Plan Review Details - Permit 04110565
Plan Review Stops For Permit 04110565
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-11-19 Cont ID  
Sent By rbrown Date 2004-11-19 Time 15:08 Rev Time 0.00
Received By rbrown Date 2004-11-19 Time 15:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By rbrown Date 2004-11-12 Time 13:44 Rev Time 0.00
Received By rbrown Date 2004-11-12 Time 13:44 Sent To  
Notes
2004-11-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FBC 1504.1WIND RESISTANCE OF MODIFIED
 BITUMEN ROOFING SYSTEM.PAGE 15 OF THE
 SUBMITTED JOHN MANSVILLE MODIFIED
 BITUMEN ROOFING SYSTEM NOA# 01-0628.14
 STATES THAT THE MAXIMUM DESIGN PRESSURE
 FOR THE PROPOSED SYSTEM IS -52.5 PSF.
 THE DESIGN PRESSURE REQUIRED IS -80 PSF
 (REF: FIG. 9 OF RWDI WIND LOAD STUDY
 REPORT #03-1042 DATED 12/20/04
 SUBMITTED
 UNDER THE BUILDING PERMIT# 02040459).
 SUBMIT A PRODUCT APPROVAL FOR A ROOFING
 SYSTEM WITH A DESIGN PRESSURE OF -80
 PSF
 OR BETTER.IT IS NOTED THAT GENERAL
 LIMITATION #7, ON PAGE 22 OF THE NOA,
 ALLOWS ENHANCED UPLIFT PRESSURES AT
 CORNERS AND PERIMETER IF FASTENER
 DENSITIES ARE INCREASED.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-18 Cont ID  
Sent By csiegber Date 2004-11-18 Time 16:46 Rev Time 0.00
Received By csiegber Date 2004-11-18 Time 16:46 Sent To B
Notes
2004-11-18 00:00:00TO RB DESK/RESUB