Plan Review Details - Permit 04110588
Plan Review Stops For Permit 04110588
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2005-01-13 Cont ID  
Sent By alange Date 2005-01-13 Time 10:12 Rev Time 0.25
Received By alange Date 2005-01-13 Time 10:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-08 Cont ID  
Sent By alange Date 2004-12-08 Time 09:09 Rev Time 0.50
Received By alange Date 2004-12-08 Time 09:09 Sent To  
Notes
2004-12-08 00:00:00DENIED
  
 INSUFFICIENT INFORMATION PROVIDED FOR A
 BUILDING REVIEW.
 SHOW ON PLANS NEW AND EXISTING WORK
 BEING DONE, SHOW USE, IS A GARAGE OR
 LIVING SPACE.
 IF IT IS A HABITABLE AREA THE FINISH
 FLOOR SHALL BE A MINIMUM OF 4" ABOVE
 FINISH GRADE.
  
 SUBMIT DETAILS FOR NEW FRAMING AND
 PRODUCT APPROVALS FOR EXTERIOR DOORS,
 WINDOWS AND ROOFING.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-06 Cont ID  
Sent By btrobaug Date 2005-01-06 Time 16:22 Rev Time 0.33
Received By btrobaug Date 2005-01-06 Time 15:57 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-18 Cont ID  
Sent By btrobaug Date 2004-11-18 Time 18:35 Rev Time 0.00
Received By BTROBAUG Date 2004-11-22 Time 14:16 Sent To Z
Notes
2004-11-18 00:00:00 
 SPOKE WITH OWNER WHO SAID THIS SPACE
 WAS A LEGALLY REQUIRED GARAGE, AM
 SENDING TO ZONING FOR OPINION./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-05 Cont ID  
Sent By mjacobs Date 2005-01-05 Time 08:41 Rev Time 0.00
Received By mjacobs Date 2005-01-05 Time 08:41 Sent To E
Notes
2005-01-05 00:00:00TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 14:05 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 14:05 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-22 Cont ID  
Sent By dpalmer Date 2004-11-22 Time 14:17 Rev Time 0.00
Received By dpalmer Date 2004-11-22 Time 14:17 Sent To P
Notes
2004-11-22 00:00:00BACK FROM ZONING, TO PLUMB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-10 Cont ID  
Sent By csiegber Date 2004-11-10 Time 14:08 Rev Time 0.00
Received By csiegber Date 2004-11-10 Time 14:08 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-01-12 Cont ID  
Sent By jleech Date 2005-01-12 Time 10:07 Rev Time 0.25
Received By jleech Date 2005-01-12 Time 10:07 Sent To B
Notes
2005-01-12 00:00:00NO PLUMBING PLANS SUBMITED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-27 Cont ID  
Sent By kstevens Date 2004-11-27 Time 05:17 Rev Time 0.50
Received By kstevens Date 2004-11-27 Time 05:16 Sent To B1
Notes
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) MORE INFORMATION IS REQUIRED. PERMIT
 APPLICATION STATES "INSTALL WATER HEATER
 ELECTRIC OUTLETS", BUT IT SEEMS THAT
 MORE WORK IS SHOWN ON THE PLANS. WITH
 THE ADDITION OF A SANITARY RISER DIAGRAM
 IT SEEMS THAT A BATHROOM IS BEING
 ADDED.
 ALSO IT SEEMS THAT A WASH MACHINE IS
 BEING ADDED TO THE HOUSE. WILL THE
 BATHROOM BE FRAMED IN OR IS IT
 EXISTING?
 2) SHT PL:1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) PLEASE SHOW ALL PIPE SIZES AND
 IDENTIFY ALL FIXTURES. SECTION 104.2.1
 B) TRAPS ARE REQUIRED AT THE SHOWER,
 THE LAV., AND THE WASH MACHINE. SECTION
 1002.1
 C) THE WASH MACHINE REQUIRES A
 STANDPIPE AND SHALL HAVE A CLEANOUT
 INSTALLED 4 FEET ABOVE THE FLOOR FOR
 ACCESS. SECTIONS 1002.1 & 708.10
 D) THE TWO 2" DRAINS ARE NOT VENTED,
 AND PIPED AS SUCH WILL BE AN "S" TRAP.
 SECTIONS 902.1 & 1002.3(5)
 E) ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SECTION
 909.1 (THE WASH MACHINE SHALL CONNECT
 DOWNSTREAM OF THE BATHROOM FIXTURES).
 3) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SECTION 104.2.1
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-01-04 Cont ID  
Sent By mmclean Date 2005-01-04 Time 16:29 Rev Time 0.00
Received By mmclean Date 2005-01-04 Time 16:29 Sent To I
Notes
2005-01-04 00:00:00OK FOR INTERIOR WORK.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-11-22 Cont ID  
Sent By mmclean Date 2004-11-22 Time 13:02 Rev Time 0.00
Received By mmclean Date 2004-11-22 Time 13:02 Sent To E
Notes
2004-11-22 00:00:00DENIED, NEED TO PROVIDE A COMPLETE FLOOR
 PLAN OF THE EXISTING AND REMODEL PLANS.
 CAN EITHER CONVERT APARTMENT BACK TO
 GARAGE OR MAKE IT APART OF THE MAIN
 STRUCTURE.