Plan Review Details - Permit 04110966
Plan Review Stops For Permit 04110966
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-01-04 Cont ID  
Sent By jwitmer Date 2005-01-04 Time 12:18 Rev Time 1.25
Received By jwitmer Date 2005-01-04 Time 12:18 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-14 Cont ID  
Sent By jwitmer Date 2004-12-14 Time 10:52 Rev Time 1.10
Received By jwitmer Date 2004-12-14 Time 08:51 Sent To  
Notes
2004-12-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110966
 ADD: 1601 BWLVEDERE ROAD
 CONT: HIGGINS
 TEL: (561)684-6400
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 407.14 HIGHLY TOXIC LIQUIDS
 407.14.4 EXTERIOR STORAGE
 EXTERIOR STORAGE OF HIGHLY TOXIC OR
 TOXIC SOLIDS OR LIQUIDS SHALL NOT BE
 PERMITTED WITHIN 20'-0" OF ANY
 BUILDING,
 PROPERTY LINE,STREET, ALLEY, PUBLIC
 WAY,
 OR EXIT TO A PUBLIC WAY.
 EXCEPTION, AN UNPIERCED 2 HR WALL FIRE
 RESISTANT WALL EXTENDING NOT LESS THAN
 30" ABOVE AND TO THE SIDES OF THE
 STORAGE AREA MAY BE PROVIDED IN LIEU OF
 SUCH DISTANCE.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-07 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 13:29 Rev Time 0.33
Received By btrobaug Date 2005-01-07 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-11-19 Cont ID  
Sent By btrobaug Date 2004-11-19 Time 09:46 Rev Time 1.00
Received By btrobaug Date 2004-11-19 Time 07:32 Sent To FIRE
Notes
2004-12-02 00:00:00 
 PROVISO
 ~~~~~~~
  
 PLEASE NOTE THAT A DISCONNECT IS
 REQUIRED PER 225.31. PROVIDE A REVISED
 DRAWING INDICATING ALL
 EQUIPMENT,LOCATIONS AND RATINGS, PRIOR
 TO FINAL INSPECTION.
  
  
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-12-20 Cont ID  
Sent By mcarsill Date 2004-12-20 Time 16:39 Rev Time 0.00
Received By mcarsill Date 2004-12-20 Time 16:39 Sent To  
Notes
2004-12-20 00:00:001. INSTALLATION TO COMPLY WITH NFPA 30
 AND NFPA 30A.
  
 2. FUEL TANK INSTALLATION SHALL
 COMPLY WITH ALL APPLICABLE SET-BACK
 REQUIREMENTS FROM PROPERTY LINES,
 IMPORTANT BUILDINGS, ETC.
  
 3. WARNING LABELS, PLACARDS, AND
 OTHER SIGNAGE WILL BE REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2004-12-20 Time 13:46 Rev Time 0.00
Received By mjacobs Date 2004-12-02 Time 12:23 Sent To PC
Notes
2004-12-02 00:00:00SENT TO COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2004-11-22 Time 17:16 Rev Time 0.00
Received By mjacobs Date 2004-11-22 Time 17:16 Sent To Z
Notes
2004-11-22 00:00:00SENT TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-04 Cont ID  
Sent By pkrauss Date 2004-12-20 Time 12:30 Rev Time 0.00
Received By pkrauss Date 2004-11-18 Time 10:21 Sent To  
Notes
2004-11-18 00:00:00 
 TO ZONING, MICHELLE,S DESK./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-01-04 Cont ID  
Sent By pkrauss Date 2005-01-04 Time 12:25 Rev Time 0.10
Received By pkrauss Date 2005-01-04 Time 12:25 Sent To  
Notes
2005-01-04 00:00:00PROVISO:
 ADDITIONAL PERMIT REQUIRED FOR THE FUEL
 PIPING.PLEASE PROVIDE PLANS WITH
 PIPING MATERIAL, SIZE, AND LAYOUT FOR
 FUEL PIPING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-16 Cont ID  
Sent By pkrauss Date 2004-12-16 Time 14:54 Rev Time 0.55
Received By pkrauss Date 2004-12-16 Time 14:54 Sent To  
Notes
2004-12-16 00:00:00SEE COMMENTS BY JIM WITMER, BUILDING
 PLANS EXAMINER.PLANS ARE OTHERWISE
 CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 3 Status P Date 2005-01-04 Cont ID  
Sent By mmclean Date 2005-01-04 Time 10:23 Rev Time 0.00
Received By mmclean Date 2005-01-04 Time 10:23 Sent To B
Notes
2005-01-04 00:00:00APPROVED WITH MINOR AMENDMENT #PB 975B
 BY EDNASHA BOWERS, PLANNER 822-1444.
 PLANS GIVEN TO JIM WITMER, BLDG PLAN
 REVIEWER MM

Review Stop Z ZONING
Rev No 2 Status F Date 2004-12-03 Cont ID  
Sent By mjacobs Date 2004-12-20 Time 13:46 Rev Time 0.00
Received By mmclean Date 2004-12-03 Time 15:34 Sent To  
Notes
2004-12-03 00:00:00DENIED, NEED TO APPLY FOR A MINOR
 AMENDMENT FOR GENERATOR AND FENCE.NEED
 TO CALL PLANNING & ZONING AT 822-1435 TO
 SPEAK WITH A PLANNNER FOR THE PROCESS.
 CALLED RAY HIGGINS (CONTRACTOR). PLANS
 RETURNED TO COMM BOARD #50 MM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-01 Cont ID  
Sent By mmclean Date 2004-12-01 Time 16:00 Rev Time 0.00
Received By mmclean Date 2004-12-01 Time 16:00 Sent To E
Notes
2004-12-01 00:00:00DENIED, NEED TO PROVIDE SITEPLAN OR
 SURVEY SHOWING THE LOCATION OF THE
 GENERATOR.BILL T CALLED CONTRACTOR AND
 INFORM THEM OF WHAT'S NEEDED FOR ZONING.
 PLANS RETURNED TO BILL T