIEW NOTE.
  
 FOR EXAMPLE:
 PLEASE SEE THE LIGHTING FIXTURE COUNT DOES NOT
 CORRELATE WITH PLANS. THE LIGHTING FIXTURES ARE SHOWN
 AS 1 (ONE) FIXTURE AT *X* AMOUNT OF WATTS WHICH IS NOT
 ACCURATE. PLEASE SEE THE AMOUNT OF FIXTURES, THE
 WATTAGE OF FIXTURES AND THE TYPES OF FIXTURES NEED TO
 COORDINATE WITH PLANS.
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH DOES NOT SHOW ANY EXTERIOR
 LIGHTING. HOW IS THIS POSSIBLE WHEN THERE ARE CLEARLY
 EXTERIOR LIGHTS SHOWN ON PLANS?
 ** AS NOTED ABOVE, THIS IS NOT AN EXHAUSTED LIST AND
 GIVES SOME EXAMPLES ONLY.
 13-400.2,400.3.A,13-415.2.AB.1, 13-415.1.A, TABLE
 415,.415.2 ETC
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 40 Status F Date 2007-10-07 Cont ID  
Sent By dpalmer Date 2007-10-07 Time 13:00 Rev Time 0.00
Received By dpalmer Date 2007-10-07 Time 13:00 Sent To  
Notes
2007-10-07 13:00:422007-10-07 13:00:42
  
 *** DENIED REVISION ***
  
 PHASE II/ ROTUNDA
  
 1) NOTE: PLEASE SEE THIS IS A THRESHOLD PROJECT AND
 THREE SETS OF PLANS ARE NEEDED.
 PLEASE SEE THAT THE ARCHITECTURAL AND OTHER TRADES WERE
 SPLIT UP HOWEVER THESE NEED TO BE SUBMITTED TOGETHER AS
 THE REVISIONS AS SUBMITTED CLEARLY AFFECT ALL TRADES
 FOR REVIEW.
  
 2) NOTE: PLEASE SEE THE ARCHITECT SEAL USED ON A SHEETS
 IS NO LONGER VALID FOR USE. PLEASE SEE FAC 61G1-16.002
 AS THE MINIMUM SIZE WAS CHANGED BY THE BOARD SEVERAL
 YEARS AGO.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY
 OTHER TRADE.
  
 3) NOTE: PLEASE SEE THAT COMPLIANCE WITH NFPA-101 7.8
 AND 7.9 NEEDS TO BE MET.
 PLEASE SEE THERE ARE AREAS IN WHICH BATTERY BACK UP
 TYPE OF LIGHTING FIXTURES ARE MISSING.
 PLEASE KNOW THAT LIGHTING IS REQUIRED FOR ALL EGRESS
 PATHS INCLUDING THAT TO THE EXIT DISCHARGE
 AREAS/PATHS.
 FOR EXAMPLE: PLEASE SEE THE STAIR AREAS OUTSIDE WHICH
 ARE PART OF THE EXIT DISCHARGE WHICH DO NOT CONTAIN
 BATTERY BACK UP LIGHTING.
 PLEASE SEE THE HALL WHICH DOES NOT INDICATE ANY
 EMERGENCY LIGHTING FIXTURES.
 PLEASE SEE COURTYARD AREAS AS THESE ARE EXIT PATHS
 HOWEVER AS THEY ARE NOT CONSIDERED THE PUBLIC RIGHT OF
 WAY OR SAFE DISTANCE FROM THE BUILDING, EMERGENCY
 LIGHTING FIXTURES WILL BE REQUIRED.
 PLEASE SEE ANY TOILETS WHICH ARE NOT A SINGLE POINT OF
 USE WILL ALSO REQUIRE A BATTERY BACK UP FIXTURES OF
 SOME TYPE.
 PLEASE SEE THERE ARE OTHER AREAS ALSO HOWEVER NOT ALL
 ARE LISTED.
 PLEASE SUBMIT AND PROVIDE LIGHTING PHOTO-METRICS FOR
 ALL EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE
 THE LEVELS UNDER NORMAL FOR STAIRS SHALL MEET THE
 MINIMUM OF 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED TO
 GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. FBC
 104.1.2, FAC 61G15-33.004
 NFPA-101 7.8, 7.9
  
 4) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS
 WHICH COORDINATE ALL LIGHTING ON PLANS AND FIXTURE
 LEGEND. PLEASE SEE THAT NO UPDATED CALCULATIONS WERE
 SUBMITTED BASED ON THE REVISED LIGHTING FIXTURES FROM
 PHASE ONE AND WILL BE REQUIRED BEFORE PHASE TWO
 CONSTRUCTION.
 THE INPUT DATA REPORT NEEDS ALL ITEMS ON PLANS WHICH
 CONSUME ENERGY AND PROVIDES EFFICIENCY TO BE ON THE
 IDR.
 PLEASE SEE 2001 FBC AND CHAPTER 13, 400.2, 400.3.A,
 415.1.AB.1, 415.1.A, TABLE 4-15, 415.2 ETC.
 PLEASE KNOW THE REVISED CALCULATIONS WILL BE REQUIRED
 TO BE DONE UNDER THE CODE IN AFFECT AND UNDER PERMIT
 APPLICATION.
  
  
 5) NOTE: PLEASE CLEARLY SEPARATE ELECTRICAL ON RISER
 FOR WHICH IS PART OF EACH PHASE AS THE PHASE I WORK IS
 COMPLETED.
 PLEASE SHOW HOW ALL NEW WORK WILL TAKE PLACE FOR
 INSTALLATION OF FEEDERS ETC TO EXISTING EQUIPMENT WHICH
 IS CURRENTLY ENERGIZED. THIS WAS GONE OVER SEVERAL
 YEARS AGO WHEN THIS PROJECT STARTED THAT THIS
 INFORMATION WOULD BE NEEDED AT A LATER DATE FOR PHASE
 II.
 FBC 104.1.2
 ** PLEASE SEE THAT REVISIONS ARE BEING SUBMITTED FOR
 SHEETS AND ITEMS WHICH HAVE ALREADY HAD A FINAL
 INSPECTION. PLEASE DO NOT SUBMIT ANY REVISIONS FOR WORK
 WHICH WAS ALREADY COMPLETED EXCEPT THAT WORK WHICH IS
 DIRECTLY AFFECTED BY PHASE II.
 FOR EXAMPLE: WHY ARE ALL VOLTAGES ON PANELS BEING NOTED
 AS REVISIONS?
 PLEASE KNOW THAT A DETAILED RESPONSE LETTER/REVISION
 LISTING LETTER WOULD HELP ON THE REVIEW PROCESS. (NOT
 REQUIRED HOWEVER REVISIONS AS SUBMITTED ARE CONFUSING
 AND SOME CHANGES MADE ARE NOT UNDERSTOOD)
 PLEASE PROVIDE MORE INFORMATION.
  
 6) NOTE: PLEASE SEE FBC CHAPTER 11 FOR ALL MINIMUM
 LEVELS FOR HORN/STROBE DEVICES. ALL LOCATIONS AND
 MINIMUM LEVELS SHALL BE SHOWN AND STATED. 11-4.28.1,.2
 AND .3(4).
 ** EVEN AS THE FA SYSTEM IS UNDER A SEPARATE PERMIT
 THESE ITEMS ARE STILL REQUIRED ON PLANS FOR MINIMUM ADA
 COMPLIANCE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 39 Status P Date 2007-06-05 Cont ID  
Sent By dpalmer Date 2007-06-05 Time 09:58 Rev Time 0.00
Received By dpalmer Date 2007-06-05 Time 09:58 Sent To PC
Notes
2007-06-05 10:00:34REV'SSKE2.04, 2.06A,2.06

Review Stop E ELECTRICAL
Rev No 38 Status N Date 2007-05-11 Cont ID  
Sent By dpalmer Date 2007-05-11 Time 10:05 Rev Time 0.00
Received By dpalmer Date 2007-05-11 Time 10:05 Sent To  
Notes
2007-05-11 10:06:26MECH REV FOR ELECTRICAL RM,NO ELEC .

Review Stop E ELECTRICAL
Rev No 37 Status N Date 2007-02-08 Cont ID  
Sent By dpalmer Date 2007-02-08 Time 10:22 Rev Time 0.00
Received By dpalmer Date 2007-02-08 Time 10:22 Sent To PC
Notes
2007-02-08 10:24:14LETTERS SUBMITTED FOR EXPLANATION OF REVISIONS WAS NOT
 NEEDED FOR RECORD IN THIS OFFICEAT THIS TIME.

Review Stop E ELECTRICAL
Rev No 36 Status P Date 2007-02-03 Cont ID  
Sent By dpalmer Date 2007-02-03 Time 17:29 Rev Time 0.00
Received By dpalmer Date 2007-02-03 Time 16:07 Sent To PC
Notes
2007-02-03 17:32:01REDLINED REVSION #7 ON RISER SHEET WHICH READS REV#6.
 REDLINED, E FIXURES ON E1.02, NOTE #4 MENTIONS
 CONTRACTOR MAY HAVE OPTION,THIS IS NOT THE OPTION OF
 THE CONTRACTOR. EM BATTERY BACK UP FIXTUURES WERE
 REDLINED ON PLANS PREVIOUSLY.THEMAIN ELECTRICAL
 ROOM, GEN RM, FIIRE PUMP AND ELEVATOR EQUIPMENT ROOMS
 SHOULD CONTAIN BATTERY BACK UP FIXTURES OF SOME SORT.

Review Stop E ELECTRICAL
Rev No 35 Status P Date 2007-02-03 Cont ID  
Sent By dpalmer Date 2007-02-03 Time 16:05 Rev Time 0.00
Received By dpalmer Date 2007-02-03 Time 16:05 Sent To M
Notes
2007-02-03 16:07:02REVISION TO ADD A/C IN ELEVATOR EQUIPMENT ROOM TO EM
 PANEL.
 ROUTED TO MECH.

Review Stop E ELECTRICAL
Rev No 34 Status P Date 2006-12-07 Cont ID  
Sent By dpalmer Date 2006-12-07 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2006-12-06 Time 20:14 Sent To PC
Notes
2006-12-07 16:42:19REVISIONS FOR AVAILABLE FAULT CURRENT, EQUIPMENT AND
 BREAKER CHANGES.
2006-12-06 20:24:58IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 33 Status P Date 2006-12-07 Cont ID  
Sent By dpalmer Date 2006-12-07 Time 15:30 Rev Time 0.00
Received By dpalmer Date 2006-12-06 Time 20:14 Sent To FIRE
Notes
2006-12-07 15:30:54FIRE PUMP SUBMITTIALS, ELECTRICAL SECTION FOR FPC OK,
 STAMPED AND ROUTED TO FIRE.
2006-12-07 06:46:13REVIEW IN PROGRESS
2006-12-06 20:24:42IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 32 Status P Date 2006-12-05 Cont ID  
Sent By dpalmer Date 2006-12-05 Time 13:11 Rev Time 0.00
Received By dpalmer Date 2006-12-05 Time 12:14 Sent To PC
Notes
2006-12-05 13:11:47SKE SHEETS, FOR LIGTHING LAYOUT CHANGES ONLY, FOUR 8
 1/2 BY 11'S.

Review Stop E ELECTRICAL
Rev No 31 Status P Date 2006-12-05 Cont ID  
Sent By dpalmer Date 2006-12-05 Time 13:10 Rev Time 0.00
Received By dpalmer Date 2006-12-05 Time 12:14 Sent To PC
Notes
2006-12-05 13:11:21SKE SHEETS, FOR LIGTHING LAYOUT CHANGES ONLY, THREE 8
 1/2 BY 11'S.

Review Stop E ELECTRICAL
Rev No 30 Status F Date 2006-11-30 Cont ID  
Sent By dpalmer Date 2006-11-30 Time 17:29 Rev Time 0.00
Received By dpalmer Date 2006-11-21 Time 11:31 Sent To PC
Notes
2006-11-30 17:31:44**** UNSAT ****
  
 1) NOTE: PLEASE SEE IN REVIEW OF LETTER PROVIDED WITH
 RESPECT TO ?INTEGRATED EQUIPMENT RATED SYSTEM AND
 "SERIES RATED" SYSTEM. PLEASE EXPLAIN HOW THIS WILL OR
 WILL NOT AFFECT THE SELECTIVE COORDINATION OF THE
 SYSTEM.
 PLEASE SEE 90.1A, 110.9, 110.10, 240.4A, 240.12 AND
 NFPA-110 (2002) 6.5.
 ALL SYSTEM SHALL BE RATED FOR THE AVAILABLE FAULT
 CURRENTS ON THE PRIMARY/FPL SIDE AND THE AVAILABLE
 FAULT CURRENT ON THE SECONDARY, HOWEVER PLEASE VERIFY
 AND SHOW HOW THIS CHANGING OF THE SYSTEM WILL AFFECT
 SECTIONS AS NOTED ABOVE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2006-11-21 12:25:39SPOKE TO ENGINEER, LTRT ON HOLD TO REVIEW FURTHER.

Review Stop E ELECTRICAL
Rev No 29 Status P Date 2006-11-13 Cont ID  
Sent By dpalmer Date 2006-11-13 Time 16:26 Rev Time 0.00
Received By dpalmer Date 2006-11-13 Time 16:26 Sent To PC
Notes
2006-11-13 16:27:47REV FOR SKE 1.06, FROM SHEET E6.02 AND SKE-6.02. OK.
 ONLY ONE LETTER OF EXPLANATION SUBMITTED FROM ENGINEER,
 RETAINED FOR OUR FILE SET.

Review Stop E ELECTRICAL
Rev No 28 Status P Date 2006-11-13 Cont ID  
Sent By dpalmer Date 2006-11-13 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2006-11-13 Time 15:05 Sent To FIRE
Notes
2006-11-13 15:07:14SKE-1.06,FROM SHEET E106,LOCATION CHANGE FOR RECESSED
 EM LTS, OK WITH ELEC, SENT TO FIRE.

Review Stop E ELECTRICAL
Rev No 27 Status F Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 13:55 Rev Time 0.00
Received By dpalmer Date 2006-10-28 Time 13:54 Sent To PC
Notes
2006-10-28 13:57:09** UNSAT **
  
 1) NOTE: SKE-6.02, PLEASE BE SURE A NOTE WHICH STATES
 THE "LOCK-OFF" DEVICE SHALL BE AN INTEGRAL PART OF THE
 BREAKER.
 DEVICE CAN NOT BE A CLIP/SNAP ON DEVICE.
 110.3,90.4.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 26 Status P Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 13:54 Rev Time 0.00
Received By dpalmer Date 2006-10-28 Time 13:41 Sent To PC
Notes
2006-10-28 13:54:59REV FOR DOOR EGRESS OK, UNDER FAILURE OF POWER, EGRESS
 IN NOT IMPEDED.

Review Stop E ELECTRICAL
Rev No 25 Status P Date 2006-10-21 Cont ID  
Sent By dpalmer Date 2006-10-21 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2006-10-21 Time 17:00 Sent To PC
Notes
2006-10-21 17:43:17REV'S.
  
 E0.02A, 1.02, 1.04,
 1.06,1.07,2.02,2.04,2.06,3.02,3.06,3.08,4.01

Review Stop E ELECTRICAL
Rev No 24 Status N Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 14:26 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 14:26 Sent To  
Notes
2006-10-15 14:26:57SK' SHEETS FOR SMOKE DAMPERS, SMOKE SHIELDS ETC NOT FOR
 ELECTRICAL REVIEW.

Review Stop E ELECTRICAL
Rev No 23 Status P Date 2006-10-05 Cont ID  
Sent By dpalmer Date 2006-10-05 Time 11:38 Rev Time 0.00
Received By dpalmer Date 2006-10-05 Time 11:14 Sent To PC
Notes
2006-10-05 00:00:00REV LTR ABOUT DELETION OF SHEETS ON
 PREVIOUS REVIEWS.

Review Stop E ELECTRICAL
Rev No 22 Status P Date 2006-10-05 Cont ID  
Sent By dpalmer Date 2006-10-05 Time 11:39 Rev Time 0.00
Received By dpalmer Date 2006-10-05 Time 11:14 Sent To PC
Notes
2006-10-05 00:00:00LT-ING REV'S OK.

Review Stop E ELECTRICAL
Rev No 21 Status P Date 2006-09-22 Cont ID  
Sent By dpalmer Date 2006-09-22 Time 20:13 Rev Time 0.00
Received By dpalmer Date 2006-09-22 Time 20:01 Sent To PC
Notes
2006-09-22 00:00:00*** NOTES ***
  
 ** PLEASE SEE ALL REV'S FOR MOTORIZED
 CURTAINS , RECEPTS OK.
  
 1) NOTE: PLEASE SUBMIT ELECTRICAL SITE
 LIGHTING UNDER A SEPARATE ELECTRICAL
 PERMIT, WHICH WILL INCLUDE ALL
 REFERENCES TO THE PANELS, CIRCUITS
 ETC.(AS SHOWN)
 PLEASE SUBMIT LIGHTING FIXTURES
 SPECS/MANUFACTURE SHEETS INDICATING THE
 LISTINGS FROM A NRTL. (UL, CSA, MET,
 ETL, TUV, ETC.)
  
 ** PLEASE KNOW, ANY LTS /POLES OVER 6FT
 SHALL ALSO SUBMIT WIND LOAD CALCULATIONS
 FOR REVIEW.
  
 2) NOTE: PLEASE SUBMIT ACCESS CONTROL
 SYSTEM UNDER A LV PERMIT WHICH WILL SHOW
 THE SAME LOCATIONS AND NOTES AS
 INDICATED ON PLANS SUBMITTED, HOWEVER
 PLEASE ALSO SUBMIT THE SPEC/CUT SHEETS
 FOR SYSTEM AND DEVICES TO BE INSTALLED.
 PLEASE KNOW, THIS WILL ALSO BE REVIEWED
 BY THE FIRE MARSHAL'S OFFICE FOR THE
 FAIL SAFE OPERATION, UNDER POWER LOSS
 ETC. THIS INFORMATION IS SHOWN/NOTED ON
 PLANS AND SHOULD NOT BE AN ISSUE,
 HOWEVER WILL REVIEW FIRE'S REVIEW.
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 20 Status N Date 2006-09-07 Cont ID  
Sent By dpalmer Date 2006-09-07 Time 12:43 Rev Time 0.00
Received By dpalmer Date 2006-09-07 Time 12:43 Sent To  
Notes
2006-09-07 00:00:00REVISION FOR CEILING DETAIL IS NOT FOR
 ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 19 Status P Date 2006-07-28 Cont ID  
Sent By dpalmer Date 2006-07-28 Time 19:09 Rev Time 0.00
Received By dpalmer Date 2006-07-28 Time 18:58 Sent To P
Notes
2006-07-28 00:00:00REV FOR KITCHEN CIRCUITING TO KITCHEN
 PANEL.
 PANEL FROM PREVIOUS REVISION LOCATED IN
 CABINET WAS REMOVED.

Review Stop E ELECTRICAL
Rev No 18 Status P Date 2006-07-27 Cont ID  
Sent By dpalmer Date 2006-07-27 Time 17:11 Rev Time 0.00
Received By dpalmer Date 2006-07-27 Time 17:11 Sent To PC
Notes
2006-07-27 00:00:00REV FOR UNDERGROUND LV COMMUNICATION
 CONDUIT.

Review Stop E ELECTRICAL
Rev No 17 Status P Date 2006-07-24 Cont ID  
Sent By dpalmer Date 2006-07-24 Time 12:30 Rev Time 0.00
Received By dpalmer Date 2006-07-24 Time 11:00 Sent To PC
Notes
2006-07-24 00:00:00REV'S TO LIGHTING CONTROLS, CIRCUITING,
 ZONES, SOME PANELS ON RISERS AND
 SCHEDULE.S

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2006-07-24 Cont ID  
Sent By dpalmer Date 2006-07-24 Time 10:58 Rev Time 0.00
Received By dpalmer Date 2006-07-24 Time 09:48 Sent To PC
Notes
2006-07-24 00:00:00GEN REV'S TO RECEPTS AND FLR BOXES,
 CIRCUITINGTO FLR BOXES.
 0.01,2.02, 2.04, 2.06, 5.04

Review Stop E ELECTRICAL
Rev No 15 Status P Date 2006-06-25 Cont ID  
Sent By dpalmer Date 2006-06-25 Time 14:10 Rev Time 0.00
Received By dpalmer Date 2006-06-25 Time 14:10 Sent To PC
Notes
2006-06-25 00:00:00** REV, SKEC, FOR ADDED RECEPT/LV FOR
 ATM MACHINES.

Review Stop E ELECTRICAL
Rev No 14 Status F Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 16:21 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 16:21 Sent To PC
Notes
2006-05-14 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE SHEET IN ONE SET
 NOTE SIGNED AND DATED BY ENGINEER.
 FS 471.025
  
 2) NOTE: PLEASE SEE PANEL LB14 IS NOW
 BEING MOVED INTO THE GEN ROOM?
 PLEASE CLARIFY THIS AND PLEASE SEE
 NFPA-110 FOR ELECTRICAL EQUIPMENT
 PERMITTED IN GEN RM, SHALL BE PART OF
 THE EPSS.
  
 ** PLEASE ALSO SEE COMMENTS DATED 5/4/06
  
 PLEASE SUBMIT THE ABOVE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 13 Status F Date 2006-05-04 Cont ID  
Sent By dpalmer Date 2006-05-04 Time 17:44 Rev Time 0.00
Received By dpalmer Date 2006-05-04 Time 17:44 Sent To  
Notes
2006-05-04 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS
 IN OTHER THAN DWELLING UNITS AND GFI
 PROTECTION REQUIRED.
  
 2) NOTE: PLEASE SEE PLANS MENTIONS FOR A
 "JUNCTION BOX" TO CONTAIN A NEW
 DISTRIBUTION PANEL. PLEASE SEE
 240.24,408,110.26 A DISTIBUTION PANEL
 MAY NOT BE INSIDE A J-BOX. THERE IS NOT
 ENOUGH INFORMATION AND IT DOES NOT SEEM
 LIKE THIS WILL BE PERMITTED.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2006-04-27 Cont ID  
Sent By dpalmer Date 2006-04-27 Time 14:21 Rev Time 0.00
Received By dpalmer Date 2006-04-27 Time 11:04 Sent To  
Notes
2006-04-27 00:00:00REV DATED 3/7/06, SHEETS,
 2.03,2.06,5.04,5.05

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2006-04-27 Cont ID  
Sent By dpalmer Date 2006-04-27 Time 10:50 Rev Time 0.00
Received By dpalmer Date 2006-04-27 Time 10:41 Sent To  
Notes
2006-04-27 00:00:00REV'S
 2.01,2.02,2.06,2.07,2.08,3.06,5.02,
 5.04,5.05

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2006-04-24 Cont ID  
Sent By dpalmer Date 2006-04-24 Time 16:55 Rev Time 0.00
Received By dpalmer Date 2006-04-24 Time 16:55 Sent To PC
Notes
2006-04-24 00:00:00REV'S DATED 4/14/06 FOR 2.02,3.02,5.02,
 5.04, 6.02

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2006-04-03 Cont ID  
Sent By dpalmer Date 2006-04-03 Time 09:09 Rev Time 0.00
Received By dpalmer Date 2006-04-03 Time 08:47 Sent To PC
Notes
2006-04-03 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE ALL SHEETS FORM
 REVISION FROM E2.02. PLEASE REVISE SHEET
 2.02.
 PLEASE ALSO SEE THAT TITLE BLOCK FOR
 FIRM SHALL BE AFFIXED TO ALL SHEETS
 BEING REVISED AS "HANSON ENGINEERING
 SERVICES" IS THE FRIM OF RECORD. IT IS
 NOTED THE FIRM # IS ON SHEETS.
  
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-04-03 Cont ID  
Sent By dpalmer Date 2006-04-03 Time 09:04 Rev Time 0.00
Received By dpalmer Date 2006-04-03 Time 08:47 Sent To PC
Notes
2006-04-03 00:00:00REV'S FOR PA SYSTEM, CCTV LOCATIONS.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-04-03 Cont ID  
Sent By dpalmer Date 2006-04-03 Time 09:04 Rev Time 0.00
Received By dpalmer Date 2006-04-03 Time 08:47 Sent To PC
Notes
2006-04-03 00:00:00REV'S FOR LIGHTING LAYOUTS.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-03-17 Cont ID  
Sent By dpalmer Date 2006-03-17 Time 18:20 Rev Time 0.00
Received By dpalmer Date 2006-03-17 Time 18:08 Sent To FIRE
Notes
2006-03-17 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE PLANS ARE NOW COMING
 IN WITH A REFERENCE TO A NEW "IT" ROOM.
 WITH THE DECLARATION, PLEASE SEE NFPA-75
 FOR STRUCTURAL COMPONETS, MECHANICAL
 SYSTEMS/DUCTS WHICH FEED THIS ROOM AND
 PLEASE SEE 645 OF NFPA-70 FOR
 INFORMATION FOR ELECTRICAL SYSTEMS
 FEEDING SUCH ROOM. 645.10,645.7,645.5
 ETC.
 PLEASE ADJUST AS NEEDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-09-04 Cont ID  
Sent By dpalmer Date 2005-09-04 Time 16:28 Rev Time 1.25
Received By dpalmer Date 2005-09-04 Time 15:03 Sent To  
Notes
2005-09-04 00:00:00*** NOTE ***
  
 ** PLANS IN TEMPORARY "F" STATUS.
 ONE SHEET (E 5.04) IN THIRD SET DID NOT
 GET SIGNED AND DATED BY THE ENGINEER OF
 RECORD. CALLED AND LEFT MESSAGE FOR
 ENGINEER TO COME IN AND SIGN SHEET.
  
 ALL THREE SETS STAMPED FOR REVISIONS OF
 LIGHTING FIXTURES FOR EGRESS ETC.
 REVISIONS FOR CIRCUITING FOR ELEVATOR
 EQUIPMENT RMS.
 REVISED SHEET:
 E-SHEETS
 5.01,0.02,1.01,1.02,1.03,1.04,1.05,
 1.06,1.07,1.08,2.02,4.02,5.03, 5.04
  
  
 ** REDLINED PLANS, AN EMERGENCY BATTERY
 BACK-UP TYPE LT FIXTURE WILL BE REQUIRED
 IN MAIN ELECTRICAL RM.
 NFPA-70, 700.16, NFPA-101 7-9
  
 NOTED NFPA-101 11-8.5(9) FOR CENTRAL
 STATION AREA.
2005-09-03 00:00:00IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 12:26 Rev Time 1.50
Received By dpalmer Date 2005-07-06 Time 12:25 Sent To  
Notes
2005-07-06 00:00:00******** NOTES/ REVSION /PROVISO *****
  
 1)NOTE: PLEASE SEE CIRCUITING FOR
 ELEVATOR EQUIPMENT ROOMS FOR LTS AND
 RECEPTS SHALL MEET 620.23,620.24.
  
 2)NOTE: PLEASE SEE EGRESS LIGHTING
 CIRCUITING SHALL BE WIRED AS ALTERNATING
 CIRCUITS TO ALLEAVIATE ANY SINGLE MEANS
 OF DISCONNECT, TRIPPING OF BRKR ETC TO
 LEAVE ANY AREA IN DARKNESS.
 LS NFPA-101 7-9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 3RD SET SUBMITTED BY STEVE KNIGHT FOR
 "A, S, M.E.P"S.
 STAMPED 3RD SET OF ELECTRICAL PLANS. OK
 WITH PROVISO.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-06-24 Cont ID  
Sent By dpalmer Date 2005-06-24 Time 16:42 Rev Time 5.00
Received By dpalmer Date 2005-06-24 Time 15:18 Sent To  
Notes
2005-06-27 00:00:00*********IN FAILED STATUS *********
  
 ONLY TWO SETS OF PLANS SUBMITTTED .
 ONLY TWO JOBSITE SPEC BOOKS SUBMITTED.
  
 TWO SETS OF PLANS STAMPED AND NOTED WITH
 "PROVISO".
2005-06-24 00:00:00******** NOTES/ REVSION /PROVISO *****
  
 1)NOTE: PLEASE SEE CIRCUITING FOR
 ELEVATOR EQUIPMENT ROOMS FOR LTS AND
 RECEPTS SHALL MEET 620.23,620.24.
  
 2)NOTE: PLEASE SEE EGRESS LIGHTING
 CIRCUITING SHALL BE WIRED AS ALTERNATING
 CIRCUITS TO ALLEAVIATE ANY SINGLE MEANS
 OF DISCONNECT, TRIPPING OF BRKR ETC TO
 LEAVE ANY AREA IN DARKNESS.
 LS NFPA-101 7-9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-02 Cont ID  
Sent By dpalmer Date 2005-03-02 Time 13:55 Rev Time 5.00
Received By dpalmer Date 2005-03-02 Time 09:21 Sent To  
Notes
2005-03-02 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE SEE BLDG/FIRE AND
 MECHANICAL REVIEW NOTES FOR "ATRIUM".
 IT IS MY UNDER STANDING A VARIANCE IS TO
 BE APPLIED FOR WHICH MAY OR MAY NOT
 AFFECT ELECTRICAL PLANS.
  
 2)NOTE: PLEASE SEE A DETAILED LETTER(?)
 WILL BE REQUIRED FOR PHASE II AND SHUT
 DOWN OF ELECTRICALEQUIPMENT BEFORE
 PULLING IN CONDUCTORS ETC.
  
 3)NOTE: PLEASE SEE RESPONSE LTR
 MENTIONS; "THE LIGHTNING PROTECTION
 SYSTEM UNDER THE ELECTRICAL CONTRACTOR'S
 PERMIT (OR) A SEPARATE SUBCONTRACTOR
 PERMIT". PLEASE SEE SINCE LIGHTNING
 PROTECTION SYSTEM HAS BEEN REMOVED FROM
 PLANS. THIS WILL BE REQUIRED TO BE UNDER
 SEPARATE PERMIT AND MAY NOT BE UNDER
 ELECTRICAL CONTRACTORS BASEBUILDING
 ELECTRICAL PERMIT.
  
 4)NOTE: PLEASE SEE RESPONSE LTR TO NOTE
 #4 FROM PREVIOUS REVIEW WHICH MENTIONS;
 A)L2B3: "THIS PANEL IS A SPARE PANEL FOR
 FUTURE LOADS".
 PLEASE CLARIFY, PANEL SCHEDULE FOR L2B3
 CONTAINS NUMEROUS CIRCUITS AND LOADS??
  
 5)NOTE: PLEASE SEE NOTE #4 FROM PREVIOUS
  
 REVIEW; RESPONSE LTR PART;
 H) L1A2: RISER TO BE CHANGED TO 125A,
 FEEDER SIZE WILL BE CHANGED
 ACCORDINGLY".
 PLEASE SEE PANEL ON RISER NOW MENTIONS
 150A MLO, AND PANEL INDICATES 150A MCB.
 PLEASE SEE INCREASE FROM LTR NOTING 125A
 WHICH IS FINE, HOWEVER RISER INDICATES
 MLO, WHEN MCB IS REQUIRED FOR SECONDARY
 SIDE OF TRANSFORMER.
 THIS SEEMS TO BE A MISPRINT?
  
 6)NOTE: PLEASE SEE EH2 IS A 200MCB FED
 FROM MSB WITH A 200A BRKR. THIS IS OK,
 HOWEVER FEED FROM GENERATOR INDICATES A
 400A BRKR FEEDING 400A ATS AND THEN TO
 200A RATED PANEL/BRKR.
 PLEASE VERIFY THIS.
 PLEASE ALSO VERIFY CONDUCTORS/CONDUITS
 FROM GENERATOR TO NEW DISC'S, DISC'S
 BACK TO ATS AND ATS TO PANELS EH2.
 PLEASE VERIFY IF A TAP RULE IS OF SOME
 SORT IS BEING APPLIED.
 PLEASE ALSO SEE POSSIBLE VOLTAGE DROP.
  
 7)NOTE: PLEASE SEE MANUFACTURE CUT/SPECS
 SHEETS STILL REQUIRED FOR FIRE PUMP/
 FIRE PUMP CONTROLLER, ATS, GNERATOR AND
 SUB BASE FUEL FOR LIQUID TYPE FUELS.
 SPECS BOOKS DO NOT SEEM TO SPECIFICALLY
 DESIGNATE EQUIPMENT, SIZES ETC.
  
  
 8)NOTE: PLEASE SEE SPEC BOOK PAGE
 16075-8, MENTIONS BROWN, ORANGE, YELLOW
 FOR 277/480V SYSTEMS.
 PLEASE SEE "B" IS NOT A HIGH-LEG FOR
 277/480V. PLEASE SEE LOCAL AMENDMENTS
 FOR BR/ PURPLE/ YELLOW.215
  
 9)NOTE: PLEASE SEE ONLY SET OF SPECS
 BOOKS WERE SUBMITTED, PLEASE SUBMIT TWO
 MORE SETS FOR REVIEW.
  
 PLEASE SEE DUE TO HAND WRITTEN NOTES
 ADDED FOR LOCKED ROTOR FOR FIRE PUMP ETC
 ANDCOMMENTS FOR CONDUCTORS/ CONDUITS
 AND PANEL L1A2, PLEASE REVISE AND
 REPRINT NEW RISER DIAGRAM SHEET.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-22 Cont ID  
Sent By dpalmer Date 2004-12-22 Time 14:15 Rev Time 12.00
Received By dpalmer Date 2004-12-22 Time 14:15 Sent To  
Notes
2004-12-22 00:00:00*************** UNSAT *****************
  
 PALM BEACH ATLANTIC UNIVERSITY
 WARREN LIBRARY
  
 1)NOTE: PLEASE SEE 230.72 FOR GROUPING
 OF MAINS.
 PLEASE SEE LOCATION OF EHDP1. THIS WILL
 BE REQUIRED TO BE LOCATED IN CLOSE
 PROXIMITY OF MSB.
 230.72B THE ONE OR MORE ADDITIONAL
 SERVICE DISCONNECTING MEANS FOR FIRE
 PUMPS, FOR LEGALLY REQUIRED STANDBY, OR
 FOR OPTIONAL STANDBY SERVICES PERMITTED
 BY 230.2 SHALL BE INSTALLED REMOTE FROM
 THE ONE TO SIX SERVICE DISCONNECTING
 MEANS FOR NORMAL SERVICE TO MINIMIZE
 THE
 POSSIBILITY OF SIMULTANEOUS
 INTERRUPTION
 OF SUPPLY. HOWEVER, A RESPONSE FROM
 NFPA
 MENTIONS REMOTE MAY BE A CLOSE AS 10'.
 THIS WAS BROUGHT UP IN PREVIOUS
 MEETINGS
 AND DECIDED THIS LOCATION WAS TO BE
 MOVED?
  
 2)NOTE: PLEASE SEE LIGHTNING PROTECTION
 SYSTEM:IF THIS WILL BE INSTALLED
 UNDER
 MAIN ELECTRICAL CONTRACTORS PERMIT:
 PLEASE SUBMIT COMPLETE PLANS FOR THIS
 UNDER NFPA-780. IF THIS WILL BE
 INSTALLED BY ASUB-CONTRACTOR THIS MAY
 BE DONE UNDER SEPARATE PERMIT. PLEASE
 ONLY REFERENCE ON PLANS AND REMOVE
 LIGHNING AS SHOWN.
  
 3)NOTE: PLEASE SEE CONDUIT FILL FOR
 1-1/2" CONDUIT SIZE TO HDP2 ON MSB.
  
 4)NOTE: PLEASE CORRELATE PANEL
 SCHEDULES, PANELS AND EQUIPMENT SHOWN
 ON
 RISER DIAGRAM.
 PLEASE SEE THE FOLLOWING AS A SOME
 NOTED
 ON PLAN REVIEW.
  
 L2B3-NO PANEL SCHEDULE?
 EL3- NO PANEL SCHEDULE?
 L1B3- PANEL NOT INDICATED ON LEGEND ON
 E5.04, MISSING INFORMATION ON RISER,
 OCP,SIZE?
 H2B1- 225A ON RISER 400A ON PANEL
 SCHEDULE.
 EH2- NOT ON RISER?
 H1B2- 400A ON PANEL SCHEDULE, 225A ON
 RISER.
 L4A1- 250A ON RISER 225A ON PANEL
 SCHEDULE.
 L1A2- 125A ON PANEL SCHEDULE,225A ON
 RISER.
 L2B1- 250A ON RISER AND 400A ON PANEL
 SCHEDULE.
  
 5)NOTE: PLEASE SEE SIZE OF OCP FOR
 TRANSFORMER T1A1, MAX 125% 450.3
  
 6)NOTE: PLEASE SEE A MCB WILL BE
 REQUIRED FOR L3A2 ON THE LOAD SIDE OF
 THE TRANSFORMER. PLEASE SEE LOADS ARE
 NOT SPECIFIC.IN ADDITION TO THE
 REQUIREMENTS OF 408.13, A POWER
 PANELBOARD WITH SUPPLY CONDUCTORS THAT
 INCLUDE A NEUTRAL AND HAVING MORE THAN
 10 PERCENT OF ITS OVERCURRENT DEVICES
 PROTECTING BRANCH CIRCUITS RATED 30
 AMPERES OR LESS SHALL BE PROTECTED BY
 AN
 OVERCURRENT PROTECTIVE DEVICE HAVING A
 RATING NOT GREATER THAN THAT OF THE
 PANELBOARD. THE OVERCURRENT PROTECTIVE
 DEVICE SHALL BE LOCATED WITHIN OR AT
 ANY
 POINT ON THE SUPPLY SIDE OF THE
 PANELBOARD.
  
 7)NOTE: PLEASE SUBMIT COMPLETED
 INFORMATION FOR FIRE PUMP.
 PLEASE SEE 695.4B1 THE OVERCURRENT
 PROTECTIVE DEVICE(S) SHALL BE SELECTED
 OR SET TO CARRY INDEFINITELY THE SUM OF
 THE LOCKED-ROTOR CURRENT OF THE FIRE
 PUMP MOTOR(S) AND THE PRESSURE
 MAINTENANCE PUMP MOTOR(S) AND THE
 FULL-LOAD CURRENT OF THE ASSOCIATED
 FIRE
 PUMP ACCESSORY EQUIPMENT WHEN CONNECTED
 TO THIS POWER SUPPLY.
 PLEASE SEE SECONDARY OCP IS NOT
 PERMITTED AS SHOWN.695.5BTHE PRIMARY
 OVERCURRENT PROTECTIVE DEVICE(S) SHALL
 BE SELECTED OR SET TO CARRY
 INDEFINITELY
 THE SUM OF THE LOCKED-ROTOR CURRENT OF
 THE FIRE PUMP MOTOR(S) AND THE PRESSURE
 MAINTENANCE PUMP MOTOR(S) AND THE
 FULL-LOAD CURRENT OF THE ASSOCIATED
 FIRE
 PUMP ACCESSORY EQUIPMENT WHEN CONNECTED
 TO THIS POWER SUPPLY. SECONDARY
 OVERCURRENT PROTECTION SHALL NOT BE
 PERMITTED.
  
 8)NOTE: PLEASE SEE NO INFORMATION WAS
 GIVEN FOR FIRE PUMP CONTROLLER. PLEASE
 SEE RISER DOES NOT INDICATE ANY METHOD
 OF TRANSFER OF POWER FROM FPL AND
 GENERATOR FOR FIRE PUMP?
 PLEASE COMPLETE AND SUBMIT ALL
 MANUFACTURE SPECS FOR FIRE PUMP, FIRE
 PUMP CONTROLLER, ATS, GENERATOR, FUEL
 ETC.
  
 9)NOTE: PLEASE SEE SOME ELECTRICAL ROOM
 LAYOUTS DO NOT MEET 110.26 FOR CODE
 COMPLIANCE.
 PLEASE SEE PLANS AND ADJUST.
  
 10)NOTE: PLEASE SHOW GROUNDING
 ELECTRODE
 SYSTEM PER 250.50. COULD NOT LOCATE ANY
 ON ELECTRICAL PLANS SUBMITTED.
  
 11)NOTE: PLEASE SHOW GROUNDING FOR ALL
 TRANSFORMERS OR A COMMON DETAIL FOR
 TRANSFORMERS PER 250.30
  
 12)NOTE: PLEASE SEE NOTES FROM ALL
 OTHER
 REVIEWERS ON THE SCOPE OF WORK FOR
 PAHSE
 ONE AND TWO AND POSSIBLE SEPARATE
 PERMITS FOR EACH OR ALL WORK MUST BE
 COMPLETED UNDER ONE PHASE.
 PHASE ONE WILL NOTBE PERMITTED TO
 HAVE
 POWER WITH FEEDERS ETC FOR PHASE TWO
 NOT
 INSTALLED AND PULLED/SAFED OFF ETC.
 PLEASE SEE THAT A MEETING TO DICUSS THE
 PROCESS OF PHASES, COMPLETIONS, C/O'S
 ETC.
  
 13)NOTE: PLEASE SEE DUE TO COMPLETE
 INFORMATION NOT SUBMITTED AT THIS TIME
 A
 COMPLETE REVIEW FOR CODE COMPLIANCE CAN
 NOT BE DONE.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
  
  
 IF SYSTEM IS
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 6 Status N Date 2008-07-17 Cont ID  
Sent By rchokshi Date 2008-07-17 Time 11:40 Rev Time 0.00
Received By rchokshi Date 2008-07-17 Time 11:34 Sent To  
Notes
2008-07-17 11:40:32YOUR DRAWING REVISED SEWER CONNECTION WHICH IS MORE
 THAN 5 FEET AWAY FROM THE BUILDING.THEREFORE,
 PLUMBING DOES NOT LOOK AT ANY WATER/SEWER MORE THAN 5
 FEET AWAY GROM BUILDING PER KEN STEVENS.I ASKED
 KINSSION GRACIEN OF WEITZ CO. TO TAKE IT TO MANNY
 GONZALEZ AT 1000 45TH ST. FOR HIS REVIEW.
  
 RASIK CHOKSHI

Review Stop ENG ENGINEERING CSD
Rev No 5 Status N Date 2007-10-04 Cont ID  
Sent By rchokshi Date 2007-10-04 Time 16:22 Rev Time 0.00
Received By rchokshi Date 2007-10-04 Time 16:22 Sent To P
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2007-09-06 Cont ID  
Sent By rchokshi Date 2007-09-06 Time 15:39 Rev Time 0.00
Received By rchokshi Date 2007-09-06 Time 15:30 Sent To  
Notes
2007-09-06 15:39:52****FAILED***
  
 YOU HAVE NOT WRITTEN ANYTHING IN REVISION AND
 SUBMITTALS FORM.WE NEED TO KNOW WHAT WAS CHANGED
 FROM LAST REVISION IN DETAIL,LIKE STORM WATER CALS
 CHANGED, PARKING, HANDICAP PARKING, SIDEWALK, SLOPE,
 ETC CHANGED ANYTHING FROM PREVIOUS REVISION??PLEASE
 EXPLAIN.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2005-06-08 Cont ID  
Sent By mamini Date 2005-06-08 Time 13:42 Rev Time 1.00
Received By mamini Date 2005-06-08 Time 13:41 Sent To  
Notes
2005-06-08 00:00:00NOTE:
  
 1. CONTRACTOR APPLIED FOR A SEPARATE
 UNDERGROUND UTILITIES AND SITE WORK IN
 ORDER TO START THE PROJECT, SEE PERMIT #
 05060590.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-02-11 Cont ID  
Sent By mamini Date 2005-02-11 Time 13:35 Rev Time 0.50
Received By mamini Date 2005-02-11 Time 13:34 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-12-08 Cont ID  
Sent By mamini Date 2004-12-08 Time 09:00 Rev Time 1.00
Received By mamini Date 2004-12-08 Time 09:00 Sent To  
Notes
2004-12-08 00:00:00FAILED:
  
 1. PLEASE NOTE THAT ACCORDING TO OUR
 RECORDS, REVIEW COMMENTS FORM THE
 PUBLIC UTILITIES AND ENGINEERING HAVE
 NOT BEEN ADDRESSED, PLEASE CONTACT
 MANNY GONZALEZ AT 494-1085.
 2. PLEASE SUBMIT STORM WATER
 CALCULATIONS FOR THE PROPOSED SITE FOR
 OUR REVIEW AND APPROVAL.
 3. PLEASE SHOW THE FDCS, NOTE THAT THEY
 SHOULD BE LOCATED NOT MORE THAN
 150'FROM THE CLOSEST FIRE HYD.
 3. SHEET C3.01, SHOWS A EXIST. METER &
 A BACKFLOW, HOW THEY ARE BEING
 CONNECTED?
 4. SHEET C3.01, SHOWS 4" CALV WM, IF
 NOT BEING USED, IT SHOULD BE CAPPED AT
 GATE VALVE IN KINGS COURT.
 5. SHEET SP1.01 SHOWS WM ON SOUTH OF
 THE PROPOSED SITE CONNECTED TO A NEW
 FHYD, THEN CONNECTED TO THE 4" CALV WM
 IN KINGS COURT, SHEET C3.01 SHOWS THIS
 LINE BEING CAPPED AT PROPERTY LINE,
 PLEASE VERIFY.
 6. PLEASE INCLUDE POLLUTION PREVENTION
 PLANS IN CIVIL DRAWING.
 7. A SAFTY FENCE 8'HIGH SHOULD BE
 INSTALLED ALONG SIDE OF THE OLIVE AND
 PEMBBROKE PLACE AND MAINTAINED DURING
 THE CONST.
 8. PLEASE NOTE THAT WORK IN PUBLIC
 R.O.W REQUIRES A SEPARATE PERMIT FROM
 THE FDOT AND THE PUBLIC UTILITIES AND
 ENGINEERING,494-1086.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 21 Status P Date 2009-06-02 Cont ID  
Sent By mawillia Date 2009-06-02 Time 17:20 Rev Time 0.00
Received By mawillia Date 2009-06-02 Time 17:00 Sent To  
Notes
2009-06-02 17:08:03*****REVISION #7, DATED 3/16/2009, APPROVED*****
  
  
 REVISED SHEET E1.01 (OF THE 5 REVISED ELECTRICAL
 SHEETS) STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 20 Status P Date 2009-04-10 Cont ID  
Sent By mwennerg Date 2009-04-10 Time 14:08 Rev Time 0.00
Received By mwennerg Date 2009-04-10 Time 14:08 Sent To  
Notes
2009-04-10 14:09:05REVISION DATED 2/27/09

Review Stop FIRE FIRE DEPARTMENT
Rev No 19 Status P Date 2009-01-22 Cont ID  
Sent By mwennerg Date 2009-01-22 Time 14:01 Rev Time 0.00
Received By mwennerg Date 2009-01-22 Time 14:01 Sent To  
Notes
2009-01-22 14:01:50REVISION #4 DATED 12/09/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 18 Status P Date 2009-01-06 Cont ID  
Sent By mwennerg Date 2009-01-06 Time 14:00 Rev Time 0.00
Received By mwennerg Date 2009-01-06 Time 14:00 Sent To  
Notes
2009-01-06 14:01:44REVISION CCD #15 DATED 11/19/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 17 Status P Date 2008-12-22 Cont ID  
Sent By mawillia Date 2008-12-22 Time 14:00 Rev Time 0.00
Received By mawillia Date 2008-12-19 Time 15:50 Sent To E
Notes
2008-12-22 14:00:21*****REVISION APPROVED*****
  
  
 REVISED (3/02/07) PLAN SHEETS FPO.01, FP1.01, FP1.03,
 FP1.05 AND REVISED (10/30/08) PLAN SHEET FP1.07 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 16 Status P Date 2008-10-23 Cont ID  
Sent By mwennerg Date 2008-10-23 Time 11:28 Rev Time 0.00
Received By mwennerg Date 2008-10-23 Time 11:28 Sent To  
Notes
2008-10-23 11:29:12REVISION DATED 8/29/08.

Review Stop FIRE FIRE DEPARTMENT
Rev No 15 Status F Date 2008-05-20 Cont ID  
Sent By mawillia Date 2008-05-20 Time 16:40 Rev Time 0.00
Received By mawillia Date 2008-05-20 Time 16:25 Sent To  
Notes
2008-05-20 16:40:07*****UNSAT*****
  
  
 **IN REFERENCE TO THE FM-200 SYSTEM ALTERNATE NOT TO BE
 UTILIZED, PLEASE DELETE REFERENCE TO THIS SYSTEM AS
 INDICATED ON SHEET FP1.07 (LEVEL 3 - AREA B)
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status N Date 2007-11-09 Cont ID  
Sent By mwennerg Date 2007-11-09 Time 10:33 Rev Time 0.00
Received By mwennerg Date 2007-11-09 Time 10:33 Sent To  
Notes
2007-11-09 10:34:33REVISIONS DON'T APPEAR TO IMPACT LIFE SAFETY OR FIRE
 PROTECTION SYSTEMS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status F Date 2007-10-31 Cont ID  
Sent By mawillia Date 2007-10-31 Time 19:24 Rev Time 0.00
Received By mawillia Date 2007-10-25 Time 18:08 Sent To  
Notes
2007-10-31 19:24:10*****DENIED*****
  
  
 1.SHEET A1.03, A1.05,PROVIDE PRESCRIPTIVE STRENGHTS
 FOR THE NEW HANDRAILS.
  
 2.SHEET A1.03, PROVIDE SPECS AND PRESCRIPTIVE
 STRENGHTS FOR THE ORNAMENTAL GLASS RAILING.
  
 3.NO MENTION OF THE DIMENSIONS OF THE NEW RECESSED
 ADDRESS NUMBERS ON A3.02 SHEET.AS PER WEST PALM BEACH
 CODE,ADDRESS NUMBERS SHALL BE NO LESS THAN 6" IN
 HEIGHT AND NO LESS THAN 1" IN WIDTH AS PER WEST PALM
 BEACH CODE
  
 4.ON SHEET A6.01, A6.03, A6.05 IN THE CEILING LEGEND,
 A SYMBOL IS SHOWN FOR A SMOKE OR HEAT DETECTOR. SPECIFY
 THE TYPE OF DEVICE TO BE USED AS PER NFPA 72 - 2002
 EDITION.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status F Date 2007-10-23 Cont ID  
Sent By mwennerg Date 2007-10-23 Time 09:45 Rev Time 0.00
Received By mwennerg Date 2007-10-23 Time 09:45 Sent To  
Notes
2007-10-23 09:52:32***DENIED***
  
 PLANS INDICATE THE PROPOSED INSTALLATION OF AN FM-200
 FIRE SUPPRESSION SYSTEM TO AREAS ON THE THIRD LEVEL.
 PLEASE NOTE THAT REFERENCED SYSTEM SHALL BE USED IN
 ADDITION TO A COMPLETE WET AUTOMATIC FIRE SPRINKLER
 SYSTEM IN SAME THE AREAS AND NOT AS AN ALTERNATIVE
 METHOD ONLY. SEPARATE SHOP DRAWINGS AND PERMIT WILL BE
 REQUIRED PRIOR TO INSTALLATION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2006-12-22 Cont ID  
Sent By mawillia Date 2006-12-22 Time 10:32 Rev Time 0.00
Received By mawillia Date 2006-12-22 Time 10:32 Sent To  
Notes
2006-12-22 10:37:40*****REVISION APPROVED******
  
  
  
 RELOCATION OF FIREFIGHTER'S COMMAND PANEL(SEE
 APPROPIATE MECHANICAL PLAN SHEET)

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2006-12-19 Cont ID  
Sent By mawillia Date 2006-12-19 Time 12:26 Rev Time 0.00
Received By mawillia Date 2006-12-19 Time 12:26 Sent To  
Notes
2006-12-19 12:28:58*****REVISION APPROVED*****
  
  
  
  
 * 60 HP FIRE PUMP TO A 50 HP FIRE PUMP (SEE SHEET
 FP1.02)

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2006-11-14 Cont ID  
Sent By mawillia Date 2006-11-14 Time 12:06 Rev Time 0.00
Received By mawillia Date 2006-11-14 Time 12:06 Sent To  
Notes
2006-11-14 12:07:27*****REVISION APPROVED*****

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status N Date 2006-05-31 Cont ID  
Sent By mwennerg Date 2006-05-31 Time 14:40 Rev Time 0.00
Received By mwennerg Date 2006-05-31 Time 14:40 Sent To  
Notes
2006-05-31 00:00:00NO REVISIONS SUBMITTED FOR FIRE REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status N Date 2006-05-09 Cont ID  
Sent By mwennerg Date 2006-05-09 Time 11:21 Rev Time 0.00
Received By mwennerg Date 2006-05-09 Time 11:21 Sent To  
Notes
2006-05-09 00:00:00NO FIRE PROTECTION OR FIRE ALARM SHEETS
 SUBMITTED WITH THIS REVISION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2005-09-13 Cont ID  
Sent By mwennerg Date 2005-09-13 Time 10:29 Rev Time 0.00
Received By mwennerg Date 2005-09-13 Time 10:29 Sent To  
Notes
2005-09-13 00:00:00REVISION DATED 9/9/05
  
 EXACT LOCATION OF REMOTE FUEL FILL
 STSTION TO BE DETERMINED. MORE DETAILS
 REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-07-06 Cont ID  
Sent By mwennerg Date 2005-07-06 Time 15:48 Rev Time 0.00
Received By mwennerg Date 2005-07-06 Time 15:48 Sent To  
Notes
2005-07-06 00:00:00******APPROVED******
  
 PLEASE DISREGARD REVIEWS #3, & #4.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2005-06-28 Cont ID  
Sent By mwennerg Date 2005-06-28 Time 11:14 Rev Time 0.00
Received By mwennerg Date 2005-06-28 Time 11:21 Sent To  
Notes
2005-06-28 00:00:00****DENIED****
  
 1) PLEASE SEE FIRE REVIEW COMMENTS FROM
 LAST REVIEW. IT DOESN'T APPEAR THAT THE
 COMMENTS HAVE BEEN ADDRESSED. PLEASE
 SUBMIT YOUR RESPONSES FOR REVIEW.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2005-06-28 Cont ID  
Sent By mwennerg Date 2005-06-28 Time 11:24 Rev Time 0.00
Received By mwennerg Date 2005-06-28 Time 10:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-03-11 Cont ID  
Sent By mcarsill Date 2005-03-11 Time 12:24 Rev Time 0.00
Received By mcarsill Date 2005-03-11 Time 12:24 Sent To  
Notes
2005-03-11 00:00:001. THE EXISTING ROTUNDA BUILDING IS
 NOT EQUIPPED WITH A SMOKE MANAGEMENT
 SYSTEM AND CONTAINS AN ATRIUM. A MEETING
 WAS HELD RECENTLY TO DISCUSS THE CODE
 ISSUES AND A CONSTRUCTION BOARD OF
 ADJUSTMENT AND APPEALS CASE IS
 SCHEDULED FOR MARCH 17, 2005.
  
 2. THE PLANTING PLAN, PAGE L1.01
 MAKES REFERENCE TO A TWENTY FOOT
 WIDE FIRE CORRIDOR TO THE WEST OF
 THE PROPOSED LIBRARY. WHAT LIVE LOADS
 OF FIRE APPARATUS IS IT EXPECTED TO
 SUPPORT.
  
 3. PLEASE EXPLAIN PIVOT GATE DETAIL
 ON PAGE A1.03. WHAT PURPOSE DO THEY
 SERVE AND DO THEY CREATE ANY PROBLEMS.
  
 4. THE TWO STUDIES SUBMITTED TO THE
 CITY MAKE REFERENCE TO THE GRAND
 STAIR. IS THERE ANY POSSIBILITY THAT
 THE GRAND STAIR WOULD BE USED FOR
 EXITING OR SHOULD ALL INTERESTED
 PARTIES AGREE THAT IT WILL NOT BE
 USED FOR ANY EXITING.
  
 5. PLEASE INDICATE THAT PROPOSED
 CARD READERS WHEN INSTALLED WILL
 NOT INTERFERE WITH ANY EXIT ACCESS,
 OR EXITING.
  
 6. THE REFLECTED CEILING PLAN
 LEVEL THREE, AREA A, EAST SIDE
 APPEARS TO NEED ANOTHER EXIT SIGN.
 EXIT SIGN PLACEMENT SHALL NOT
 EXCEED 100 FEET.
  
 7. THE REQUIRED SMOKE EXHAUST SYSTEM
 SHALL BE CONNECTED TO THE GENERATOR
 SYSTEM. ALSO THE SMOKE EXHAUST SYSTEM
 FOR THE ATRIUM MUST BE PRE-TESTED AND
 WHEN TESTED WITH CITY OFFICIALS THE
 SYSTEM IS TO BE TESTED ON NORMAL AND
 ALSO ON EMERGENCY POWER.
  
 8. EXIT DOORS ARE ALSO TO BE FISH
 SCALED WHEN THE SMOKE EXHAUST SYSTEM
 IS ACTIVATED TO ENSURE THAT ALL EXIT
 DOORS CAN BE OPENED EASILY.
  
 9. PLEASE EXPLAIN FACTORY MOUNTED
 DISCONNECT SWITCH IN EXIT ACCESS AREA
 OF ROTUNDA STAIR AREA. PAGES E2.01 AND
 E2.03.
  
 10. EMERGENCY GENERATOR ROOM SHALL
 BE AT LEAST TWO HOUR FIRE RATED DUE TO
 FUEL STORAGE BELOW THE GENERATOR.
  
 11. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM AND FIRE SPRINKLER
 SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-21 Cont ID  
Sent By mcarsill Date 2004-12-21 Time 12:52 Rev Time 0.00
Received By mcarsill Date 2004-12-21 Time 07:22 Sent To  
Notes
2004-12-21 00:00:001. ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. WHAT HAPPENS WHEN THE EXISTING
 METAL STAIRS ARE REMOVED. WHAT AFFECT
 WILL IT HAVE.
  
 3. ELECTRONIC SWITCHES, CHAIN AND
 LOCKS REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 4. THE 20 FOOT WIDE FIRE CORRIDOR
 LOCATED ALONG THE WEST SIDE OF THE
 BUILDING IS EXPECTED TO SUPPORT WHAT
 WEIGHT.
  
 5. ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY IN 6" LETTERS.
  
 6. ALL NEW STAIRS AND RAMPS SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 7. ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 8. THE THREE STORY BUILDING PLANNED
 FOR DEMOLITION IS PRESENTLY USED FOR
 WHAT PURPOSE.
  
 9.WHAT FIRE AND LIFE SAFETY SYSTEMS
 PRESENTLY EXISTS IN THE PHASE II
 BUILDING.
  
 10. NO CUTTING OR WELDING OPERATIONS
 ARE
 TO BE PERFORMED UNTIL APPROVAL OF THE
 FIRE PREVENTION BUREAU IS OBTAINED AND
 COMPLIANCE WITH NFPA 51B, THE
 STANDARD FOR CUTTING AND WELDING
 OPERATIONS IS ACHIEVED.
  
 11. TACTILE SIGNAGE IS REQUIRED AT ALL
 EXIT STAIRS.
  
 12. THE ROOM CONTAINING THE GENERATOR
 MUST BE AT LEAST TWO HOUR FIRE RATED
 IF THE ROOM IS TO CONTAIN DIESEL
 FUEL. OPENING PROTECTIVES WILL BE
 REQUIRED.
  
 13. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 14. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 15. THE BUILDING MAY BE LOCATED IN THE
 CITY FIRE LIMITS. CERTAIN RESTRICTIONS
 MAY APPLY. PLEASE SEE APPENDIX F,
 LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING
 CODE.
  
 16. PLEASE EXPLAIN CARD READERS NOTED
 ON DOOR SCHEDULE AND INSIDE STAIRS.
 PLEASE EXPLAIN WHAT INFLUENCE THEY
 HAVE ON ANY EXITING.
  
 17. THE REQUIRED FIRE ALARM SYSTEM
 SHALL
 BE MONITORED BY A UL LISTED CENTRAL
 STATION LISTED FOR CENTRAL STATION
 SERVICE.
  
 18. KNOX-BOX LOCKING CAPS WILL BE
 REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTION.
  
 19. BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF 6" HIGH NUMBERS
 ARE REQUIRED.
  
 20. NO NON FIRE RATED MATERIALS SHALL
 BE USED AS TEMPORARY DUSTPROOF
 PARTITIONS FOR THE PHASE II
 CONSTRUCTION.
  
 21. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH
 REQUIREMENTS FOR THE GLASS RAILING.
  
 22. NO COMBUSTIBLES ALLOWED IN ANY
 RETURN AIR PLENUMS.
  
 23. PLEASE EXPLAIN MAIN INGRESS/EGRESS
 FACILITIES FOR THE BUILDING. PLEASE
 EXPLAIN HOW THE 50 % OF OCCUPANT
 LOAD EXIT DISCHARGE REQUIREMENTS IS
 BEING MET.
  
 24. A TABLE AND CHAIRS ARE NOTED
 DIRECTLY IN FRONT OF THE ATRIUM STAIR.
  
 25. PLEASE INDICATE LOCATION OF THE
 FIREFIGHTERS SMOKE CONTROL PANEL FOR
 THE ATRIUM SYSTEM. HOW WILL THE
 ATRIUM SYSTEM BE TESTED.
  
 26. THE HVAC DESIGN REQUIRES BOX ON
 PAGE M0.01 IS BLANK.
  
 27. THE ATRIUM SHALL MEET THE
 REQUIREMENTS OF THE LIFE SAFETY CODE,
 101, 2000 EDITION, SECTION 8.2.5.6.
 PLEASE EXPLAIN HOW THE CODE OR
 THE EXCEPTIONS ARE BEING MET.
  
 28. THE MANUAL CONTROLS FOR THE ATRIUM
 SHALL DISPLAY A GRAPHIC OF THE
 BUILDING.
 HOA SWITCHES ONLY WILL NOT BE ALLOWED.
 A GRAPHIC REPRESENTATION OF THE
 BUILDING SHALL BE PROVIDED.
  
 29. EXIT SIGN PLACEMENT SHALL
 NOT EXCEED 100 FEET.
  
 30. PLEASE VERIFY ALL DOOR SWINGS.
  
 31. PANIC HARDWARE REQUIRED ON EXIT
 DOORS.
  
 32. ALL SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF THREE FEET
 FROM ALL AIR CONDITIONER DIFFUSERS.
  
 33. PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE OF THE FIRE ALARM
 SYSTEM WILL SAY.
  
 34. WHAT WILL THE SMOKE EXHAUST PANEL
 LOOK LIKE.
  
 35. ACTIVATION OF DUCT SMOKE DETECTORS
 SHALL CAUSE THE FIRE ALARM SYSTEM TO
 ACTIVATE.
  
 36. NO PENETRATIONS PERMITTED WITHIN
 ANY REQUIRED EXIT STAIR.
  
 37. WHAT IS THE PROPOSED HEIGHT OF
 THE COLLECTION STACK RACKS.
  
 38. ARE ANY EDUCATIONAL CLASSES OR
 ACTIVITIES PLANNED FOR INSIDE THE
 BUILDING.
  
 39. ALL EXTERIOR STAIRS SHALL BE
 SLIP RESISTANT.
  
 40. THE EXITING RATIONALE SHALL BE
 FURTHER EXPLAINED.
  
 41. THE FLOOR PLANS SHOULD BE MADE
 LARGER FOR IDENTIFICATION PURPOSES.
  
 42. THE NEW PHASE ONE SQUARE FOOTAGE
 WHEN ADDED TOGETHER HAS A MATH
 ERROR. ALSO THE GROSS AREA NUMBER
 APPEARS INCORRECT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 154 Status N Date 2009-09-29 Cont ID  
Sent By shill Date 2009-09-29 Time 12:48 Rev Time 0.00
Received By shill Date 2009-09-29 Time 12:48 Sent To  
Notes
2009-09-29 12:48:49REVISED LANDSCAPE PLAN TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 153 Status N Date 2009-08-31 Cont ID  
Sent By lmartine Date 2009-08-31 Time 14:37 Rev Time 0.00
Received By lmartine Date 2009-08-31 Time 14:37 Sent To  
Notes
2009-08-31 14:38:39IN ZONING

Review Stop I INCOMING/PROCESSING
Rev No 152 Status N Date 2009-08-25 Cont ID  
Sent By lmartine Date 2009-08-25 Time 16:22 Rev Time 0.00
Received By lmartine Date 2009-08-25 Time 16:21 Sent To  
Notes
2009-08-25 16:22:12TEST AN D BALANCE REPORT, GAVE TO HAROLD MOSER

Review Stop I INCOMING/PROCESSING
Rev No 151 Status N Date 2009-07-22 Cont ID  
Sent By lmartine Date 2009-07-22 Time 14:43 Rev Time 0.00
Received By lmartine Date 2009-07-22 Time 14:42 Sent To  
Notes
2009-07-22 14:43:34RFI #209
2009-07-22 14:42:49GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 150 Status N Date 2009-07-16 Cont ID  
Sent By rmcdouga Date 2009-07-15 Time 11:32 Rev Time 0.00
Received By rmcdouga Date 2009-07-15 Time 11:32 Sent To  
Notes
2009-07-16 11:33:02ELECT. REV. SENT TO DPALMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 149 Status N Date 2009-06-12 Cont ID  
Sent By kstevens Date 2009-06-12 Time 11:14 Rev Time 0.00
Received By kstevens Date 2009-06-12 Time 11:14 Sent To  
Notes
2009-06-12 11:14:50SENT REVISION TO DVP DESK

Review Stop I INCOMING/PROCESSING
Rev No 148 Status N Date 2009-06-10 Cont ID  
Sent By dpalmer Date 2009-06-10 Time 08:19 Rev Time 0.00
Received By dpalmer Date 2009-06-10 Time 08:19 Sent To B
Notes
2009-06-10 08:21:59TO JW

Review Stop I INCOMING/PROCESSING
Rev No 147 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rmcdouga Date 2009-06-03 Time 14:10 Sent To  
Notes
2009-06-04 14:11:25REVISION TO D PALMER

Review Stop I INCOMING/PROCESSING
Rev No 146 Status N Date 2009-06-02 Cont ID  
Sent By btrobaug Date 2009-06-02 Time 15:15 Rev Time 0.00
Received By btrobaug Date 2009-06-02 Time 15:15 Sent To B
Notes
2009-06-02 15:15:39TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 145 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2009-05-26 Time 11:16 Sent To  
Notes
2009-05-26 11:17:08TO DEWEY'S DESK, ELECTRICAL SHEETS ONLY./WRT

Review Stop I INCOMING/PROCESSING
Rev No 144 Status N Date 2009-05-14 Cont ID  
Sent By shill Date 2009-05-14 Time 12:03 Rev Time 0.00
Received By shill Date 2009-05-14 Time 12:03 Sent To  
Notes
2009-05-14 12:04:01TO COMMERCIAL BOARD #24
  

Review Stop I INCOMING/PROCESSING
Rev No 143 Status N Date 2009-04-30 Cont ID  
Sent By rregueir Date 2009-04-30 Time 16:05 Rev Time 0.00
Received By rregueir Date 2009-04-30 Time 16:04 Sent To E
Notes
2009-04-30 16:04:57LOW VOLTAGE REVISIONS SENT TO DVP DESK

Review Stop I INCOMING/PROCESSING
Rev No 142 Status N Date 2009-04-10 Cont ID  
Sent By adarroug Date 2009-04-10 Time 16:29 Rev Time 0.00
Received By adarroug Date 2009-04-10 Time 16:29 Sent To  
Notes
2009-04-10 16:29:31TO "C19"

Review Stop I INCOMING/PROCESSING
Rev No 141 Status N Date 2009-03-31 Cont ID  
Sent By adarroug Date 2009-03-31 Time 09:26 Rev Time 0.00
Received By adarroug Date 2009-03-31 Time 09:26 Sent To P
Notes
2009-03-31 09:26:26TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 140 Status N Date 2009-03-27 Cont ID  
Sent By adarroug Date 2009-03-27 Time 14:06 Rev Time 0.00
Received By adarroug Date 2009-03-27 Time 14:06 Sent To  
Notes
2009-03-27 14:07:06TO IN-BOX "C12"

Review Stop I INCOMING/PROCESSING
Rev No 139 Status N Date 2009-03-27 Cont ID  
Sent By adarroug Date 2009-03-27 Time 11:00 Rev Time 0.00
Received By adarroug Date 2009-03-27 Time 11:00 Sent To B
Notes
2009-03-27 11:00:26TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 138 Status N Date 2009-03-12 Cont ID  
Sent By shill Date 2009-03-12 Time 09:46 Rev Time 0.00
Received By shill Date 2009-03-12 Time 09:46 Sent To B
Notes
2009-03-12 09:46:53TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 137 Status N Date 2009-03-10 Cont ID  
Sent By adarroug Date 2009-03-10 Time 14:26 Rev Time 0.00
Received By adarroug Date 2009-03-10 Time 14:26 Sent To  
Notes
2009-03-10 14:38:59TO "COMM" BD#16

Review Stop I INCOMING/PROCESSING
Rev No 136 Status N Date 2009-02-27 Cont ID  
Sent By adarroug Date 2009-02-27 Time 09:52 Rev Time 0.00
Received By adarroug Date 2009-02-27 Time 09:52 Sent To B
Notes
2009-02-27 09:52:47TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 135 Status N Date 2009-02-27 Cont ID  
Sent By adarroug Date 2009-02-27 Time 09:16 Rev Time 0.00
Received By adarroug Date 2009-02-27 Time 09:15 Sent To B
Notes
2009-02-27 09:16:21TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 134 Status N Date 2009-02-25 Cont ID  
Sent By adarroug Date 2009-02-25 Time 16:07 Rev Time 0.00
Received By adarroug Date 2009-02-25 Time 16:07 Sent To B
Notes
2009-02-25 16:08:20TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 133 Status N Date 2009-02-24 Cont ID  
Sent By adarroug Date 2009-02-24 Time 13:30 Rev Time 0.00
Received By adarroug Date 2009-02-24 Time 13:30 Sent To P
Notes
2009-02-24 13:31:05TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 132 Status N Date 2009-02-24 Cont ID  
Sent By adarroug Date 2009-02-24 Time 13:28 Rev Time 0.00
Received By adarroug Date 2009-02-24 Time 13:28 Sent To M
Notes
2009-02-24 13:28:27TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 131 Status N Date 2009-02-12 Cont ID  
Sent By adarroug Date 2009-02-12 Time 09:07 Rev Time 0.00
Received By adarroug Date 2009-02-12 Time 09:06 Sent To P
Notes
2009-02-12 09:07:32TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 130 Status N Date 2009-02-04 Cont ID  
Sent By adarroug Date 2009-02-04 Time 15:42 Rev Time 0.00
Received By adarroug Date 2009-02-04 Time 15:41 Sent To B
Notes
2009-02-04 15:42:17TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 129 Status N Date 2009-01-29 Cont ID  
Sent By adarroug Date 2009-01-29 Time 16:20 Rev Time 0.00
Received By adarroug Date 2009-01-29 Time 16:20 Sent To P
Notes
2009-01-29 16:20:57TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 128 Status N Date 2009-01-06 Cont ID  
Sent By adarroug Date 2009-01-06 Time 15:31 Rev Time 0.00
Received By adarroug Date 2009-01-06 Time 15:31 Sent To B
Notes
2009-01-06 15:31:36TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 127 Status N Date 2009-01-06 Cont ID  
Sent By adarroug Date 2009-01-06 Time 14:39 Rev Time 0.00
Received By adarroug Date 2009-01-06 Time 14:39 Sent To B
Notes
2009-01-06 14:40:23TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 126 Status N Date 2009-01-06 Cont ID  
Sent By adarroug Date 2009-01-06 Time 14:25 Rev Time 0.00
Received By adarroug Date 2009-01-06 Time 14:25 Sent To  
Notes
2009-01-06 14:27:35TO "COMM" BD#47

Review Stop I INCOMING/PROCESSING
Rev No 125 Status N Date 2008-12-17 Cont ID  
Sent By adarroug Date 2008-12-17 Time 13:01 Rev Time 0.00
Received By adarroug Date 2008-12-17 Time 13:01 Sent To B
Notes
2008-12-17 13:02:02TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 124 Status N Date 2008-12-08 Cont ID  
Sent By adarroug Date 2008-12-08 Time 09:51 Rev Time 0.00
Received By adarroug Date 2008-12-08 Time 09:51 Sent To  
Notes
2008-12-08 09:51:21TO "COMM" BD#36

Review Stop I INCOMING/PROCESSING
Rev No 123 Status N Date 2008-12-05 Cont ID  
Sent By adarroug Date 2008-12-05 Time 16:07 Rev Time 0.00
Received By adarroug Date 2008-12-05 Time 16:07 Sent To B
Notes
2008-12-05 16:07:51TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 122 Status N Date 2008-11-18 Cont ID  
Sent By adarroug Date 2008-11-18 Time 11:35 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 11:35 Sent To  
Notes
2008-11-18 11:38:22TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 121 Status N Date 2008-11-05 Cont ID  
Sent By adarroug Date 2008-11-05 Time 08:41 Rev Time 0.00
Received By adarroug Date 2008-11-05 Time 08:41 Sent To B
Notes
2008-11-05 08:44:02TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 120 Status N Date 2008-10-30 Cont ID  
Sent By adarroug Date 2008-10-30 Time 16:00 Rev Time 0.00
Received By adarroug Date 2008-10-30 Time 16:00 Sent To B
Notes
2008-10-30 16:01:21TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 119 Status N Date 2008-10-07 Cont ID  
Sent By adarroug Date 2008-10-07 Time 16:45 Rev Time 0.00
Received By adarroug Date 2008-10-07 Time 16:45 Sent To B
Notes
2008-10-07 16:46:01TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 118 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 11:17 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 11:17 Sent To  
Notes
2008-09-22 11:29:10TO "COMM" BD#34

Review Stop I INCOMING/PROCESSING
Rev No 117 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 09:42 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 09:42 Sent To B
Notes
2008-09-22 09:42:56TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 116 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 15:57 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 15:57 Sent To M
Notes
2008-08-28 16:10:20TO "MECH" TOM G.

Review Stop I INCOMING/PROCESSING
Rev No 115 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 16:13 Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 16:13 Sent To B
Notes
2008-08-26 16:14:24SUBMITTALS TO "BUILD" JIM W.

Review Stop I INCOMING/PROCESSING
Rev No 114 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 12:15 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 12:15 Sent To M
Notes
2008-08-21 12:18:05TO "M"BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 113 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 11:41 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 11:41 Sent To B
Notes
2008-08-21 11:41:24TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 112 Status N Date 2008-08-12 Cont ID  
Sent By adarroug Date 2008-08-12 Time 15:42 Rev Time 0.00
Received By adarroug Date 2008-08-12 Time 15:41 Sent To B
Notes
2008-08-12 15:42:34TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 111 Status N Date 2008-08-07 Cont ID  
Sent By shill Date 2008-08-07 Time 14:42 Rev Time 0.00
Received By shill Date 2008-08-07 Time 14:42 Sent To P
Notes
2008-08-07 14:43:04TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 110 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 08:50 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 08:50 Sent To P
Notes
2008-07-17 08:50:49TO "P" BOX/ 2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 109 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 08:42 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 08:42 Sent To E
Notes
2008-07-17 08:42:56TO "ENG" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 108 Status N Date 2008-07-16 Cont ID  
Sent By adarroug Date 2008-07-16 Time 10:57 Rev Time 0.00
Received By adarroug Date 2008-07-16 Time 10:57 Sent To P
Notes
2008-07-16 10:58:05TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 107 Status N Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-07-01 Time 11:47 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 11:47 Sent To B
Notes
2008-07-01 11:49:01TO "JWITMER" DESK W/SUBMITTAL FROM 6/27/08

Review Stop I INCOMING/PROCESSING
Rev No 106 Status N Date 2008-06-30 Cont ID  
Sent By adarroug Date 2008-06-30 Time 11:35 Rev Time 0.00
Received By adarroug Date 2008-06-30 Time 11:35 Sent To B
Notes
2008-06-30 11:36:18TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 105 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 08:15 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 08:15 Sent To B
Notes
2008-06-17 08:16:16TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 104 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 16:43 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 16:43 Sent To B
Notes
2008-06-16 16:45:30TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 103 Status N Date 2008-06-09 Cont ID  
Sent By adarroug Date 2008-06-09 Time 16:56 Rev Time 0.00
Received By adarroug Date 2008-06-09 Time 16:56 Sent To E
Notes
2008-06-09 16:56:31TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 102 Status N Date 2008-06-09 Cont ID  
Sent By adarroug Date 2008-06-09 Time 16:38 Rev Time 0.00
Received By adarroug Date 2008-06-09 Time 16:38 Sent To B
Notes
2008-06-09 16:39:14TO "JWITMER" DESK/ 2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 101 Status N Date 2008-06-02 Cont ID  
Sent By adarroug Date 2008-06-02 Time 08:57 Rev Time 0.00
Received By adarroug Date 2008-06-02 Time 08:57 Sent To  
Notes
2008-06-02 09:02:17TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 100 Status N Date 2008-06-02 Cont ID  
Sent By adarroug Date 2008-06-02 Time 08:36 Rev Time 0.00
Received By adarroug Date 2008-06-02 Time 08:36 Sent To B
Notes
2008-06-02 08:36:48TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 99 Status N Date 2008-04-23 Cont ID  
Sent By adarroug Date 2008-04-23 Time 13:47 Rev Time 0.00
Received By adarroug Date 2008-04-23 Time 13:47 Sent To B
Notes
2008-04-23 13:47:53TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 98 Status N Date 2008-04-23 Cont ID  
Sent By adarroug Date 2008-04-23 Time 13:40 Rev Time 0.00
Received By adarroug Date 2008-04-23 Time 13:40 Sent To B
Notes
2008-04-23 13:40:37TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 97 Status N Date 2008-04-23 Cont ID  
Sent By adarroug Date 2008-04-23 Time 13:21 Rev Time 0.00
Received By adarroug Date 2008-04-23 Time 13:21 Sent To  
Notes
2008-04-23 13:23:29TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 96 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 11:45 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 11:45 Sent To  
Notes
2008-04-17 11:45:57TO "COMM" BD#45

Review Stop I INCOMING/PROCESSING
Rev No 95 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 09:43 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 09:43 Sent To B
Notes
2008-04-17 09:43:20TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 94 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 08:23 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 08:23 Sent To B
Notes
2008-02-29 08:23:32TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 93 Status N Date 2008-01-10 Cont ID  
Sent By spalmer Date 2008-01-10 Time 08:59 Rev Time 0.00
Received By spalmer Date 2008-01-10 Time 08:59 Sent To  
Notes
2008-01-10 09:00:06TO JIM WITMERS DESK

Review Stop I INCOMING/PROCESSING
Rev No 92 Status N Date 2007-12-26 Cont ID  
Sent By spalmer Date 2007-12-26 Time 15:26 Rev Time 0.00
Received By spalmer Date 2007-12-26 Time 15:26 Sent To B
Notes
2007-12-26 15:27:22TO JIM WITMERS DESK (3 REVISIONS)

Review Stop I INCOMING/PROCESSING
Rev No 91 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 11:38 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 11:38 Sent To  
Notes
2007-10-25 15:33:48TO "COMM" BD#47
2007-10-03 11:39:11WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 90 Status N Date 2007-10-02 Cont ID  
Sent By adarroug Date 2007-10-02 Time 12:04 Rev Time 0.00
Received By adarroug Date 2007-10-02 Time 12:04 Sent To ENG
Notes
2007-10-02 12:05:13TO "ENG" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 89 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 10:20 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 10:20 Sent To  
Notes
2007-09-25 12:34:03TO "COMM" BD#13
2007-09-05 10:21:02WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 88 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 10:05 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 10:05 Sent To  
Notes
2007-09-27 15:26:51TO "COMM" BD#16
2007-09-05 10:06:03WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 87 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 09:00 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 09:00 Sent To ENG
Notes
2007-09-05 09:00:26TO "ENG" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 86 Status N Date 2007-05-31 Cont ID  
Sent By adarroug Date 2007-05-31 Time 15:08 Rev Time 0.00
Received By adarroug Date 2007-05-31 Time 15:08 Sent To E
Notes
2007-05-31 15:09:08TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 85 Status N Date 2007-05-31 Cont ID  
Sent By adarroug Date 2007-05-31 Time 15:06 Rev Time 0.00
Received By adarroug Date 2007-05-31 Time 15:06 Sent To E
Notes
2007-05-31 15:07:21TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 84 Status N Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 10:51 Rev Time 0.00
Received By shill Date 2007-05-03 Time 10:51 Sent To  
Notes
2007-05-10 09:30:29TO "COMM" BD#61
2007-05-03 10:52:01WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 83 Status N Date 2007-01-29 Cont ID  
Sent By adarroug Date 2007-01-29 Time 18:10 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 18:10 Sent To P
Notes
2007-01-29 18:10:33TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 82 Status N Date 2007-01-29 Cont ID  
Sent By adarroug Date 2007-01-29 Time 08:28 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 08:28 Sent To B
Notes
2007-01-29 08:29:19TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 81 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 09:49 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 09:49 Sent To E
Notes
2007-01-24 09:50:17TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 80 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 09:46 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 09:46 Sent To B
Notes
2007-01-24 09:47:52TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 79 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 15:28 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 15:28 Sent To E
Notes
2007-01-20 15:28:44TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 78 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 14:46 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 14:46 Sent To P
Notes
2007-01-20 14:46:56TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 77 Status N Date 2006-12-11 Cont ID  
Sent By adarroug Date 2006-12-11 Time 10:07 Rev Time 0.00
Received By adarroug Date 2006-12-11 Time 10:07 Sent To M
Notes
2006-12-11 10:09:03TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 11:49 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 11:49 Sent To FIRE
Notes
2006-12-06 11:50:07TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 15:51 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 15:49 Sent To E
Notes
2006-12-05 15:50:10TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 74 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 13:33 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 13:33 Sent To M
Notes
2006-12-04 13:34:15TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 73 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 13:32 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 13:32 Sent To FIRE
Notes
2006-12-04 13:32:44TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 13:31 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 13:31 Sent To E
Notes
2006-12-04 13:31:43TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 17:44 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 17:44 Sent To E
Notes
2006-11-29 17:45:00SENT TO DEWEY PALMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 08:51 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 08:51 Sent To M
Notes
2006-11-17 08:51:54TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 08:49 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 08:49 Sent To E
Notes
2006-11-17 08:50:21TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 68 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 16:02 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 16:02 Sent To E
Notes
2006-11-08 16:02:22TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 10:14 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 10:14 Sent To M
Notes
2006-11-07 10:14:23TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 09:51 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 09:51 Sent To E
Notes
2006-11-07 09:51:38TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2006-10-26 Cont ID  
Sent By adarroug Date 2006-10-26 Time 16:10 Rev Time 0.00
Received By adarroug Date 2006-10-26 Time 16:10 Sent To E
Notes
2006-10-26 16:11:12TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 08:31 Rev Time 0.00
Received By adarroug Date 2006-10-18 Time 08:31 Sent To M
Notes
2006-10-18 08:32:23TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 18:02 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 18:02 Sent To E
Notes
2006-10-14 18:02:25TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2006-09-27 Cont ID  
Sent By adarroug Date 2006-09-27 Time 16:20 Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 16:20 Sent To  
Notes
2006-10-13 15:00:47TO "COMM" BD#58
2006-09-27 00:00:00WAITING FOR "COMM" BD-"ELEC" AND "MECH"
 REV

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2006-09-27 Cont ID  
Sent By adarroug Date 2006-09-27 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 16:19 Sent To E
Notes
2006-09-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2006-09-27 Cont ID  
Sent By adarroug Date 2006-09-27 Time 16:06 Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 16:06 Sent To B
Notes
2006-09-27 00:00:00TO "JWITMER" DESK/2 REV

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2006-09-27 Cont ID  
Sent By adarroug Date 2006-09-27 Time 15:40 Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 15:40 Sent To E
Notes
2006-09-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2006-09-27 Cont ID  
Sent By adarroug Date 2006-09-27 Time 15:38 Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 15:38 Sent To FIRE
Notes
2006-09-27 00:00:00TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 10:42 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 10:42 Sent To E
Notes
2006-09-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 10:39 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 10:39 Sent To M
Notes
2006-09-12 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 11:26 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 11:26 Sent To B
Notes
2006-09-08 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2006-09-07 Cont ID  
Sent By adarroug Date 2006-09-07 Time 13:19 Rev Time 0.00
Received By adarroug Date 2006-09-07 Time 13:19 Sent To B
Notes
2006-09-07 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2006-08-21 Cont ID  
Sent By adarroug Date 2006-08-21 Time 11:07 Rev Time 0.00
Received By adarroug Date 2006-08-21 Time 11:07 Sent To B
Notes
2006-08-21 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2006-08-21 Cont ID  
Sent By adarroug Date 2006-08-21 Time 10:46 Rev Time 0.00
Received By adarroug Date 2006-08-21 Time 10:46 Sent To  
Notes
2006-09-07 00:00:00TO "BOB"#7
2006-08-21 00:00:00WAITING FOR "BOB"-REV

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2006-08-17 Cont ID  
Sent By adarroug Date 2006-08-17 Time 11:36 Rev Time 0.00
Received By adarroug Date 2006-08-17 Time 11:36 Sent To P
Notes
2006-08-17 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2006-08-17 Cont ID  
Sent By adarroug Date 2006-08-17 Time 11:31 Rev Time 0.00
Received By adarroug Date 2006-08-17 Time 11:31 Sent To B
Notes
2006-08-17 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 17:07 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 17:06 Sent To E
Notes
2006-08-08 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 17:50 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 17:49 Sent To P
Notes
2006-08-02 00:00:00SENT TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 17:43 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 17:43 Sent To B
Notes
2006-08-02 00:00:00SENT TO" JWHITMER" DESK/ 2 SUBS

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 11:46 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 11:46 Sent To B
Notes
2006-07-27 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 11:43 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 11:43 Sent To E
Notes
2006-07-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 17:51 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 17:51 Sent To B
Notes
2006-07-14 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 17:49 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 17:49 Sent To  
Notes
2006-07-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 15:45 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 15:45 Sent To E
Notes
2006-07-14 00:00:00TO "DPALMER" DESK/2 REV

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 15:40 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 15:40 Sent To M
Notes
2006-07-14 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 11:01 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 11:00 Sent To B
Notes
2006-06-22 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 09:31 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 09:31 Sent To B
Notes
2006-06-22 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 16:51 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 16:51 Sent To M
Notes
2006-06-21 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 16:45 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 16:45 Sent To E
Notes
2006-06-21 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 16:41 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 16:41 Sent To B
Notes
2006-06-21 00:00:00TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 15:52 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 15:52 Sent To B
Notes
2006-06-12 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 10:25 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 10:25 Sent To FIRE
Notes
2006-05-26 00:00:00TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 09:20 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 09:20 Sent To M
Notes
2006-05-02 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 17:15 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 17:15 Sent To E
Notes
2006-05-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 17:10 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 17:10 Sent To B
Notes
2006-05-01 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 17:03 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 17:03 Sent To B
Notes
2006-05-01 00:00:00TO "JWITMER' DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-04-18 Time 15:02 Rev Time 0.00
Received By adarroug Date 2006-04-18 Time 15:02 Sent To B
Notes
2006-04-18 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-04-18 Time 10:03 Rev Time 0.00
Received By adarroug Date 2006-04-18 Time 10:03 Sent To E
Notes
2006-04-18 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-04-18 Time 10:01 Rev Time 0.00
Received By adarroug Date 2006-04-18 Time 10:01 Sent To E
Notes
2006-04-18 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-04-18 Time 09:47 Rev Time 0.00
Received By adarroug Date 2006-04-18 Time 09:47 Sent To  
Notes
2006-05-04 00:00:00TO "COMM" BD#11-REV
2006-04-18 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2006-03-30 Cont ID  
Sent By adarroug Date 2006-03-30 Time 13:04 Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 13:04 Sent To B
Notes
2006-03-30 00:00:00TO "JWITMER" DESK/2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2006-03-30 Cont ID  
Sent By adarroug Date 2006-03-30 Time 13:02 Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 13:02 Sent To E
Notes
2006-03-30 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2006-03-30 Cont ID  
Sent By adarroug Date 2006-03-30 Time 12:48 Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 12:48 Sent To  
Notes
2006-03-30 00:00:00TO "BOB"#2-REV

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2006-03-30 Cont ID  
Sent By adarroug Date 2006-03-30 Time 12:14 Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 12:14 Sent To E
Notes
2006-03-30 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 15:34 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 15:34 Sent To E
Notes
2006-03-21 00:00:00REV TO DP'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 15:33 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 15:33 Sent To  
Notes
2006-03-21 00:00:00WAITING FOR COMM BAORD.

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 15:29 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 15:29 Sent To M
Notes
2006-03-21 00:00:00IN MECH INBOX

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 12:57 Rev Time 0.00
Received By dpalmer Date 2006-03-17 Time 12:57 Sent To  
Notes
2006-04-11 00:00:00TO "COMM" BD#62--2 REVISIONS
2006-03-21 00:00:00WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2006-02-17 Cont ID  
Sent By adarroug Date 2006-02-17 Time 08:26 Rev Time 0.00
Received By adarroug Date 2006-02-17 Time 08:26 Sent To E
Notes
2006-02-17 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-01-30 Cont ID  
Sent By adarroug Date 2006-01-30 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-01-30 Time 16:19 Sent To M
Notes
2006-01-30 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-01-26 Cont ID  
Sent By adarroug Date 2006-01-26 Time 14:37 Rev Time 0.00
Received By adarroug Date 2006-01-26 Time 14:37 Sent To P
Notes
2006-01-26 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-01-23 Cont ID  
Sent By adarroug Date 2006-01-23 Time 14:44 Rev Time 0.00
Received By adarroug Date 2006-01-23 Time 14:44 Sent To E
Notes
2006-01-23 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-01-06 Cont ID  
Sent By adarroug Date 2006-01-06 Time 10:05 Rev Time 0.00
Received By adarroug Date 2006-01-06 Time 10:04 Sent To B
Notes
2006-01-06 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-12-13 Cont ID  
Sent By adarroug Date 2005-12-13 Time 18:09 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 18:09 Sent To B
Notes
2005-12-13 00:00:00TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 10:51 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 10:51 Sent To B
Notes
2005-12-10 00:00:00TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-11-23 Cont ID  
Sent By adarroug Date 2005-11-23 Time 16:09 Rev Time 0.00
Received By adarroug Date 2005-11-23 Time 16:09 Sent To B
Notes
2005-11-23 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 11:00 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 11:00 Sent To B
Notes
2005-10-14 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 17:12 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 17:12 Sent To B
Notes
2005-10-05 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 18:26 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 18:26 Sent To B
Notes
2005-09-01 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 11:38 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 11:38 Sent To B
Notes
2005-08-16 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-15 Cont ID  
Sent By adarroug Date 2005-08-15 Time 14:15 Rev Time 0.00
Received By adarroug Date 2005-08-15 Time 14:15 Sent To  
Notes
2005-08-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 10:16 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 10:16 Sent To  
Notes
2005-08-08 00:00:00TO "COMM" BD#36

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-07 Cont ID  
Sent By shill Date 2005-06-07 Time 14:03 Rev Time 0.00
Received By shill Date 2005-06-07 Time 14:03 Sent To  
Notes
2005-06-07 00:00:00COMM BOARD #42
 1 BOX SPECS, 7 ROLLS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-10 Cont ID  
Sent By adarroug Date 2005-02-10 Time 15:34 Rev Time 0.00
Received By adarroug Date 2005-02-10 Time 15:34 Sent To  
Notes
2005-02-10 00:00:00TO "COMM" BD#11/COMM RACK-6ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-30 Cont ID  
Sent By mjacobs Date 2004-12-30 Time 18:42 Rev Time  
Received By kstevens Date 2004-11-22 Time 15:07 Sent To  
Notes
2004-11-22 00:00:00SENT TO "COMM BD#19. 3 ROLL PLANS ON
 RACK.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-09-30 Cont ID  
Sent By rkussner Date 2009-09-30 Time 12:15 Rev Time 0.00
Received By rkussner Date 2009-09-30 Time 12:15 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-09-02 Cont ID  
Sent By rkussner Date 2009-09-02 Time 14:07 Rev Time 0.00
Received By rkussner Date 2009-09-02 Time 14:07 Sent To  
Notes
2009-09-02 14:19:29***LANDSCAPE REIVEW FAILED***
  
 1. THE CHANGES MADE TO THE LANDSCAPE FOR THIS PHASE AND
 THE OTHER PHASES SHOWN ON THE PLAN REQUIRES A MINOR
 AMENDMENT TO THE PD PRIOR TO APPROVAL OF THIS PERMIT.
  
 2. THE SYMBOL 'RR' WAS SHOWN ON THE PLANTING PLAN SHEET
 L1.01 AND ON SHEET 2 BUT THERE IS NO REFERENCE TO THAT
 SYMBOL ON THE PLANT LIST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 34 Status P Date 2009-09-08 Cont ID  
Sent By hmoser Date 2009-09-08 Time 15:01 Rev Time 0.00
Received By hmoser Date 2009-09-08 Time 15:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 33 Status P Date 2009-06-11 Cont ID  
Sent By rregueir Date 2009-06-11 Time 10:36 Rev Time 0.00
Received By rregueir Date 2009-06-11 Time 10:07 Sent To PC
Notes
2009-06-11 10:36:42M1.01 DELTA 9. SMOKE DAMPERS SHALL BE MAXIMUM 24" FROM
 SMOKE BARRIER IN ACCORDANCE WITH NFPA 90A.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 32 Status P Date 2009-04-27 Cont ID  
Sent By rregueir Date 2009-04-27 Time 15:19 Rev Time 0.00
Received By rregueir Date 2009-04-27 Time 15:18 Sent To  
Notes
2009-04-27 15:18:58REVISED M101 AND M103.
 PROVISO:
 PIPE PENETRATION OS RATED STAIR ENCLOSURE PROHIBITED IN
 ACCORDANCE WITH 2001 FBC-B 1006.1.3.1

Review Stop M MECHANICAL (A/C)
Rev No 31 Status P Date 2009-03-30 Cont ID  
Sent By rregueir Date 2009-03-30 Time 20:40 Rev Time 0.00
Received By rregueir Date 2009-03-30 Time 20:38 Sent To  
Notes
2009-03-30 20:40:32M1.01 DELTA 7, M5.2 DELTA 4

Review Stop M MECHANICAL (A/C)
Rev No 30 Status P Date 2009-03-05 Cont ID  
Sent By rregueir Date 2009-03-05 Time 14:53 Rev Time 0.00
Received By rregueir Date 2009-03-05 Time 14:52 Sent To PC
Notes
2009-03-05 14:53:16REVISED M1.01, M1.03, M1.05, M7.03

Review Stop M MECHANICAL (A/C)
Rev No 29 Status F Date 2009-02-01 Cont ID  
Sent By rregueir Date 2009-02-01 Time 14:42 Rev Time 0.00
Received By rregueir Date 2009-02-01 Time 14:39 Sent To PC
Notes
2009-02-01 14:42:46REVIEW: PAGE M1.03 REVISION #7
 ACTION: DENIED
  
 FBC 2001 CODE FAMILY
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE TOILET EXHAUST DUCTS FROM THE 1ST FLOOR TO THE
 3RD FLOOR, AS SHOWN ON PAGES M1.03 THROUGH M1.07, SHALL
 BE IN A SHAFT ENCLOSURE IN ACCORDANCE WITH 2001 FBCM
 607.4.
  
 2. DUCT PENETRATIONS OF THE SHAFT ENCLOSURE SHALL BE
 PROTECTED WITH FIRE DAMPERS IN ACCORDANCE WITH 2001
 FBCM 607.1.2. NOTE #1 ON PAGE M1.07 REFERENCES A CODE
 SECTION (607.5.3) WHICH DOES NOT EXIST IN THE 2001
 FBCM. PLEASE PROTECT PENETRATIONS IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE 2001 FLORIDA BUILDING CODE,
 MEACHANICAL.
  
 3. PAGE M1.03 SHOWS TWO DUCT PENETRATIONS FO A RATED
 STAIR ENCLOSURE. PENETRATIONS OF STAIR ENCLOSURES FOR
 PURPOSES OTHER THAN INDEPENDENT PRESSURIZATION ARE
 PROHIBITED IN ACCORDANCE WITH 2001 FBCB 1006.1.3.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 28 Status F Date 2009-01-20 Cont ID  
Sent By rregueir Date 2009-01-20 Time 08:50 Rev Time 0.00
Received By rregueir Date 2009-01-20 Time 08:48 Sent To  
Notes
2009-01-20 08:50:45REVIEW #: REVISION 15
 ACTION: DENIED
  
 FBC 2001 CODE FAMILY
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE TOILET EXHAUST DUCTS FROM THE 1ST FLOOR TO THE
 3RD FLOOR, AS SHOWN ON PAGES M1.03 THROUGH M1.07, SHALL
 BE IN A SHAFT ENCLOSURE IN ACCORDANCE WITH 2001 FBCM
 607.4.
  
 2. DUCT PENETRATIONS OF THE SHAFT ENCLOSURE SHALL BE
 PROTECTED WITH FIRE DAMPERS IN ACCORDANCE WITH 2001
 FBCM 607.1.2. NOTE #1 ON PAGE M1.07 REFERENCES A CODE
 SECTION (607.5.3) WHICH DOES NOT EXIST IN THE 2001
 FBCM. PLEASE PROTECT PENETRATIONS IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE 2001 FLORIDA BUILDING CODE,
 MEACHANICAL.
  
 3. PAGE M1.03 SHOWS TWO DUCT PENETRATIONS FO A RATED
 STAIR ENCLOSURE. PENETRATIONS OF STAIR ENCLOSURES FOR
 PURPOSES OTHER THAN INDEPENDENT PRESSURIZATION ARE
 PROHIBITED IN ACCORDANCE WITH 2001 FBCB 1006.1.3.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 27 Status N Date 2009-01-20 Cont ID  
Sent By rregueir Date 2009-01-20 Time 08:51 Rev Time 0.00
Received By rregueir Date 2009-01-14 Time 20:06 Sent To  
Notes
2009-01-20 08:51:57REVIEW COMPLETED ON 1/20/09. SEE REVIEW FOR THAT DATE.

Review Stop M MECHANICAL (A/C)
Rev No 26 Status P Date 2008-09-04 Cont ID  
Sent By tgordon Date 2008-09-04 Time 13:48 Rev Time 1.20
Received By tgordon Date 2008-09-04 Time 13:48 Sent To  
Notes
2008-09-04 13:49:54REVISION TO MECH. PLAN M1.05 AND M7.03.

Review Stop M MECHANICAL (A/C)
Rev No 25 Status F Date 2008-09-04 Cont ID  
Sent By tgordon Date 2008-09-04 Time 10:50 Rev Time 4.00
Received By tgordon Date 2008-09-04 Time 10:50 Sent To  
Notes
2008-09-04 11:49:22PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH CITY OF WEST PALM BEACH
 AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECH. PLANS M1.01, M1.03, M1.05.
 *** DENIED ***
  
 THE FOLLOWING HAD NOT BEEN NOTICED IN PREVIOUS REVIEWS.
  
 1) PLAN M1.01 SHOWS A SUPPLY AIR DUCT AND A RETURN AIR
 TRANSFER DUCT PENETRATING THE RATED WALL TO A STAIRWAY
 ENCLOSURE (BS-3S AND BS-3N), THIS DOES NOT COMPLY WITH
 2001 FBC 1006.1.3.1. PLEASE CORRECT.
  
 2) PLAN M1.03 SHOWS A SUPPLY AIR DUCT AND A RETURN AIR
 TRANSFER DUCT PENETRATING THE RATED WALL TO A STAIRWAY
 ENCLOSURE, THIS DOES NOT COMPLY WITH 2001 FBC
 1006.1.3.1. PLEASE CORRECT.
  
 3) PLAN M1.05 SHOWS A 5" SUPPLY AIR DUCT PENETRATING A
 SMOKE BARRIER (SEE YELLOW HIGH LIGHT ON PLAN) A SMOKE
 DAMPER WILL BE REQUIRED PER 2001 FBC/M 607.3.2.
  
 4) SEE ATTACHED BUILDING REVIEW NOTES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 24 Status F Date 2008-08-22 Cont ID  
Sent By tgordon Date 2008-08-22 Time 08:21 Rev Time 0.45
Received By tgordon Date 2008-08-22 Time 08:20 Sent To  
Notes
2008-08-22 08:28:54PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE SHOP DRAWINGS SUBMITTED AC-1, AC-2, AC-3 AND
 AC-4 ARE MORE OF A REVISION AND NEED TO BE DONE BY THE
 ENGINEER, PER F.S. 471.003 (2) (H).
  
 **PLEASE BE AWARE WHEN RESUBMITTING THE SEALED
 REVISIONS THEIR WILL BE NO ADDITIONAL FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 23 Status P Date 2008-06-03 Cont ID  
Sent By tgordon Date 2008-06-03 Time 10:44 Rev Time 2.30
Received By tgordon Date 2008-06-03 Time 10:44 Sent To  
Notes
2008-06-03 10:45:30REVISION TO MECH. PLAN M1.01.

Review Stop M MECHANICAL (A/C)
Rev No 22 Status P Date 2008-04-22 Cont ID  
Sent By tgordon Date 2008-04-22 Time 14:34 Rev Time 0.45
Received By tgordon Date 2008-04-22 Time 14:34 Sent To  
Notes
2008-04-22 14:36:34REVISED MECH. PLANS WERE REVIEWED, STAMPED, AND FILED
 ON 9-28-07.

Review Stop M MECHANICAL (A/C)
Rev No 21 Status P Date 2007-09-28 Cont ID  
Sent By tgordon Date 2007-09-28 Time 16:54 Rev Time 1.30
Received By tgordon Date 2007-09-28 Time 16:54 Sent To  
Notes
2007-09-28 16:57:34REVISION TO MECH. PLANS PAGES M0.01, M1.01, M1.03,
 M1.05, M1.07, M5.0, M5.1, M5.2, M6.0, M7.01, M7.03.

Review Stop M MECHANICAL (A/C)
Rev No 20 Status P Date 2007-05-18 Cont ID  
Sent By tgordon Date 2007-05-18 Time 16:38 Rev Time 0.45
Received By tgordon Date 2007-05-18 Time 16:38 Sent To  
Notes
2007-05-18 16:42:10MECHANICAL REVISED SHOP DRAWINGS SKEM-4, SKEM-5, AND
 SKEM-6 FOR ELECTRICAL ROOMS 3A28, 2A24, AND 3A16.

Review Stop M MECHANICAL (A/C)
Rev No 19 Status P Date 2007-03-06 Cont ID  
Sent By tgordon Date 2007-03-06 Time 09:22 Rev Time 0.35
Received By tgordon Date 2007-03-06 Time 09:22 Sent To  
Notes
2007-03-06 09:25:25REVISION PAGE SKP-2
 *** PROVISO ***
 1) 2001 FBC/M 1305.6 FILL PIPING.
 A FILL PIPE SHALL TERMINATE OUTSIDE OF A BUILDING AT A
 POINT AT LEAST 2 FEET (610 MM) FROM ANY BUILDING
 OPENING AT THE SAME OR LOWER LEVEL. A FILL PIPE SHALL
 TERMINATE IN A MANNER DESIGNED TO MINIMIZE SPILLING
 WHEN THE FILLING HOSE IS DISCONNECTED. FILL OPENING
 SHALL BE EQUIPPED WITH A TIGHT METAL COVER DESIGNED TO
 DISCOURAGE TAMPERING.
 2) 2001 FBC/M 1305.7 VENT PIPING.
 LIQUID FUEL VENT PIPES SHALL TERMINATE OUTSIDE OF
 BUILDINGS AT A POINT NOT LESS THAN 2 FEET (610 MM)
 MEASURED VERTICALLY OR HORIZONTALLY FROM ANY BUILDING
 OPENING. OUTER ENDS OF VENT PIPES SHALL TERMINATE IN A
 WEATHERPROOF VENT CAP OR FITTING OR BE PROVIDED WITH A
 WEATHERPROOF HOOD. ALL VENT CAPS SHALL HAVE A MINIMUM
 FREE OPEN AREA EQUAL TO THE CROSS-SECTIONAL AREA OF THE
 VENT PIPE AND SHALL NOT EMPLOY SCREENS FINER THAN NO. 4
 MESH. VENT PIPES SHALL TERMINATE SUFFICIENTLY ABOVE THE
 GROUND TO AVOID BEING OBSTRUCTED WITH SNOW OR ICE. VENT
 PIPES FROM TANKS CONTAINING HEATERS SHALL BE EXTENDED
 TO A LOCATION WHERE OIL VAPORS DISCHARGING FROM THE
 VENT WILL BE READILY DIFFUSED. IF THE STATIC HEAD WITH
 A VENT PIPE FILLED WITH OIL EXCEEDS 10 POUNDS PER
 SQUARE INCH (PSI) (69 KPA), THE TANK SHALL BE DESIGNED
 FOR THE MAXIMUM STATIC HEAD THAT WILL BE IMPOSED.
 LIQUID FUEL VENT PIPES SHALL NOT BE CROSS CONNECTED
 WITH FILL PIPES, LINES FROM BURNERS OR OVERFLOW LINES
 FROM AUXILIARY TANKS.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 18 Status F Date 2007-02-07 Cont ID  
Sent By tgordon Date 2007-02-07 Time 09:01 Rev Time 0.25
Received By tgordon Date 2007-02-07 Time 09:01 Sent To  
Notes
2007-02-07 09:05:29REVISION FOR A/C UNIT IN ELEVATOR EQUIP. ROOM
 *** DENIED ***
 1) PLEASE SHOW A/C EQUIPMENT LISTING ON PLAN.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR A/C
 UNIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 17 Status N Date 2007-01-03 Cont ID  
Sent By pkrauss Date 2007-01-03 Time 07:57 Rev Time 0.00
Received By pkrauss Date 2007-01-03 Time 07:57 Sent To  
Notes
2007-01-03 07:58:32SUBMITTAL / LOCATION OF SMOKE EMITTOR'S /REFERENCE PLAN
 SHEET M1.02 (SKEM.7)

Review Stop M MECHANICAL (A/C)
Rev No 16 Status P Date 2006-12-21 Cont ID  
Sent By hmoser Date 2006-12-21 Time 18:01 Rev Time 0.00
Received By hmoser Date 2006-12-21 Time 18:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date 2006-12-11 Cont ID  
Sent By hmoser Date 2006-12-11 Time 16:58 Rev Time 0.00
Received By hmoser Date 2006-12-11 Time 16:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2006-11-03 Cont ID  
Sent By pkrauss Date 2006-11-03 Time 06:39 Rev Time 0.00
Received By pkrauss Date 2006-11-02 Time 14:56 Sent To  
Notes
2006-11-02 14:57:03REVISED PLAN SHEET M6.0

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2006-10-30 Cont ID  
Sent By pkrauss Date 2006-10-30 Time 12:38 Rev Time 0.00
Received By pkrauss Date 2006-10-30 Time 11:18 Sent To  
Notes
2006-10-30 14:03:34REVISED SHEETS:M1.02 ELEC RMS 1A36 & 1A19, M1.04 ELEC
 ROOM 2A24, M1.06 ELEC ROOM 3A28 & 3A16.

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2006-07-27 Cont ID  
Sent By hmoser Date 2006-07-25 Time 14:58 Rev Time 0.00
Received By hmoser Date 2006-07-27 Time 10:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2006-07-25 Cont ID  
Sent By hmoser Date 2006-07-25 Time 14:38 Rev Time 0.00
Received By hmoser Date 2006-07-25 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 10 Status N Date 2006-05-08 Cont ID  
Sent By pkrauss Date 2006-05-08 Time 07:50 Rev Time 0.00
Received By pkrauss Date 2006-05-08 Time 06:53 Sent To  
Notes
2006-05-08 00:00:00REVISION - SKM-1

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2006-05-02 Cont ID  
Sent By pkrauss Date 2006-05-02 Time 14:41 Rev Time 0.00
Received By pkrauss Date 2006-05-02 Time 10:54 Sent To  
Notes
2006-05-02 00:00:00REVISED SHEETS; M1.02, 1.04, 1.06, 1.08,
 5.1.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2006-03-30 Cont ID  
Sent By tgordon Date 2006-03-30 Time 13:50 Rev Time 0.20
Received By tgordon Date 2006-03-30 Time 13:50 Sent To  
Notes
2006-03-30 00:00:00MECH. REV. FOR FUEL STORAGE TANK VENTS.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-03-23 Cont ID  
Sent By tgordon Date 2006-03-23 Time 08:09 Rev Time 0.45
Received By tgordon Date 2006-03-23 Time 08:09 Sent To P
Notes
2006-03-23 00:00:00MECH. REV. REMOTE FUEL/SPILL CONTAINMENT
 FOR GENERATOR.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-02-14 Cont ID  
Sent By tgordon Date 2006-02-14 Time 08:10 Rev Time 0.30
Received By tgordon Date 2006-02-14 Time 08:09 Sent To  
Notes
2006-02-14 00:00:00MECH. REV. TO CHILLED WATER PIPING.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-09-13 Cont ID  
Sent By pkrauss Date 2005-09-13 Time 12:55 Rev Time 2.00
Received By pkrauss Date 2005-09-13 Time 12:54 Sent To  
Notes
2005-09-13 00:00:00ADDITIONAL PERMIT REQUIRED FOR REMOTE
 FUEL TANK AND PIPING.PLEASE PROVIDE
 VENTING INFORMATION FOR THE GENERATOR

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-07-21 Cont ID  
Sent By pkrauss Date 2005-07-21 Time 16:43 Rev Time 0.55
Received By pkrauss Date 2005-07-21 Time 16:35 Sent To  
Notes
2005-07-21 00:00:002 SETS OF PLANS WERE SUBMITTED &
 APPROVED, 3RD SET WAS SUBMITTED LATER
 WITH NO REVISIONS TO THE 2 APPROVED
 SETS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-06-30 Cont ID  
Sent By pkrauss Date 2005-06-30 Time 07:58 Rev Time 1.00
Received By pkrauss Date 2005-06-30 Time 07:58 Sent To  
Notes
2005-06-30 00:00:00DENIED:
 NEED THREE SETS OF PLANS, ONLY TWO
 SUBMITTED.PLANS APPROVED 4/4/05
  
 THE FOLLOWING PLANS WERE REVISED
 5/19/05:
 M1.03, M1.05, M1.08, M.62, M7.02, M7.03.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-04-07 Cont ID  
Sent By pkrauss Date 2005-03-23 Time 16:39 Rev Time 8.00
Received By pkrauss Date 2005-03-23 Time 16:39 Sent To  
Notes
2005-03-23 00:00:00DENIED:
 APPROVAL FOR THE VARIANCE WAS REVERSED.
  
 MECHANICAL APPROVAL PER THE VARIANCE
 APPROVED BY THE CONSTRUCTION BOARD OF
 ADJUSTMENT AND APPEALS (2-24-05) - CASE
 NUMBER 1228.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-30 Cont ID  
Sent By pkrauss Date 2004-12-30 Time 15:57 Rev Time 12.00
Received By pkrauss Date 2004-12-30 Time 15:57 Sent To  
Notes
2004-12-30 00:00:00DENIED:
 1.PLAN SHEET A1.07, INDICATES A FUME
 HOOD LOCATED IN ROOM 02.THIS IS NOT
 INDICATED ON THE MECHANICAL PLAN.
 PLEASE CLARIFY WHAT THE FUME HOOD WILL
 BE UTILIZED FOR.
  
 2.PLAN SHEET M1.01, PLAN INDICATE
 DUCT
 PENETRATING RATED WALL AT BS-3S & 3N,
 AND ALSO AT THE 2HR TEMPORARY WALL.
 PER
 2001 FBC(M)607.6, SPECIFIC LOCATIONS OF
 THE FIRE DAMPERS ARE REQUIRED.
 EXCEPTIONS FOR FIRE DAMPERS SHALL
 COMPLY
 WITH 2001 FBC(M)607.1.3 #3 ITEMS 1
 THROUGH 4.PLEASE ANNOTATE ON THE PLAN
 SHOULD THE EXCEPTION APPLY.
  
 3.PLAN SHEET M1.02, PLAN INDICATES
 DUCTS AND OR GRILLES PENETRATING OR
 TERMINATING AT RATED WALLS/PARTITIONS -
 ROOM # 19,20,21,35, 1S-2 & 1S-1.2001
 FBC(M) 607.6.
  
 4.PLAN SHEET M1.03, DUCT/GRILLE
 PENETRATIONS OR TERMINATION AT RATED
 WALLS/PARTITIONS - ROOM 11, 15, 1S-3S &
 3N.
  
 5.PLAN SHEET M1.03, CLARIFY CHASE IN
 ROOM 04, IS THIS RATED?
  
 6.PLAN SHEET M1.03, CLARIFY FRESH AIR
 INTAKE & BRANCH DUCT AT EXTERIOR WALL
 IS
 THIS A RELIEF GRILLE OR SUPPLY?
  
 7.PLAN SHEET M1.03, PLEASE IDENTIFY
 AHU IN THE MECHANICAL ROOM #15.PLEASE
 IDENTIFY ALL EQUIPMENT.
  
 8.PER 2001 FBC 414.5, ATRIUM SHALL BE
 SEPARATED FROM ADJACENT SPACES WITH A 1
 HOUR FIRE SEPARATION.THIS IS NOT
 INDICATED ON PLAN SHEETS A0.02 & A0.03.
  
 9.PLAN SHEET M7.02 INDICATES SMOKE
 EXHAUST AND CALCULATIONS FOR PHASE I.
 PLEASE CLAIRFY THE FOLLOWING:
 1) WILL THERE BE NO COMUNICATION
 BETWEEN
 THE TWO PHASES UNTIL COMPLETTION OF
 PHASE II.
 2) UPON COMPLETION OF PHASE II WILL
 THEY
 REMAIN "SEPARATED" BY WALLS & DOORS OR
 IS THE INTENT TO HAVE THE TWO
 STRUCTURES
 BE "OPEN" TO EACH OTHER.
 3) SHOULD THE INTENT BE FOR "OPEN" THE
 TWO STRUCTURES INTO ONE, THIS WILL THEN
 CHANGE THE CALCULATION FOR THE "ATRUIM"
 SMOKE EXHAUST.
  
 10.PLEASE PROVIDE ADDITIONAL
 INFORMATION ON PHASE II.IT APPEARS BY
 DEFININTION THAT IT ALSO HAS AN ATRIUM.
  
 11.PHASE II INDICATES "BASEMENT"
 SHOULD THIS SPACE ACTUALLY BE BELOW
 GRADE, SHOW COMPLIANCE WITH 2001 FBC(M)
 403.6.7.
  
 12.FAN SHUTDOWN BY DUCT SMOKE
 DETECTORS REQUIRED PER 2001
 FBC(M)606.2.1.
  
 13.NO COMBUSTIBLE ALLOWED IN THE
 RETURN AIR PLEUNUM, 2001 FBC(M)602.2.1.
  
 14.PLANS INDICATE ROOF ACCESS.WILL
 ANY MECHANICAL EQUIPMENT BE LOCATED IN
 THIS AREA?
  
 15.PROVIDE ADDITIONAL INFORMATION ON
 THE GENERATOR.INDICATE DISTANCES TO
 DOORS, WINDOWS, AND FRESH AIR INTAKES.
 PROVIDE ELEVATION FOR THE MUFFLER
 EXHAUST TERMINATION.
  
 16.INDICATE WHAT TYPE OF "FUEL" OR
 GAS
 WILL BE USED FOR THE GENERATOR.
  
 PLEASE PROVIDE A RESPONSE LETTER
 ADDRESSING COMMENTS TO HELP EXPEDITE
 FUTURE REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719
 OR
 E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 33 Status P Date 2009-05-20 Cont ID  
Sent By kstevens Date 2009-05-20 Time 12:01 Rev Time 0.00
Received By kstevens Date 2009-05-20 Time 12:01 Sent To  
Notes
2009-05-20 12:02:41REVISIONS OK -- SHT P1.03 REVISIONS 8, 9 & 10

Review Stop P PLUMBING
Rev No 32 Status N Date 2009-05-14 Cont ID  
Sent By shill Date 2009-05-14 Time 10:56 Rev Time 0.00
Received By shill Date 2009-05-14 Time 10:56 Sent To P
Notes
2009-05-14 10:56:19TO PLUMBING BOX

Review Stop P PLUMBING
Rev No 31 Status F Date 2009-05-01 Cont ID  
Sent By kstevens Date 2009-05-01 Time 13:43 Rev Time 0.00
Received By kstevens Date 2009-05-01 Time 13:43 Sent To  
Notes
2009-05-01 13:44:40REVISION DENIED
 REFERENCE:
 FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P1.03. THE LATEST REVIEWED & STAMPED REVISION
 WAS REVISION 7 SIGNED & SEALED 14 JAN 09. THE SHEET
 SUBMITTED SHOWS REVISIONS 8, & 9. THE ONLY REVISION
 CLOUDED AND NUMBERED IS NUMBER 9. ALL REVISIONS TO
 PREVIOUSLY REVIEWED & STAMPED SHEETS SHALL BE CLOUDED
 AND NUMBERED. SECTION 106.1.3. PLEASE SHOW THE
 LOCATIONS FOR REVISION 8 AS WELL AS REVISION 9 WHEN
 RESUBMITTING FOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 30 Status F Date 2009-04-30 Cont ID  
Sent By kstevens Date 2009-04-30 Time 13:35 Rev Time 0.00
Received By kstevens Date 2009-04-30 Time 13:35 Sent To  
Notes
2009-04-30 13:42:47REVISION DENIED
 REFERENCE:
 FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P1.03. THE LATEST REVIEWED & STAMPED REVISION
 WAS REVISION 7 SIGNED & SEALED 14 JAN 09. THE SHEET
 SUBMITTED SHOWS REVISIONS 8, 9 & 10. THE ONLY REVISION
 CLOUDED AND NUMBERED IS NUMBER 10. ALL REVISIONS TO
 PREVIOUSLY REVIEWED & STAMPED SHEETS SHALL BE CLOUDED
 AND NUMBERED. SECTION 106.1.3. PLEASE SHOW THE
 LOCATIONS FOR REVISIONS 8 & REVISION 9 AS WELL AS
 REVISION 10 WHEN RESUBMITTING FOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 29 Status P Date 2009-04-30 Cont ID  
Sent By kstevens Date 2009-04-30 Time 13:35 Rev Time 0.00
Received By kstevens Date 2009-04-30 Time 13:35 Sent To  
Notes
2009-04-30 13:35:40REVISION OK -- SHT P1.01

Review Stop P PLUMBING
Rev No 28 Status F Date 2009-03-16 Cont ID  
Sent By kstevens Date 2009-03-16 Time 16:46 Rev Time 0.00
Received By kstevens Date 2009-03-16 Time 16:46 Sent To  
Notes
2009-03-16 16:50:49DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1.03 REVISION 8 SHOWS A TEE AT THE BASE OF THE
 STORM RISER WITH A CLEANOUT AND A PLUG UNDER THE SLAB.
 PLEASE CLARIFY. SECTIONS 106.1.1 & 704.5. DEAD ENDS ARE
 PROHIBITED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 27 Status P Date 2009-03-16 Cont ID  
Sent By kstevens Date 2009-03-16 Time 16:46 Rev Time 0.00
Received By kstevens Date 2009-03-16 Time 16:46 Sent To  
Notes
2009-03-16 16:46:40REVISION OK -- SHT P1.03 REVISION #7.

Review Stop P PLUMBING
Rev No 26 Status P Date 2009-02-27 Cont ID  
Sent By kstevens Date 2009-02-27 Time 10:45 Rev Time 0.00
Received By kstevens Date 2009-02-27 Time 10:44 Sent To  
Notes
2009-02-27 10:45:32REVISION OK -- SHT P1.07

Review Stop P PLUMBING
Rev No 25 Status F Date 2009-02-12 Cont ID  
Sent By kstevens Date 2009-02-12 Time 10:36 Rev Time 0.00
Received By kstevens Date 2009-02-12 Time 10:35 Sent To  
Notes
2009-02-12 10:42:42DENIED
 REFERENCE:
 FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1 (ADMIN)
  
 1. SHT P1.03. CHANGES TO THE STORM PIPING SHALL BE
 REFLECTED ON THE STORM RISER DIAGRAM AREA "B". SECTIONS
 104.2.1 & 1101.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 24 Status P Date 2009-02-12 Cont ID  
Sent By kstevens Date 2009-02-12 Time 10:34 Rev Time 0.00
Received By kstevens Date 2009-02-12 Time 10:34 Sent To  
Notes
2009-02-12 10:35:50REVISIONS OK -- SHTS P1.05, P1.07 & P3.05.
  

Review Stop P PLUMBING
Rev No 23 Status P Date 2009-01-22 Cont ID  
Sent By kstevens Date 2009-01-22 Time 16:24 Rev Time 0.00
Received By kstevens Date 2009-01-22 Time 16:24 Sent To  
Notes
2009-01-22 16:25:57REVISIONS OK -- SHTS P1.01, P1.03, P1.05, P1.07, P1.09,
 P3.05 & P5.01.

Review Stop P PLUMBING
Rev No 22 Status P Date 2008-08-15 Cont ID  
Sent By kstevens Date 2008-08-15 Time 15:27 Rev Time 0.00
Received By kstevens Date 2008-08-15 Time 15:27 Sent To  
Notes
2008-08-15 15:29:29REVISIONS OK--SHTS P1.03, P1.07 & P3.05.

Review Stop P PLUMBING
Rev No 21 Status P Date 2008-07-24 Cont ID  
Sent By kstevens Date 2008-07-24 Time 11:10 Rev Time 0.00
Received By kstevens Date 2008-07-24 Time 11:10 Sent To  
Notes
2008-07-24 11:10:59REVISIONS OK--SHTS P1.09 & P1.10REVISION #2 ON
 BOTH

Review Stop P PLUMBING
Rev No 20 Status F Date 2008-07-24 Cont ID  
Sent By kstevens Date 2008-07-23 Time 17:45 Rev Time 0.00
Received By kstevens Date 2008-07-23 Time 17:44 Sent To  
Notes
2008-07-24 11:08:59REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1.03 REVISION NUMBER 3 DENIED. THERE ARE
 CHANGES/REVISIONS BETWEEN COLUUM LINES 10 THRU 11 AND B
 THRU H THAT ARE NOT CLOUDED NOR INDICATED WITH A
 REVISION NUMBER. SECTION 106.1.3.
  
 2. SHT P3.05 REVISION NUMBER 2 DENIED. THERE ARE
 CHANGES/REVISIONS SHOWN ON THE TOILET AREAS IN THE
 BASEMENT AREA "B", THE BASEMENT AREA "B"PLUMBING NEW
 WORK KEYED NOTES THAT ARE NOT CLOUDED NOR INDICATED
 WITH A REVISION NUMBER. SECTION 106.1.3.
  
 3. SHT P1.03 REVISION NUMBER 4 NOT FOUND. PLEASE CLOUD
 AND NUMBER REVISION #4 FOR REVIEW. SECTION 106.1.3.
  
 4. SHT P1.07 REVISION NUMBER 4 NOT APPROVED. SHOW THE
 PIPE SIZES FOR THE HORIZONTAL STORM SYSTEM. MINIMUM 4"
 REQUIRED FOR 1107SF, MINIMUM 5" REQUIRED FOR 1883SF,
 MINUIMUM 5" REQUIRED FOR OVERFLOW DRAIN 1107SF, &
 MINIMUM 6" REQUIRED FOR OVERFLOW DRAIN 1883SF. PLEASE
 SHOW PIPE SIZE AND/OR SLOPE OF PIPE THAT COMPLIES WITH
 SECTION 1106.3 & SECTION 1107.3.
  
 5. SHT P3.05 REVISION NUMBER 4 NOT APPROVED. THERE ARE
 CHANGES/REVISIONS ON THE PLANS THAT ARE NOT CLOUDED NOR
 INDICATED WITH A REVISION NUMBER. SECTION 106.1.3.--
 ALSO DRY HORIZONTAL VENTS ARE NOT APPROVED UPSTREAM OF
 THE WATER CLOSETS IN BOTH THE MEN'S TOILET ROOM AND
 WOMEN'S TOILET ROOM. SECTIONS 905.3 & 905.4.
  
 6. SHT P3.05 REVISION NUMBER 5 NOT APPROVED. THERE ARE
 CHANGES/REVISIONS ON THE PLANS THAT ARE NOT CLOUDED NOR
 INDICATED WITH A REVISION NUMBER. SECTION 106.1.3.--
 ALSO DRY HORIZONTAL VENTS ARE NOT APPROVED UPSTREAM OF
 THE WATER CLOSETS IN BOTH THE MEN'S TOILET ROOM AND
 WOMEN'S TOILET ROOM. SECTIONS 905.3 & 905.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 19 Status F Date 2008-07-02 Cont ID  
Sent By kstevens Date 2008-07-02 Time 14:43 Rev Time 0.00
Received By kstevens Date 2008-07-02 Time 14:43 Sent To  
Notes
2008-07-02 14:48:56REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1.03 REVISION #3 INDICATED IN THE REVISION
 INDEX ON THE TITLE BLOCK IS NOT SHOWN ON THE FLOOR PLAN
 NOR ON THE RISER DIAGRAMS. ALSO NOT ALL
 CHANGES/REVISIONS ARE CLOUDED & NUMBERED WITH A
 REVISION NUMBER. SECTION 106.1.3.
  
 2. SHT P3.05 REVISION #2 INDICATED IN THE REVISION
 INDEX ON THE TITLE BLOCK IS NOT SHOWN ON THE FLOOR PLAN
 NOR ON THE RISER DIAGRAMS. ALSO NOT ALL
 CHANGES/REVISIONS ARE CLOUDED & NUMBERED WITH A
 REVISION NUMBER. SECTION 106.1.3.
  
 3. SHT P3.05 HORIZONTAL DRY VENTS ARE NOT APPROVED.
 SECTION 905.3. THIS IS SHOWN ON THE FLOOR PLAN AND THE
 RISER DIAGRAM FOR THE BASEMENT WORK.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 18 Status P Date 2008-07-02 Cont ID  
Sent By kstevens Date 2008-07-02 Time 14:42 Rev Time 0.00
Received By kstevens Date 2008-07-02 Time 14:42 Sent To  
Notes
2008-07-02 14:43:07REVISIONS OK--SHTS P1.01 & P5.01

Review Stop P PLUMBING
Rev No 17 Status P Date 2008-04-24 Cont ID  
Sent By kstevens Date 2008-04-24 Time 08:45 Rev Time 0.00
Received By kstevens Date 2008-04-24 Time 08:45 Sent To  
Notes
2008-04-24 08:47:09REVISION OK--8.5X11 SHEET REVISED A PORTION OF THE
 SANITARY RISER DIAGRAM FOR SHEET P3.05.

Review Stop P PLUMBING
Rev No 16 Status F Date 2007-11-05 Cont ID  
Sent By kstevens Date 2007-11-05 Time 11:50 Rev Time 0.00
Received By kstevens Date 2007-11-02 Time 11:50 Sent To  
Notes
2007-11-05 11:52:54DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P3.05 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. (SEE RED LINE EXAMPLE, ON ONE SET, OF
 RISER THAT REFLECT THE FLOOR PLAN). SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 15 Status P Date 2007-11-05 Cont ID  
Sent By kstevens Date 2007-11-05 Time 11:48 Rev Time 0.00
Received By kstevens Date 2007-11-02 Time 18:55 Sent To  
Notes
2007-11-05 11:49:46REVISIONS OK--SHTS P1.05, P1.07, P3.06

Review Stop P PLUMBING
Rev No 14 Status N Date 2007-10-16 Cont ID  
Sent By lmartine Date 2007-10-16 Time 13:39 Rev Time 0.00
Received By lmartine Date 2007-10-16 Time 13:39 Sent To  
Notes
2007-10-16 13:40:18PLUMBING REVIEW NOT REQUIRED FOR ADDED ROOF DRAIN

Review Stop P PLUMBING
Rev No 13 Status P Date 2007-03-06 Cont ID  
Sent By kstevens Date 2007-03-06 Time 08:29 Rev Time 0.00
Received By kstevens Date 2007-03-06 Time 08:29 Sent To  
Notes
2007-03-06 08:30:08REVISION OK - SHT P3.03 DELETED FLOOR SINKS - ADDED ONE
 FLOOR DRAIN.

Review Stop P PLUMBING
Rev No 12 Status N Date 2007-03-06 Cont ID  
Sent By kstevens Date 2007-03-06 Time 08:24 Rev Time 0.00
Received By kstevens Date 2007-03-06 Time 08:24 Sent To  
Notes
2007-03-06 08:24:59REVISION FOR VENT OF DIESEL FUEL TANK - ROUTED TO
 MECHANICAL

Review Stop P PLUMBING
Rev No 11 Status P Date 2006-08-22 Cont ID  
Sent By kstevens Date 2006-08-22 Time 10:43 Rev Time 0.00
Received By kstevens Date 2006-08-22 Time 10:43 Sent To  
Notes
2006-08-22 00:00:00REVISIONS OK
  
 SHTS SKPR-3R,SKP-4R, SKP-5R, & SKP-6R

Review Stop P PLUMBING
Rev No 10 Status P Date 2006-08-14 Cont ID  
Sent By kstevens Date 2006-08-14 Time 18:59 Rev Time 0.00
Received By kstevens Date 2006-08-14 Time 18:59 Sent To  
Notes
2006-08-14 00:00:00REVISION OK - CHANGED THE ROUTING OF THE
 ROOF DRAINS AND OVERFLOW DRAINS FROM THE
 4TH FLOOR TO THE 3RD FLOOR. SKP-3,
 SKP-4, SKP-5, SKP-6.

Review Stop P PLUMBING
Rev No 9 Status P Date 2006-08-10 Cont ID  
Sent By kstevens Date 2006-08-10 Time 07:47 Rev Time 0.00
Received By kstevens Date 2006-08-10 Time 07:47 Sent To  
Notes
2006-08-10 00:00:00REVISION OK - SHTS SP-CC1 & SP-CC2
 REVISIONS TO JAZZMAN CAFE SANT. AND
 WATER LAYOUTS

Review Stop P PLUMBING
Rev No 8 Status F Date 2006-06-01 Cont ID  
Sent By kstevens Date 2006-06-01 Time 08:18 Rev Time 0.00
Received By kstevens Date 2006-06-01 Time 08:18 Sent To  
Notes
2006-06-01 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. FAC-61G15-23.002(2) AND
 FS 471.025.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 7 Status P Date 2006-04-03 Cont ID  
Sent By jleech Date 2006-04-03 Time 12:27 Rev Time 0.00
Received By jleech Date 2006-04-03 Time 12:27 Sent To  
Notes
2006-04-03 00:00:00REVISION CHANGED LOCATION OF WATER
 SERVICE SHT. SKP-2 OK

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-03-23 Cont ID  
Sent By mperson Date 2006-03-23 Time 16:10 Rev Time 0.45
Received By mperson Date 2006-03-23 Time 16:10 Sent To PC
Notes
2006-03-23 00:00:00REVISION: ADDED 4" FLOOR DRAIN, 2" VENT,
 AND 1/2" POTABLE WATER FOR TRAP PRIMER

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-02-21 Cont ID  
Sent By kstevens Date 2006-02-21 Time 17:55 Rev Time 0.00
Received By kstevens Date 2006-02-21 Time 17:55 Sent To  
Notes
2006-02-21 00:00:00REVISION OK
  
 DELETED 3" VENT FROM GANG BATH 3 FLOORS

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-09-02 Cont ID  
Sent By kstevens Date 2005-09-02 Time 08:32 Rev Time 1.62
Received By kstevens Date 2005-09-01 Time 19:05 Sent To B
Notes
2005-09-02 00:00:00REVISION OK SHTS A1.04 REV. #3
 A2.09 REV. #3
 A3.03 REV. #5
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-07-21 Cont ID  
Sent By kstevens Date 2005-07-21 Time 15:18 Rev Time 7.62
Received By kstevens Date 2005-06-25 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-10 Cont ID  
Sent By kstevens Date 2005-03-10 Time 17:28 Rev Time 14.00
Received By kstevens Date 2005-03-09 Time 18:15 Sent To  
Notes
2005-03-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 CITY WPB CODE
  
 A) FROM PREVIOUS REVIEW: THE COMMENT
 NUMBER SHALL REMAIN THE SAME TO AVOID
 CONFUSION.
 1) SHT C3.01 DRAIN FOR SICSSOR LIFT TO
 STORM, MORE INFORMATION IS REQUIRED FOR
 THIS DRAIN, RESPONSE NOTED, BUT PLEASE
 INDICATE WHAT WILL BE DRAINING INTO THE
 STORM LINE. IS THIS FOR STORM WATER
 ONLY? - INDICATE IF THERE IS A
 POSSIBILITY OF OIL OR GREASE
 DRAINING/DRIPPING FROM THE LIFT AND
 ENTERING THE STORM WATER.
 4) SHT A5.01 STAFF LOUNGE AND SERVING
 ROOM SINKS SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT
 INFORMATION ON DETAIL. RESPONSE NOTED
 BUT THE FOLLOWING INFORMATION IS NOT
 SHOWN. SINK DEPTH 11-4.24.4, CLEAR FLOOR
 SPACE 11-4.24.5, EXPOSED PIPES AND
 SURFACES 11-4.24.6, & FAUCETS 11-4.24.7.
 5) SHT A8.02DETAILS 1, 2, & 3 SHOW
 CLEAR FLOOR SPACE FOR ALL ACCESSIBLE
 FIXURES, TURNING AREA FOR ALL TOILET
 ROOMS. DOORS SHALL NOT OPEN INTO THE
 CLEAR FLOOR SPACE FOR ANY REQUIRED
 FIXTURE. RESPONSE NOTED, BUT THE
 FOLLOWING INFORMATION IS NOT SHOWN:
 DETAIL #2 SHOW CLEAR FLOOR SPACE FOR
 TOILET ROOMS 07 & 08 WITH TURNING AREA,
 SECTIONS 11-4.16.2, 11-4.19.3, &
 11-4.22.3. EXPOSED PIPES AND SURFACES
 11-4.19.6. ALSO IT APPEARS THAT THE
 DOORS ARE OPENING TINTO THE CLEAR FLOOR
 SPACE FOR THE LAVS. DISPENSER TO BE A
 MINIMUM OF 19" OFF THE FLOOR ON DETAIL
 11/A802. FIGURE 29(B)
 6) SHT A8.03 COFFEE CAFE ROOMS 1A03 &
 1A04 REQUIRED THAT THE PLANS BE ROUTED
 TO THE PALM BEACH COUNTY HEALTH UNIT
 DIISION OF ENVIRONMENTAL HEALTH FOR
 REVIEW AND STAMPING PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW.
 RESPONSE NOTED, BUT THE PLANS SHALL BE
 REVIEWED AND STAMPED PRIOR TO
 RESUBMITTING FOR REVIEW CITY WPB.
 SECTION 101.4.7.
 7) SHT P102 SUBMIT CALCULATION FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, & 1107 & ALL SUBSECTIONS.
 RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS REQUIRED. SHT P1.02 4"
 RWL'S AT COL. LINES 11/R, 10-11/N,&
 10/J, MAXIMUM 1600 SF ON 4" HORIZONTAL.
 6" REQUIRED OR SLOPE TO BE INDICATED AT
 1/4"/FT. - SHT P1.03 RWL LINE AND OFD
 LINE ARE MISLABELED. - SHT P1.04 4"
 HORIZONTAL OFFSET, MAXIMUM 1600 SF,
 INDICATE SLOPE OR INCREASE TO 6". - SHT
 P1.06 MAXIMUM 1600 SF. INCREASE TO 6" OR
 INDICATE SLOPE. - SHT P1.07 RWL LINE
 FROM ROOF DRAIN AT COL. LINE 4/D SHALL
 BE RUN AT 1/4"/FT. SECTION 704.1 - SHT
 P1.08 4" OFD MISLABELED AS RWL NOT SIZED
 CORRECTLY. - PIPE SIZES MISSING ON SOME
 OFD'S AND RWL'S - SOME OFD PIPING IS
 UNDERSIZED - RWL PIPING IS MISLABELED AS
 OFD. - SOME SQUARE FOOTAGE IS NOT ADDED
 CORRECTLY. - 2" OFD PIPING NOT ADDED
 CORRECTLY. - P1.09 ALL OFD'S ARE
 MISLABELED AS RWL.
 9) SHT P3.02 WATER RISER DIAGRAM, FULL
 OPEN VALVES ARE REQUIRED ON ALL WATER
 DOWN-FEED LINES PER SECTION 606.1(4).
 RESPONSE NOTED, BUT VALVES ARE STILL NOT
 SHOWN ON LINES TO FIXTURE L-2 ON ALL
 FLOORS.
 12) SHT P3.03 DOMESTIC WATER RISER
 DIAGRAM, WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS. RESPONSE
 NOTED, BUT WHA'S ARE STILL SHOWN IN THE
 CEILING. PLEASE LOCAATE WHERE REQUIRED
 PER 604.9 (WASH MACHINE, ICE MAKER, DISH
 WASHER IF PROVIDED),
 14) SHT P3.04 WATER FILTERS SHALL BE
 NSF-42 LISTED. SUBMIT MANUFACTURE
 SPECIFICATION SHEETS. SECTION 611.
 RESPONSE NOTED, BUT SHEETS WERE NOT
 SUBMITTED AS REQUESTED.
 16) SHT P3.04 WASH SINK WATER PIPING,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201.
 FULL OPEN VALVES REQUIRED ON ALL WATER
 DOWN-FEED LINES. SECTION 606.1(4).
 RESPONSE NOTED, BUT THE WHA'S ARE STILL
 IN THE CEILING AND THE WATER DOWN-FEED
 LINES DO NOT HAVE VALVES ON THEM.
 18) SUBMIT A STORM BUILDING DRAIN
 ISOMETRIC SHOWING ALL PIPE SIZES, RISER
 CONNECTION, AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. ALSO SHOW
 SLOPE OF PIPE. SECTION 104.3.1.1. -
 SYSTEM CUT FIRST LINE OF COMMENTS FROM
 THE TEXT. STORM ISOMETRIC REQUIRED.
 19) SUBMIT A CONDENSATED DRAIN SYSTEM
 ISOMETRIC. SHOW ALL PIPE SIZES, RISERS
 AND SHOW TERMINATION POINT FOR
 CONDENSATE. SECTION 104.3.1.1. RESPONSE
 NOTED, BUT CONDENSATE SHALL NOT DRAIN
 INTO THE SANITARY SYSTEM PER CITY CODE
 SECTION 90-125(2)(B). CONDENSATE SHALL
 DRAIN SEPARATELY OUT OF THE BUILDING AND
 CONNECT TO A CATCH BASIN, A STORM LINE,
 OR A DRYWELL. A RELIEF VENT IS REQUIRED
 AS THE CONDENSATE EXITS THE BUILDING.
 *************NEW COMMENT************
 1B) SHT P1.07 ENTIRE RUN FOR RWL FROM
 RD-2 TO 6" RWL DOWN TO LEVEL 2 TO RUN AT
 1/4"/FT SLOPE. SECTION 704.1
 2B) NOTE: ONE SET OF PLUMBING SHEETS HAS
 RED LINES SHOWING LOCATION OF COMMENTS.
 PLEASE RESUBMIT THESE SHEETS FOR
 COMPARISON.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-30 Cont ID  
Sent By kstevens Date 2004-12-30 Time 18:42 Rev Time 10.00
Received By kstevens Date 2004-12-30 Time 18:42 Sent To  
Notes
2004-12-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT C3.01 DRAIN FOR SCISSOR LIFT TO
 STORM. MORE INFORMATION IS REQUIRED FOR
 THIS DRAIN. WHAT IS IT DRAINING? SECTION
 104.2.1.
 2) SEPARATE PLANS AND PERMIT ARE
 REQUIRED FOR THE IRRIGATION. SECTION
 104.1.1.
 3) SHT A5.01 INTERIOR ELEVATION DETAILS
 NUMBERS 14/A5.01 & 17/A5.01 DO NOT
 REFLECT THE DETAIL NUMBERS SHOWN ON SHTS
 A1.05 (ROOM 12) & A1.06 (ROOM 03).
 PLEASE CORRELATE PLANS/DETAILS. SECTION
 104.2.1.
 4) SHT A5.01 STAFF LOUNGE & SERVING ROOM
 SINKS SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. SUBMIT INFORMATION
 ON DETAIL.
 5) SHT A8.02 DETAILS 1, 2, & 3 SHOW
 CLEAR FLOOR SPACE FOR ALL ACCESSIBLE
 FIXTURES, (DRINKING FOUNTAIN, URINAL
 ECT.), TURNING AREA FOR ALL TOILET
 ROOMS. DOORS SHALL NOT OPEN INTO THE
 CLEAR FLOOR SPACE FOR ANY REQUIRED
 FIXTURE. SECTIONS 11-4.15, 4-16, 4-18,
 4-19, 4-22. (DETAIL 2/8.05 ROOM 7) - TWO
 DETAILS HAVE THE NUMBER "3" AND NO
 DETAIL "4". PLEASE CLARIFY. SECTION
 104.2.1.
 6) SHT A8.03 COFFEE CAFE ROOMS 1A03 &
 1A04 REQUIRED THAT THE PLANS BE ROUTED
 TO THE PALM BEACH COUNTY HEALTH UNIT
 DIISION OF ENVIRONMENTAL HEALTH FOR
 REVIEW AND STAMPING PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW.
 7) SHT P1.02 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, & 1107 AND ALL
 SUBSECTIONS. SHOW SF OF EACH AREA WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AS WELL AS ANY SF OF AREA OF
 ROOF THAT DRAIN ONTO THE ROOF AREAS FROM
 ABOVE IN THE CALCULATIONS.
 8) SHT P3.01 SANT. RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. THE WATER
 CLOSETS FOR THE MENS TOILET ROOMS ON
 EACH FLOOR ARE NOT SHOWN ON THE RISER.
 THE HORIZONTAL DRY VENTS AT THE BASE OF
 THE STACKS ARE NOT APPROVED PER SECTION
 905.3.
 9) SHT P3.02 WATER RISER DIAGRAM, FULL
 OPEN VALVES ARE REQUIRED ON ALL WATER
 DOWN FEED LINES PER SECTION 606.1(4).
 10) GREASE INTECEPTOR NOT APPROVED
 INSIDE OF THE BUILDING AND SHALL BE
 LOCATED OUTSIDE. GREASE INTERCEPTOR
 SHALL BE SIZED BY RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE PER WASTE ORD.
 NUMBER 2938-96. CONTACT R. COMPO AT
 (561) 835-4074. APPROVAL SHEET SHALL BE
 ATTACHED TO PLANS WHEN RESUBMITTING.
 11) SHT P3.03 FLOOR SINKS ARE REQUIRED
 FOR INDIRECT WASTE AND SHALL NOT BE A
 TRIPPING HAZARD. SECTION 802.3. - FLOOR
 DRAINS FOR DRAINING FLOORS ONLY.
 12) SHT P3.03 DOMESTIC WATER RISER
 DIAGRAM, WATERHAMMER ARRESTORS SHALL
 BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF INSTALLATION
 INSTRUCTIONS.
 13) SUBMIT A GREASE WASTE ISOMETRIC
 RISER DIAGRAM AND A SANT. RISER DIAGRAM
 FOR THIS FLOOR PLAN SHOWING WHERE IT
 CONNECTS TO THE BLDG DRAIN ISO. OR BLDG
 SEWER. SECTION 104.3.1.1.
 14) SHT P3.04 WATER FILTERS SHALL BE
 NSF-42 LISTED. SUBMIT MANUF.
 SPECIFICATION SHEETS. SECTION 611.
 15) SHT P3.04 ICE MAKER WATER SUPPLY
 REQUIRES BACKFLOW PROTECTION. SECTION
 608.3.
 16) SHT P3.04 WASH SINK WATER PIPING,
 WATER HAMMERS SHALL BE LOCATED NEAR THE
 FIXTURE NOT IN THE CEILING. PDI-WH 201.
 FULL OPEN VALVES REQUIRED PER SECTION
 606.1(4).
 17) SHT P3.05 SERVING ROOM WASTE RISER,
 ICE MACHINES TO INDIRECT WASTED. SECTION
 802.3 & 802.3.2.
 18) SUBMIT A STORM BUILDING DRAIN
 ISOMETRIC SHOWING ALL PIPE SIZES, RISER
 CONNECTION, AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. ALSO SHOW
 SLOPE OF PIPE. SECTION 104.3.1.1.
 19) SUBMIT A CONDENSATED DRAIN SYSTEM
 ISOMETRIC. SHOW ALL PIPE SIZES, RISERS
 AND SHOW TERMINATION POINT FOR
 CONDENSATE. SECTION 104.3.1.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 6 Status F Date 2009-09-10 Cont ID  
Sent By jroach Date 2009-09-10 Time 09:42 Rev Time 0.00
Received By ajones Date 2009-09-10 Time 09:42 Sent To  
Notes
2009-09-10 09:46:46ZONING PLAN REVIEW
  
 PERMIT NO.: 04111073
 ADDRESS: 300 PEMBROKE PLACE
 CONTRACTOR/CONTACT: DOUG STRATHIE
 TELEPHONE NO.: (561) 719.0503
 SCOPE OF REVIEW: REVISION FOR LANDSCAPE AS-BUILT.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PERSUANT TO SECTION 94-207(E) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS, ANY CHANGES TO AN
 APPROVED SITE / LANDSCAPE PLAN WITHIN A PLANNED
 DEVELOPMENT (PD) SHALL REQUIRE THE APPROVAL OF A
 AMENDMENT TO THE PD. PRIOR TO APPROVAL OF THE BUILDING
 PERMIT REVISIONS, A MINOR AMEDMENT TO THE PBAU
 COMMUNITY SERVICE PLANNED DEVELOPMENT (CSPD) SHALL BE
 SUBMITTED TO, AND APPROVED BY, THE PLANNING AND ZONING
 DEPARTMENT.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 5 Status P Date 2007-11-19 Cont ID  
Sent By jroach Date 2007-11-19 Time 21:38 Rev Time 0.00
Received By jroach Date 2007-11-19 Time 21:38 Sent To  
Notes
2007-11-19 21:40:30REVISIONS DATED 9/27/07 AND SUBMITTED TO CONSTRUCTION
 SERVICES ON OCTOBER 2, 2007...
  
 ***PASSED WITH PROVISIOS***
  
 1) THE EXISTING 3-STORY RECTANGULAR BRICK BUILDING WEST
 OF THE ROTUNDA SHALL NOT BE DEMOLISHED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 OR FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION
 PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status P Date 2007-10-09 Cont ID  
Sent By jroach Date 2007-10-09 Time 20:06 Rev Time 0.00
Received By jroach Date 2007-10-09 Time 20:06 Sent To  
Notes
2007-10-09 20:07:20REVISIONS DO NOT AFFECT ZONING REVIEW.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2005-07-13 Cont ID  
Sent By lshapiro Date 2005-07-13 Time 16:04 Rev Time 0.00
Received By lshapiro Date 2005-07-13 Time 16:04 Sent To  
Notes
2005-07-13 00:00:00MINOR CHANGES TO CUPOLA VENT STILL MEETS
 STANDARDS.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-07-13 Cont ID  
Sent By mmclean Date 2005-02-25 Time 09:11 Rev Time 0.00
Received By mmclean Date 2005-07-13 Time 15:59 Sent To  
Notes
2005-03-10 00:00:00DENIED,
 1. SITEPLAN DOES NOT MATCH WHAT WAS
 APPROVED. NEED TO APPLY FOR AN INFORMAL.
 RANDALL GRANBERRY, PLANNER 822-1454, 5TH
 FLOOR

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-03 Cont ID  
Sent By mmclean Date 2004-12-03 Time 15:32 Rev Time 0.00
Received By mmclean Date 2004-12-03 Time 15:32 Sent To  
Notes
2004-12-03 00:00:00DENIED, SITEPLAN DOES NOT MATCH APPROVED
 PLANS. RANDALL GRANBERRY 822-1454