Plan Review Details - Permit 04101222
Plan Review Stops For Permit 04101222
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-21 Cont ID  
Sent By nmccray Date 2004-12-21 Time 12:56 Rev Time 0.00
Received By nmccray Date 2004-12-21 Time 12:56 Sent To  
Notes
2004-12-21 00:00:00PASSED ON PROVISO

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-15 Cont ID  
Sent By csiegber Date 2004-11-15 Time 16:39 Rev Time 0.00
Received By nmccray Date 2004-11-15 Time 10:30 Sent To  
Notes
2004-11-15 00:00:00DENIED
  
 1) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENT
 ATTESTING TO THIS CERTIFICATION PRIOR
 TO FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 2) WEST PALM BEACH FIRE MARSHAL OFFICE
 REQUIRES DUCT DETECTORS TO SEND A
 "ALARM" CONDITION, NOT A "SUPERVISORY".
  
 3) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-09 Cont ID  
Sent By mjacobs Date 2004-12-09 Time 10:20 Rev Time 0.00
Received By mjacobs Date 2004-12-09 Time 10:20 Sent To FIRE
Notes
2004-12-09 00:00:00SENT TO "FIRE" BOX/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 16:39 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 16:39 Sent To FIRE
Notes
***NONE***