Plan Review Details - Permit 04110184
Plan Review Stops For Permit 04110184
Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2007-05-21 Cont ID  
Sent By rbrown Date 2007-05-21 Time 18:33 Rev Time 0.00
Received By rbrown Date 2007-05-21 Time 18:33 Sent To  
Notes
2007-05-21 18:44:17REVISION SUBMITTED ON 5/4/07 FOR MULLIONS AND SUBMITTAL
 FOR SGD AND SH WINDOW ENGINEERING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2007-03-16 Cont ID  
Sent By jwitmer Date 2007-03-16 Time 15:20 Rev Time 0.55
Received By jwitmer Date 2007-03-16 Time 15:20 Sent To PC
Notes
2007-03-16 15:21:15EXTERIOR WALL FRAMING AND CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2007-03-16 Cont ID  
Sent By jwitmer Date 2007-03-16 Time 14:33 Rev Time 0.55
Received By jwitmer Date 2007-03-16 Time 14:33 Sent To PC
Notes
2007-03-16 14:35:24REV # 6, 16'-0" OVERHEAD GARAGE DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2006-09-15 Cont ID  
Sent By jwitmer Date 2006-09-15 Time 10:02 Rev Time 0.55
Received By jwitmer Date 2006-09-15 Time 10:02 Sent To PC
Notes
2006-09-15 00:00:00TRASH CHUTE- OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2006-01-26 Cont ID  
Sent By shill Date 2006-01-26 Time 12:04 Rev Time 0.00
Received By shill Date 2006-01-26 Time 12:04 Sent To  
Notes
2006-01-26 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
 WINDOW SHOPS
  
 1.)THIS WAS SUBMITTED AS SHOP
 DRAWINGS.THE PRODUCTS YOU ARE USING
 ARE NOT THE SAME PRODUCTS AS THE
 APPROVED PERMIT PACKAGE.THIS IS A
 REVISION, REQUIRING REVIEW.A REVISION
 FEE HAS BEEN ADDED.WHEN RESUBMITTING,
 PLEASE SUBMIT AS A REVISION.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72, SB442.
  
 3.)EXPIRED NOAS SUBMITTED.PLEASE
 NOTE THAT THE EXPIRED NOAS BY THEMSELVES
 CANNOT BE USED TO SHOW CODE COMPLIANCE
 IF APPLYING FOR LOCAL PRODUCT APPROVAL.
  
 4.)FBC1601.2.1, THERE IS NO PROVISION
 IN THE CODE FOR A 1% WIND OVERSTRESS AS
 SHOWN FOR THE SMALL MISSILE IMPACT
 SINGLE HUNG WINDOWS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2006-01-11 Cont ID  
Sent By shill Date 2006-01-11 Time 13:34 Rev Time 0.00
Received By shill Date 2006-01-11 Time 13:34 Sent To  
Notes
2006-01-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 1.)PROVIDE A SIGNED, SEALED TRUSS
 PLACEMENT PLAN.
  
 2.)THE TRUSS ENGINEERING INDEX SHEET
 HAS A PHOTOCOPY OF A SIGNATURE.PROVIDE
 ORIGINAL SIGNED, SEALED TRUSS
 ENGINEERING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2005-12-16 Cont ID  
Sent By shill Date 2005-12-16 Time 17:39 Rev Time 0.00
Received By shill Date 2005-12-16 Time 17:39 Sent To  
Notes
2005-12-16 00:00:00****CORRECTIONS****
  
 SUBMITTALS; TENDON AND SUPPORT SHOPS AND
 CALCS
  
 BLDG 2, FL 3, 4 & ROOF
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A TITLE BLOCK IS REQUIRED,
 FAC61G15-23.003.MR. HAMID'S ADDRESS ON
 DBPE WEBSITE IS NOT THE ADDRESS ON THE
 PLAN, WHICH APPEARS TO BE FOR PTE.IF
 PTE IS PRACTICING ENGINEERING AND MR.
 HAMID IS THE INDIVIDUAL WHO IS SEALING
 THE DOCUMENT THROUGH THE COMPANY, THE
 INFORMATION FOR PTE SERVES AS THE TITLE
 BLOCK AND IS REQUIRED TO HAVE THE
 CERTIFICATE OF AUTHORIZATION FOR THE
 FIRM PRINTED ON THE PLAN.IF MR. HAMID
 IS SEALING THE PLAN INDIVIDUALLY, HIS
 TITLE BLOCK WITH ALL INFORMATION
 REQUIRED BY FAC61G15-23.002 IS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-12-16 Cont ID  
Sent By shill Date 2005-12-16 Time 17:34 Rev Time 0.00
Received By shill Date 2005-12-16 Time 17:34 Sent To  
Notes
2005-12-16 00:00:00SHORING/RESHORE LETTERS
 4TH FL SHORING, 2ND & 3RD FLOOR RESHORE
 2ND FLOOR SHORING
 ROOF SHORING, 2ND & 3RD FLOOR RESHORE
 3RD FLOOR SHORING, 1ST & 2ND FLOOR
 RESHORE

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-09-08 Cont ID  
Sent By jwitmer Date 2005-09-08 Time 12:00 Rev Time 0.33
Received By jwitmer Date 2005-09-08 Time 11:59 Sent To PC
Notes
2005-09-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110184
 ADD: 3900 N FLAGLER BLDG# 2
 CONT: THE WEITZ CO
 TEL: (561)307-1811
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SHORING LETTERS
 ACTION: DENIED
  
 THRESHOLD BUILDINGS, REQUIRES (3) OF ALL
 DOCUMEENTS WHEN SUBMITING TO THE CITY.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-08-28 Cont ID  
Sent By jwitmer Date 2005-08-28 Time 10:35 Rev Time 0.33
Received By jwitmer Date 2005-08-28 Time 10:35 Sent To PC
Notes
2005-08-28 00:00:00SUBMITTALS :
 SHORING
 RESHORING PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-07-26 Cont ID  
Sent By jwitmer Date 2005-07-26 Time 07:21 Rev Time 0.50
Received By jwitmer Date 2005-07-26 Time 07:12 Sent To  
Notes
2005-07-26 00:00:00SURVEYBLDG #2

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-06-17 Cont ID  
Sent By jwitmer Date 2005-06-17 Time 13:43 Rev Time 0.55
Received By jwitmer Date 2005-06-17 Time 13:42 Sent To  
Notes
2005-06-17 00:00:00REV # 3 PILING/ FOUNDATION, SOILS REPORT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-05-06 Cont ID  
Sent By jwitmer Date 2005-05-06 Time 10:27 Rev Time 2.22
Received By jwitmer Date 2005-05-03 Time 13:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-11 Cont ID  
Sent By jwitmer Date 2005-02-11 Time 15:04 Rev Time 2.22
Received By jwitmer Date 2005-02-11 Time 15:04 Sent To  
Notes
2005-02-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110184
 ADD: 3900 N FLAGLER BLDG II
 CONT:MANHATTEN
 TEL: (561)719-3539
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 COMMENTS FROM BLDG# 1 PERMIT 04110183
 ARE COMMON TO ALL BUILDINGS.
 3 SETS OF PRODUCT APPROVLA REQUIRED FOR
 PROJECT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-10 Cont ID  
Sent By jwitmer Date 2004-12-10 Time 11:22 Rev Time 6.00
Received By jwitmer Date 2004-12-10 Time 11:21 Sent To  
Notes
2004-12-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110184
 ADD: 3900 N FLAGLER DRBLDG II
 CONT: MANHATTEN CONSTRUCTION
 TEL: (813)927-0209
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1) NOTE NOT DISCUSSED UNDER BLDG# 1, IS
 SITE AMENITIES, GAURD HOUSE, WALLS,
 WALKWAYS, ETC... REQUIRE A SEPERATE
 PERMIT. ASSUMED SEAWALL IS ALREADY
 BUILT, IF NOT A SEPERATE PERMIT IS ALSO
 REQUIRED, SEE CITY CODE FOR REQUIRED
 SEAWALL APPROVALS.
  
 2) AT PARKING SPACES COMPLYING WITH
 11-4.1.2(5)(B), PROVIDE MINIMUM VERTICAL
 CLEARENCE OF 98" AT PARKING SPACES AND
 ALONG AT LEAST ONE VEHICLE ACCESS ROUTE
 TO SUCH SPACES FROM SITE ENTRANCES AND
 EXITS.
 PROVIDE THE MINIMUM CLEARENCE OF 114"
 AT ACCESSIBLE PASSENGER LOADING ZONES &
 AT LEAST 1 VEHICLE ACCESS ROUTE TO SUCH
 AREAS FROM SITE ENTRANCES & EXITS.
  
 3) COMMENTS FROM BLDG (1) 1-33 ALSO
 PERTAIN TO THIS REVIEW AS WELL.
  
 4) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE AN ACCESSIBLE PATH TO EACH OF
 THE ELEVATORS FROM THE HANDICAPPED SPACE
 IN THE PARKING GARAGE.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2007-02-12 Cont ID  
Sent By jleahy Date 2007-02-12 Time 16:24 Rev Time 1.00
Received By jleahy Date 2007-02-12 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2006-12-22 Cont ID  
Sent By jleahy Date 2006-12-22 Time 06:47 Rev Time 0.45
Received By jleahy Date 2006-12-22 Time 06:46 Sent To  
Notes
2006-12-22 06:48:24PAGE E-501

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2006-10-31 Cont ID  
Sent By jleahy Date 2006-10-31 Time   Rev Time 1.00
Received By jleahy Date 2006-10-31 Time 16:24 Sent To  
Notes
2006-10-31 16:23:46NEED TO SHOW SIZE OF CONTROLLERS NOT SHOWN ON DRAWINGS
2006-10-20 07:07:47ELECTRICAL RISER/ REVISIONS GIVEN TO JAKE LEAHY FOR
 REVIEW.

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2006-06-24 Cont ID  
Sent By dpalmer Date 2006-06-24 Time 10:15 Rev Time 0.00
Received By dpalmer Date 2006-06-24 Time 10:02 Sent To FIRE
Notes
2006-06-24 00:00:00REV FOR UNIT LAYOUT, REV #5.
 ROUTED TO FIRE.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2006-06-09 Cont ID  
Sent By dpalmer Date 2006-06-09 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2006-06-09 Time 16:33 Sent To PC
Notes
2006-06-09 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE COMMENTS FROM
 PREVIOUS REVIEW.
 PLEASE SEE CIRCUITING FOR SD'S ON
 MUTIPLE CIRCUITS WHEN REQUIRED TO BE
 WIRED INLINE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 8 Status N Date 2006-06-02 Cont ID  
Sent By dpalmer Date 2006-06-02 Time 08:01 Rev Time 0.00
Received By dpalmer Date 2006-06-02 Time 08:01 Sent To  
Notes
2006-06-02 00:00:00NO ELECTRICAL PLANS SUBMITTED. REVISION
 COVER SHEET IS CHECKED OFF FOR
 ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-05-17 Cont ID  
Sent By dpalmer Date 2006-05-17 Time 12:02 Rev Time 0.00
Received By dpalmer Date 2006-05-17 Time 12:02 Sent To  
Notes
2006-05-17 00:00:00******** UNSAT *********
  
  
 1) NOTE: PLEASE SEE COMMENTS FROM
 PREVIOUS REVIEW AS THE SD'S ARE STILL
 SHOWN BEING WIRED TO MORE THAN ONE
 CIRCUIT IN A SINGLE UNIT??
 PLEASE KNOW, THE SD'S ARE REQUIRED TO
 WIRED "INLINE", WHICH AS SHOWN ON
 MULTIPLE CIRCUITS IS NOT PERMITTED.
 THESE MAY BE WIRED TO THE ARC FAULT
 PROTECTED BEDRM CIRCUIT, HOWEVEER THESE
 CAN ONLY BE ON ONE CIRCUIT.
 NFPA-72 8-1.4.1.6.2,
  
 2) NOTE: PLEASE SEE SEC'S HAVE NOW BEEN
 DOWN SIZED TO 3/0'S FOR ONE FIRE PUMP
 SERVICE, AND 4/0'S FOR THE OTHER.
 PLEASE SEE THAT THE SEC'S SHALL ME SIZED
 ACCORDINGLY TO THE OCP, HP, AND THE SIZE
 OF THE FPC.
 PLEASE SEE 310.16, AS 3/0'S ARE ONLY
 RATED AT 200A'S AND THE 4/0'S ARE ONLY
 RATED FOR 225A'S. PLEASE SEE
 240.4,310.16.
 THE OCP SHOWN ON MAIN IS 250A'S.
 (LOOCKED ROTOR SHOULD BE SET AND PART OF
 THE FPC AND MUST BE 6X THE FLA'S.
 695.4/695.5
  
 ** NOTE **
 PLEASE KNOW, IT HAS COME TO THE
 ATTENTION OF THIS OFFICE THAT SOME OF
 THE SLIDING GLASS DOORS ON PLANS ARE
 ACTUALLY "FIXED GLASS PANELS" PLEASE SEE
 210.52 AS "FIXED GLASS" IS CONSIDERED
 WALL SPACE.
 PLEASE SEE PLANS IN MANY PLACES STILL
 INDICATE MANY OF THESE AS SLIDING GLASS
 DOORS?? AS REVIEWED ON PREVIOUS PLANS.
 ANY INSTALLATION OF FIXED GLASS PANELS,
 WILL BE VERIFIED IN THE FIELD AND PLANS
 SHALL BE REVISED ACCORDING TO ACTUAL
 WALL SPACE CONSTRUCTED.
  
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2006-01-23 Cont ID  
Sent By dpalmer Date 2006-01-23 Time 15:08 Rev Time 0.00
Received By dpalmer Date 2006-01-23 Time 15:08 Sent To M
Notes
2006-01-23 00:00:00SUBMITTIAL FOR DRY-IN OF BLDG,NOT FOR
 ELEC REVIEW.

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2005-12-30 Cont ID  
Sent By dpalmer Date 2005-12-30 Time 15:09 Rev Time 0.00
Received By dpalmer Date 2005-12-30 Time 15:09 Sent To  
Notes
2005-12-30 00:00:00APPLIANCE SUBMITTIALS NOT NEED FOR
 REVIEW.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-12-09 Cont ID  
Sent By dpalmer Date 2005-12-09 Time 15:36 Rev Time 0.00
Received By dpalmer Date 2005-12-09 Time 15:36 Sent To  
Notes
2005-12-09 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE SEE NOTE ON ALL PLANS
 INDICATE SD'S ARE TO BE WIRED TO
 HALL/FOYER CIRCUITS, HOWEVER CIRCUITING
 ON PLANS WAS NOT CHANGED.
 PLEASE BE SURE THAT IF THESE SD'S ARE
 NOW GOING TO CHANGE TO HALL/FOYER LTS,
 THEN THESE CIRCUITS WILL ALSO NOW BE
 REQUIRED TO BE ARC FAULT.210.12
 PLEASE ALSO SEE CIRCUITING FOR SD'S HAS
 GONE BACK TO THE SD'S OF THE SAME UNIT
 BEING WIRED TO MORE THAN ONE CIRCUIT.
 SMOKE DETECTORS ARE REQUIRED TO BE WIRED
 INLINE AND THIS WILL NOT WORK ON MORE
 THAN ONE CIRCUIT.
 PLEASE ADJUST ALL CIRCUITING.
  
 2)NOTE: PLEASE SEE FIRE PUMP
 FEEDERS/SEC'S FROM THE FPL TRANSFORMER
 TO THE METER AND FROM THE METER TO THE
 FIRST MEANS OF DISCONNECT IS NOTED AS
 HAVING AN EQUIPMENT GROUNDING CONDUCTOR.
 PLEASE REVISE SCHEDULE.
 THESE ARE ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SEE 302 WHICH DOES NOT
 INDICATE ANY REVISONS, HOWEVER TITLE
 BLOCK DOES INDICATE THIS.
  
 4)NOTE: PLEASE SEE 620.23 A SEPARATE
 BRANCH CIRCUIT SHALL SUPPLY THE MACHINE
 ROOM OR CONTROL ROOM/MACHINERY SPACE OR
 CONTROL SPACE LIGHTING AND
 RECEPTACLE(S).
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-25 Cont ID  
Sent By dpalmer Date 2005-04-25 Time 18:27 Rev Time 4.00
Received By dpalmer Date 2005-04-25 Time 18:27 Sent To  
Notes
2005-04-25 00:00:00**REDLINED **
  
 1) NO EQUIPMENT GROUNDING CONDUCTORS
 FROM TRANSFORMER TO METER OR METER TO
 FIRST MEANS OF DISCONNECT.
 250.6,250.24
 EQUIPMENT GROUNDING CONDUCTORS SHOWN TO
 FIRE PUMP SHALL NOT BE INSTALLED.
  
 ALL 12 ROLLS STAMPED FOR ELECTRICAL.
 NO REVISION NEEDED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-14 Cont ID  
Sent By dpalmer Date 2005-02-14 Time 09:53 Rev Time 1.25
Received By dpalmer Date 2005-02-14 Time 09:53 Sent To  
Notes
2005-02-14 00:00:00*** NOTES ***
 THIS IS FOR BLDGS: 1,2,5 AND 6.
 THIS COMMENT DOES NOT AFFECT BLDGS: 3 OR
 4.
  
 1)NOTE:PLEASE SEE NFPA-20 IN REFERENCE
 TO FIRE PUMP ELECTRICAL SERVICE
 LOCATION.
 PLEASE SEE SERVICE SHALL BE LOCATED AS
 NOT TO BE AFFECTED IN CASE OF FIRE /
 EXPLOSION ETC WITH MAIN ELECTRICAL
 SERVICE.
 THIS FIRE PUMP SERVICE SHOULD STILL BE
 LOCATED IN CLOSE PROXIMITY TO MAIN
 ELECTRICAL RM.
 PLEASE SEE NFPA-20, 6.2.1
 6-2.1 SERVICE.
 WHERE POWER IS SUPPLIED BY A SERVICE, IT
 SHALL BE LOCATED AND ARRANGED TO
 MINIMIZE THE POSSIBILITY OF DAMAGE BY
 FIRE FROM WITHIN THE PREMISES AND
 EXPOSING HAZARDS.
 NFPA-70 695
 THE CONNECTION SHALL BE LOCATED AND
 ARRANGED SO AS TO MINIMIZE THE
 POSSIBILITY OF DAMAGE BY FIRE FROM
 WITHIN THE PREMISES AND FROM EXPOSING
 HAZARDS.
 MOST IMPORTANT IN 695.3(A)(2) IS THE
 REQUIREMENT THAT A FIRE IN ONE SOURCE
 NOT AFFECT THE RELIABILITY OF ANOTHER
 SOURCE.
  
 THIS WAS NOT IN ORIGINAL REVIEW NOTES.
  
 PLEASE MAKE THE ABOVE CHANGES AND SUBMIT
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CONTACTING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-01 Cont ID  
Sent By dpalmer Date 2004-12-01 Time 14:46 Rev Time 0.00
Received By dpalmer Date 2004-11-23 Time 15:49 Sent To  
Notes
2004-12-01 00:00:00PLEASE SEE NOTES UNDER 04110182
2004-11-30 00:00:00NOTES TO FOLLOW

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2005-02-23 Cont ID  
Sent By mamini Date 2005-02-23 Time 11:20 Rev Time 0.00
Received By mamini Date 2005-02-23 Time 11:20 Sent To  
Notes
2005-02-23 00:00:00N:
  
 1. SEE PERMIT# 05021226 FOR
 UNDERGROUND UTILITIES AND SITE WORK.
 THIS PERMIT INCLUDES BUILDING PADS
 PREPARATION FOR ALL BUILDINGS.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-11-15 Cont ID  
Sent By mamini Date 2004-11-15 Time 16:10 Rev Time 0.00
Received By mamini Date 2004-11-15 Time 15:50 Sent To  
Notes
2004-11-15 00:00:00PASSED WITH PROVISOS:
  
 1. EROSION AND SEDIMENTATION CONTROL
 DEVICES SHALL BE IN PLACE PRIOR TO
 BEGINNING CLEARING OR GRUBBING,
 DEMOLITION, OR OTHER SUCH CONSTRUCTION
 ACTIVITIES.THE DEVICES SHALL BE
 INSTALLED, MONITORED, AND MAINTAINED IN
 ACCORDANCE WITH ALL APPLICABLE FEDERAL,
 STATE, AND LOCAL REQUIREMENTS.
  
 2. WORK WITHIN PUBLIC R.O.W REQUIRES A
 PERMIT FROM PUBLIC UTILITIES AND
 ENGINEERING, PLEASE SUBMIT M.O.T PLANS
 ALSO AT THE TIME OF APPLICATION ATT:
 WINDEL PALMER, 494-1086.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2006-07-21 Cont ID  
Sent By mwennerg Date 2006-07-21 Time 10:35 Rev Time 0.00
Received By mwennerg Date 2006-07-21 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status N Date 2006-06-08 Cont ID  
Sent By mwennerg Date 2006-06-08 Time 13:39 Rev Time 0.00
Received By mwennerg Date 2006-06-08 Time 13:39 Sent To  
Notes
2006-06-08 00:00:00REVISIONS DATED 2/13/06
  
 NO NEW COMMENTS FROM LAST FIRE REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2006-01-26 Cont ID  
Sent By nmccray Date 2006-01-26 Time 12:34 Rev Time 0.00
Received By nmccray Date 2006-01-26 Time 12:34 Sent To I
Notes
2006-01-26 00:00:00PLEASE SEE NOTES UNDER PERMIT # 04110182

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-12-13 Cont ID  
Sent By nmccray Date 2005-12-13 Time 14:33 Rev Time 0.00
Received By nmccray Date 2005-12-13 Time 14:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-02-28 Cont ID  
Sent By nmccray Date 2005-02-28 Time 14:55 Rev Time 0.00
Received By nmccray Date 2005-02-28 Time 14:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By mcarsill Date 2004-12-15 Time 08:12 Rev Time 0.00
Received By mcarsill Date 2004-12-15 Time 08:11 Sent To  
Notes
2004-12-15 00:00:001. PLEASE INDICATE HOW LONG THE
 SALES TRAILER WILL BE ON-SITE.
  
 2. SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT
 DURING CONSTRUCTION.
  
 3. WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING, AND AFTER
 CONSTRUCTION.
  
 4. WILL THE GUARDHOUSE BE STAFFED
 FULL OR PART TIME. IF PART TIME,
 WHAT PROVISIONS HAVE BEEN MADE FOR
 FIRE AND PARAMEDICAL ACCESS.
  
 5. ELECTONIC SWITCHES, CHAIN AND
 LOCKS REQUIRED ON FIRE LINE
 BACKFLOW DEVICES.
  
 6. ALL NEW STAIRS AND RAMPS SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 7. BUILDING ADDRESSES REQUIRED.
  
 8. TACTILE SIGANAGE REQUIRED AT ALL
 EXITS.
  
 9. PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 10. KNOX-BOXES WILL BE REQUIRED.
  
 11. A TWO-HOUR FIRE SEPARATION IS
 REQUIRED BETWEEN THE PARKING AREAS
 AND OTHER PORTIONS OF THE BUILDING
 UNLESS AN EXCEPTION OF NFPA 88A, THE
 STANDARD FOR PARKING STRUCTURES EXISTS.
 OPENING PROTECTIVES SHALL BE AT LEAST
 1 1/2 HOURS.
  
 12. ALL TRASH CHUTES TO COMPLY WITH
 NFPA 82, INCINERATORS, WASTE AND LINEN
 HANDLING SYSTEMS AND EQUIPMENT.
  
 13. ALL BUILDINGS THREE OR MORE STORIES
 IN HEIGHT SHALL BE FIRE SPRINKLER
 PROTECTED IN ACCORDANCE WITH FS 553.895
 (2).
  
 14. STANDPIPE SYSTEMS ARE REQUIRED
 IN ALL BUILDINGS THREE STORIES OR
 THIRTY FEET IN HEIGHT.
  
 15. HOW WILL THE SEPARATE BUILDINGS
 BE IDENTIFIED. WILL THEY BE
 ADDRESSED DIFFERENTLY.
  
 16. 2 1/2 TO 1 1/2 REDUCERS ARE
 REQUIRED AT ALL HOSE VALVE LOCATIONS.
  
 17. FIRE SERVICE MAINS SHOULD BE LOOPED
 WHENEVER POSSIBLE.
  
 18. LOCKING KNOX-BOX CAPS ARE REQUIRED
 ON ALL NEW FIRE DEPARTMENT CONNECTIONS.
  
 19. ALL FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 20. ELEVATOR WARNING SIGNS REQUIRED.
  
 21. EXIT SIGN PLACEMENT SHALL NOT
 EXCEED 100 FEET.
  
 22. ADDITIONAL EXIT SIGNS ARE NEEDED
 IN THE GARAGE LEVEL.
  
 23. PLEASE NOTE ON THE PLANS THAT
 SMOKE DETECTORS SHALL BE PLACED A
 MINIMUM OF THREE FEET FROM A/C
 DIFFUSERS.
  
 24. PLEASE INDICATE ALL LOCATIONS OF
 PORTABLE FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2007-05-21 Cont ID  
Sent By shill Date 2007-05-21 Time 16:31 Rev Time 0.00
Received By shill Date 2007-05-21 Time 16:31 Sent To B
Notes
2007-05-21 16:31:48TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 14:23 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 14:22 Sent To B
Notes
2007-04-16 14:23:10TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 11:39 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 11:39 Sent To  
Notes
2007-02-08 11:40:20TO "COMM" BD#43

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 10:13 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 10:13 Sent To E
Notes
2006-12-18 10:13:40TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 17:56 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 17:56 Sent To E
Notes
2006-10-10 17:56:40TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2006-07-19 Cont ID  
Sent By adarroug Date 2006-07-19 Time 09:53 Rev Time 0.00
Received By adarroug Date 2006-07-19 Time 09:53 Sent To FIRE
Notes
2006-07-19 00:00:00TO "F" BOX/REV
 7/19/06--CONTRACTOR PULLED PLANS FROM
 REVIEW PROCESS--SEE FRONT SCREEN NOTE.
 ADARROUGH
  

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2006-06-26 Cont ID  
Sent By adarroug Date 2006-06-26 Time 10:30 Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 10:30 Sent To M
Notes
2006-06-26 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 15:37 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 15:37 Sent To E
Notes
2006-06-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2006-06-05 Cont ID  
Sent By adarroug Date 2006-06-05 Time 14:23 Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 14:23 Sent To M
Notes
2006-06-05 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 16:07 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 16:07 Sent To E
Notes
2006-05-26 00:00:00TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-05-04 Time 10:33 Rev Time 0.00
Received By adarroug Date 2006-05-04 Time 10:33 Sent To  
Notes
2006-05-24 00:00:00TO "COMM" BD#64-3 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2006-05-04 Cont ID  
Sent By adarroug Date 2006-05-04 Time 13:41 Rev Time 0.00
Received By adarroug Date 2006-05-04 Time 13:41 Sent To  
Notes
2006-05-04 00:00:00TO "COMM" BD#48-3 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 11:52 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 11:52 Sent To B
Notes
2006-04-21 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2006-04-14 Cont ID  
Sent By adarroug Date 2006-04-14 Time 11:07 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 11:07 Sent To  
Notes
2006-05-05 00:00:00TO "COMM" BD#38-3 REV'S
2006-04-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2006-01-18 Cont ID  
Sent By adarroug Date 2006-01-18 Time 14:43 Rev Time 0.00
Received By adarroug Date 2006-01-18 Time 14:43 Sent To E
Notes
2006-01-18 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 16:49 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 16:49 Sent To E
Notes
2005-12-29 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 15:56 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 15:56 Sent To B
Notes
2005-12-29 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 15:55 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 15:55 Sent To B
Notes
2005-12-29 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2005-12-13 Cont ID  
Sent By adarroug Date 2005-12-13 Time 11:00 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 11:00 Sent To B
Notes
2005-12-13 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-11-16 Cont ID  
Sent By adarroug Date 2005-11-16 Time 16:07 Rev Time 0.00
Received By adarroug Date 2005-11-16 Time 16:07 Sent To B
Notes
2005-11-16 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 15:11 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 15:11 Sent To B
Notes
2005-09-29 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-09-19 Cont ID  
Sent By adarroug Date 2005-09-19 Time 15:32 Rev Time 0.00
Received By adarroug Date 2005-09-19 Time 15:32 Sent To  
Notes
2005-09-22 00:00:00TO "COMM" BD#1/PLANS ON RACK/4 ROLLS
2005-09-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 18:36 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 18:36 Sent To B
Notes
2005-09-08 00:00:00TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 11:15 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 11:15 Sent To B
Notes
2005-08-30 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-08-17 Cont ID  
Sent By adarroug Date 2005-08-17 Time 10:36 Rev Time 0.00
Received By adarroug Date 2005-08-17 Time 10:36 Sent To B
Notes
2005-08-17 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 09:52 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 09:52 Sent To B
Notes
2005-08-09 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-07-13 Cont ID  
Sent By adarroug Date 2005-07-13 Time 10:05 Rev Time 0.00
Received By adarroug Date 2005-07-13 Time 10:05 Sent To B
Notes
2005-07-13 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 15:58 Rev Time 0.00
Received By shill Date 2005-06-10 Time 15:58 Sent To  
Notes
2005-06-10 00:00:00WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-06-08 Cont ID  
Sent By mjacobs Date 2005-06-08 Time 08:07 Rev Time 0.00
Received By mjacobs Date 2005-06-08 Time 08:07 Sent To ENG
Notes
2005-06-08 00:00:00TO 'MAMINI' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-12 Cont ID  
Sent By adarroug Date 2005-05-12 Time 14:00 Rev Time 0.00
Received By adarroug Date 2005-05-12 Time 14:00 Sent To B
Notes
2005-05-12 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-27 Cont ID  
Sent By adarroug Date 2005-04-27 Time 14:06 Rev Time 0.00
Received By adarroug Date 2005-04-27 Time 14:06 Sent To B
Notes
2005-04-27 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-26 Cont ID  
Sent By ptjomsto Date 2005-01-26 Time 15:02 Rev Time 0.00
Received By ptjomsto Date 2005-01-26 Time 15:02 Sent To  
Notes
2005-01-26 00:00:00SUBMITTAL TO NEIL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 11:23 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 11:23 Sent To  
Notes
2005-01-20 00:00:00TO "COMM BD#61/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-31 Cont ID  
Sent By pkrauss Date 2004-12-31 Time 09:28 Rev Time 0.00
Received By pkrauss Date 2004-11-05 Time 10:46 Sent To  
Notes
2004-11-05 00:00:00TO COMM BD#

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2007-03-08 Cont ID  
Sent By rregueir Date 2007-03-08 Time 09:24 Rev Time 0.00
Received By rregueir Date 2007-03-08 Time 09:18 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2006-06-29 Cont ID  
Sent By hmoser Date 2006-06-29 Time 10:19 Rev Time 0.00
Received By hmoser Date 2006-06-29 Time 09:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2006-06-20 Cont ID  
Sent By hmoser Date 2006-06-20 Time 10:18 Rev Time 0.00
Received By hmoser Date 2006-06-20 Time 10:18 Sent To  
Notes
2006-06-20 00:00:00PLAN DENIED
 PLEASE PROVIDE ENERGY CALCULATIONS AND
 NANUAL J WITH REVISIONS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2006-06-19 Cont ID  
Sent By hmoser Date 2006-06-19 Time 14:05 Rev Time 0.00
Received By hmoser Date 2006-06-19 Time 14:05 Sent To  
Notes
2006-06-19 00:00:00PERMIT NUMBER 04110184 IS FOR BUILDING 2
 PLAN REVISION ARE FOR BUILDING 4,5,6
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-06-06 Cont ID  
Sent By tgordon Date 2006-06-06 Time 09:30 Rev Time 1.00
Received By tgordon Date 2006-06-06 Time 09:30 Sent To  
Notes
2006-06-06 00:00:00MECH. REVISION TO PAGE M-203.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-01-03 Cont ID  
Sent By pkrauss Date 2006-01-03 Time 15:29 Rev Time 0.00
Received By pkrauss Date 2006-01-03 Time 15:21 Sent To  
Notes
2006-01-03 00:00:00DENIED: PERMIT 04110184
 PLANS INDICATE VE FOR VARIOUS AHU'S TO A
 LESSER TONNAGE/BTU'S.ENERGY &MANUAL
 J CALCULATIONS HAVE NOT BEEN REVISED.
 PLEASE CLARIFY MANUFACTURER REQUIREMENT
 FOR SIZING OF THE LINE SETS.
  
 PLANS INDICATE THE FOLLOWING CHANGES:
 PLAN SHEET M-201 UNIT A1
 AHU-1 (2 TON) REPLACING AHU-2 (2.5 TON)
 AHU-5 (4 TON) REPLACING AHU-6 (5 TON)
  
 PLAN SHEET M203 UNIT C2
 AHU-1 (2 TON) REPLACING AHU-2 (2.5 TON)
 AHU-2 (2.5 TON) REPLACING AHU-3 (3 TON)
  
 PLAN SHEET M205 UNIT C3
 AHU-4 (3.5 TON) REPLACING AHU-5 (4 TON)
 AHU-7 (1.5 TON ) REPLACING AHU-1 (2 TON)
  
 PLAN SHEET M206 UNIT A4
 AHU-1 (2 TON) REPLACING AHU-2 (2.5 TON)
 AHU-5 (4 TON) REPLACING AHU-6 (5 TON)
  
 PLAN SHEET M208UNITS E5 & D-5
 AHU-1 (2 TON) REPLACING AHU-2 (2.5 TON)
 AHU-3 (3 TON) REPLACING AHU-4 (3.5 TON)
 AHU-7 (1.5 TON)REPLACING AHU-1(2 TON)
  
 PLAN SHEET M210 UNITS F6, E6, & D6
 AHU-1 (2 TON) REPLACING AHU-2 (2.5 TON)
 AHU-3 (3 TON) REPLACING AHU-4 (3.5 TON)
 AHU-7 (1.5 TON) REPLACING AHU-1 (2 TON)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-05-20 Cont ID  
Sent By pkrauss Date 2005-05-20 Time 13:55 Rev Time 0.40
Received By pkrauss Date 2005-05-20 Time 13:54 Sent To  
Notes
2005-05-20 00:00:00SEE COMMENTS ON PERMIT 04110183

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-02-17 Cont ID  
Sent By pkrauss Date 2005-02-17 Time 10:51 Rev Time 0.20
Received By pkrauss Date 2005-02-17 Time 10:51 Sent To  
Notes
2005-02-17 00:00:00DENIED:BUILDING #2
 1.AS PER CONVERSATION WITH JIM
 MULLENS, DRYER SUBMITTAL TO BE CHANGED
 AND THE PLANS WILL BE REVISED DELETING
 THE BOOSTER FANS INSTALLED IN THE DRYER
 EXHAUST DUCT.SPECIFIC DRYERS ARE TO BE
 INSTALLED BY FINAL INSPECTION.
  
 2.PLAN SHEET M203 THE TRASH CHUTE ROOM
 DOES NOT INDICATE A CO SENSOR AS
 REUQIRED PER PREVIOUS REVIEW.
  
 3.PLEASE NOTE, IN THE RESIDENTIAL
 UNITS AS WELL AS COMMON AREAS, SYSTEMS
 THAT HAVE A DESIGN CAPACITY TO PRODUCE
 GREATER THAN 2,000 CFM, DUCT SMOKE
 DETECTORS WELL BE REQUIRED IN THE SUPPLY
 AIR DUCT.AS AN ALTERNATE TO THE DUCT
 SMOKE DETECTOR, UPON ACTIVATION OF AN
 AREA DUCT SMOKE DECTECTOR, THE A/C UNIT
 WILL SHUT DOWN.2001 FBC(M)606.2.1,
 606.2.2, AND 606.4.
  
 4.FAN SHUTDOWN SHALL HAVE NOTIFICATION
 PER 2001 FBC(M) 606.4.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-31 Cont ID  
Sent By pkrauss Date 2004-12-31 Time 09:27 Rev Time 0.30
Received By pkrauss Date 2004-12-31 Time 09:27 Sent To  
Notes
2004-12-31 00:00:00SEE COMMENTS UNDER PERMIT 04110182

Review Stop P PLUMBING
Rev No 7 Status F Date 2006-06-19 Cont ID  
Sent By kstevens Date 2006-06-19 Time 13:08 Rev Time 0.00
Received By kstevens Date 2006-06-19 Time 13:08 Sent To  
Notes
2006-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 REVISION DENIED, SUBMIT SHTS P206 & P208
 UNDER THE CORRECT PERMIT NUMBER.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status F Date 2006-06-19 Cont ID  
Sent By kstevens Date 2006-06-19 Time 11:10 Rev Time 0.00
Received By kstevens Date 2006-06-19 Time 11:10 Sent To  
Notes
2006-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 REVISION DENIED. SHT P208 SHALL BE
 SUBMITTED FOR REVISION UNDER THE CORRECT
 PERMIT NUMBER ONLY. (04110183)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-12-23 Cont ID  
Sent By kstevens Date 2005-12-23 Time 10:46 Rev Time 0.00
Received By kstevens Date 2005-11-15 Time 18:50 Sent To  
Notes
2005-12-23 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHTS P201, P205, P206, P207, P208,
 209, & 210 SHALL BE SUBMITTED FOR
 REVISION UNDER THE APPROPRIATE PERMIT
 NUMBER FOR THOSE SHEETS. SECTION
 104.2.1.
 2. SHTS P205 & 209 REVISION REQUIRED FOR
 THE ARCHITECTURAL SHEETS SHOWING THE
 DELETION OF THE SCUPPERS. SEE COMMENT #1
 FROM LAST REVISION SUBMITTAL (6-23-5).
 3. SHT P210 LEVEL 2-4. LEVEL 2 IS
 DIFFERENT THAN LEVELS 3 & 4. REVISE
 SEPARATELY. INDICATE UNIT DESIGNATION ON
 EACH SHEET. SECTION 104.2.1.
 - E6 OPP. REVISION REQUIRED FOR THE
 FLOOR PLAN. ONLY E6 FLOOR PLAN HAS BEEN
 REVISIED. IF FLOOR PLAN NOT REVISED,
 SUBMIT A RISER DIAGRAM TO REFLECT
 UNCHANGED FLOOR PLAN. SECTION 104.3.1.1.
 - G6 TUB NOT VENTED. WHAT RISER HAS BEEN
 REVISED TO REFLECT THIS CHANGE?
 - H6 INDICATE RISER NUMBER TO REFLECT
 CHANGE.
 - K6 2ND FLOOR INDICATE RISERS FOR
 THESE CHANGES.
 - F6 3RD & 4TH FLOORS
 4. SHT P301 WHERE IS WATER HEATER DRAIN
 PAN - WASTE WATER DETAIL? HAVE THE WATER
 HEATERS BEEN DELETED? DETAIL TO BE SHOWN
 ON REVISION.
 - WHERE IS RISERS SAN/6 & SAN/9? THESE
 ARE STILL SHOWN ON THE FLOOR PLANS.
 - SAN/7 DOES NOT REFLECT THE FLOOR
 PLAN.
 - UNIT B-2 MASTER BATH SANT FITTINGS
 SHALL BE INSTALLED TO GUIDE SEWAGE AND
 WASTE IN THE DIRECTION OF FLOW. SECTION
 706.3.
 - UNIT E-5/6 MASTER BATH, SHOW ALL PIPE
 SIZES. MAX 4FU ON 2" WET VENT. SECTION
 104.2.1 AND TABLE 909.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-06-18 Cont ID  
Sent By pschmitz Date 2005-06-18 Time 09:39 Rev Time 0.00
Received By pschmitz Date 2005-06-18 Time 09:39 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-05-14 Cont ID  
Sent By kstevens Date 2005-05-14 Time 18:45 Rev Time 0.33
Received By kstevens Date 2005-05-14 Time 18:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-02-09 Cont ID  
Sent By kstevens Date 2005-02-09 Time 10:11 Rev Time 0.50
Received By kstevens Date 2005-02-09 Time 10:11 Sent To  
Notes
2005-02-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEW:
 1) A TITLE BLOCK MUST CONTAIN THE
 FOLLOWING INFORMATION.
 61G1-16.004(2)(6)
 THE FIRM LICENSE NUMBER, AND THE
 PRINTED
 NAME OF THE PERSON SEALING THE
 DOCUMENT.
 ALSO THE CERTIFICATE OF AUTHORIZATION
 OF
 THE FIRM. SEE SHEETS L1 THRU L6 AND
 SHEETS I-1 THRU I-3.
 **************NEW COMMENT*************
 1B) SHT P202 BUILDING 1 STORM RISER
 DIAGRAM. MAXIMUM 730 SF @ 1% SLOPE. 4"
 PIPE REQUIRED ON THE HORIZONTAL PIPING
 OR INDICATE 4% SLOPE. INDICATE ON
 PLANS.
 TABLE 1106.3.
 2B) SHT P202 SCUPPERS THRU THE MANSARD
 ROOF REQUIRES A MINIMUM OF 21.195 SQ IN
 6" PIPE IS REQUIRED. TABLE 1106.3 AND
 SECTION 1107.3.
 3B) SHT P204 MINIMUM 4" PIPE REQUIRED
 ON
 STORM RISER HORIZONTAL PIPING. TABLE
 1106.3.
 4B) SHT P204 MINIMUM 6" PIPE REQUIRED
 ON
 THE SCUPPER DRAINS. SECTION 1107.3
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-08 Cont ID  
Sent By kstevens Date 2004-12-08 Time 18:19 Rev Time 0.25
Received By kstevens Date 2004-12-08 Time 18:19 Sent To  
Notes
2004-12-08 00:00:00DENIED
  
 SEE COMMENTS FROM PERMIT #04110182
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-05-24 Cont ID  
Sent By mmclean Date 2005-05-13 Time 12:30 Rev Time 0.00
Received By mmclean Date 2005-05-13 Time 12:30 Sent To  
Notes
2005-05-24 00:00:00GRACE JOYCE, APPROVED 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2005-01-20 Cont ID  
Sent By mmclean Date 2005-01-20 Time 15:14 Rev Time 0.00
Received By mmclean Date 2005-01-20 Time 15:14 Sent To  
Notes
2005-01-20 00:00:00DENIED, MUST APPLY FOR A MINOR AMENDMENT
 TO CHANGES THAT ARE BEING MADE.
 APPLICATION MAY BE IN ON MONDAY
 1/24/05.
  
 CALL GRACE JOYCE, PLANNER IF YOU HAVE
 ANY QUESTIONS, 822-1447.