2004-11-12 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| FBC 1504.1WIND RESISTANCE OF MODIFIED |
| BITUMEN ROOFING SYSTEM.PAGE 15 OF THE |
| SUBMITTED JOHN MANSVILLE MODIFIED |
| BITUMEN ROOFING SYSTEM NOA# 01-0628.14 |
| STATES THAT THE MAXIMUM DESIGN PRESSURE |
| FOR THE PROPOSED SYSTEM IS -52.5 PSF. |
| THE DESIGN PRESSURE REQUIRED IS -80 PSF |
| (REF: FIG. 9 OF RWDI WIND LOAD STUDY |
| REPORT #03-1042 DATED 12/20/04 |
| SUBMITTED |
| UNDER THE BUILDING PERMIT# 02040459). |
| SUBMIT A PRODUCT APPROVAL FOR A ROOFING |
| SYSTEM WITH A DESIGN PRESSURE OF -80 |
| PSF |
| OR BETTER.IT IS NOTED THAT GENERAL |
| LIMITATION #7, ON PAGE 22 OF THE NOA, |
| ALLOWS ENHANCED UPLIFT PRESSURES AT |
| CORNERS AND PERIMETER IF FASTENER |
| DENSITIES ARE INCREASED. |
| |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |
| E-MAIL: [email protected] |