Plan Review Details - Permit 04110260
Plan Review Stops For Permit 04110260
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-12-07 Cont ID  
Sent By btrobaug Date 2004-12-07 Time 12:19 Rev Time 0.50
Received By btrobaug Date 2004-12-07 Time 12:18 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-19 Cont ID  
Sent By btrobaug Date 2004-11-19 Time 10:58 Rev Time 0.50
Received By btrobaug Date 2004-11-19 Time 15:25 Sent To  
Notes
2004-11-19 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT SPECIFICATIONS FOR THE
 TRANSFER SWITCH FROM THE MFGR.
  
 2} SUBMIT LOAD CALCULATIONS FOR THE
 LOADS TO BE ENERGIZED BY THE GENERATOR.
  
 3} SUBMIT TWO CURRENT COPIES OF THE
 PROPERTY SURVEY INDICATING LOCATION OF
 THE GENERATOR AND RELATED EQUIPMENT, FOR
 ZONING REVIEW.
  
 4} PLEASE INCREASE THE VALUE ON THE
 APPLICATION TO INCLUDE ALL LABOR AND
 MATERIAL, INCLUDING COST OF THE
 GENERATOR AND RELATED EQUIPMEN PER
 104.6.5 FBC AND CWPB AMMENDMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-04 Cont ID  
Sent By csiegber Date 2004-11-04 Time 11:22 Rev Time 0.00
Received By csiegber Date 2004-11-04 Time 11:22 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-12-08 Cont ID  
Sent By mmclean Date 2004-12-08 Time 12:39 Rev Time 0.00
Received By mmclean Date 2004-12-08 Time 12:39 Sent To E
Notes
2004-12-08 00:00:00GENERATOR 3'X 6', 3FT FROM STRUCTURE.
 SIDE SETBACK IS OVER 22FT.