Plan Review Details - Permit 04100893
Plan Review Stops For Permit 04100893
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-01-14 Cont ID  
Sent By alange Date 2005-01-14 Time 10:52 Rev Time 0.50
Received By alange Date 2005-01-14 Time 10:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-12-29 Cont ID  
Sent By alange Date 2004-12-29 Time 09:00 Rev Time 0.00
Received By alange Date 2005-01-14 Time 10:52 Sent To  
Notes
2004-12-29 00:00:00DENIED
  
  
 3.ALL PLANS SUBMITTED SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.FBC
 104.2.1
  
 4. ENERGY CALS SUBMITTED HAVE NOT BEEN
 SIGNED.ALSO WALL "R" VALUES DO NOT
 MATCH PLANS.
  
 6.SHOW FASTENENING SCHEDULE FOR
 NAILING OF ROOF AND WALL SHEATHING.
 SHOW ON PLANS.DO NOT SUBMIT COPIES OF
 CODE SECTIONS, SHOW DETAIL ON PLANS.
 CODE SECTION WAS INCORRECT, WEST PALM
 BEACH AMMENDMENT TO THE FBC 2306.1
 SEE ATTACHED CODE SEC FOR YOUR INFO.
  
 7.PRODUCT APPROVALS ARE NOW OK.I
 COMPLETED APPROVALS THAT WERE MISSING
 STATE APPROVALS.
  
 12.SHOW ON PLANS EXISTING BUILDING ANS
 SHOW NEW WORK SPECIFIED ON PLANS.
  
 NOTE:SUBMIT TWO COMPLETED SETS OF
 PLANS IN INK OR PHOTO COPIED WITH
 ORIGONAL SIGN SIGNATURES.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-18 Cont ID  
Sent By alange Date 2004-11-18 Time 13:09 Rev Time 1.50
Received By alange Date 2004-11-18 Time 13:09 Sent To P
Notes
2004-11-18 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.ALL PLANS SUBMITTED SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.FBC104.2.1
  
 4.SUBMIT 2 COPIES OF ENERGY CALCS.
  
 5.SHOW METHOD OF CRAWL SPACE
 VENTILATION.
  
 6.SHOW FASTENING SCHEDULE FOR NAILING
 OF ROOF AND WALL SHEATHING.
  
 7.SUBMIT TWO COMPLETE COPIES OF
 PRODUCT APPROVALS FOR EXTERIOR DOORS,
 WINDOWS, ROOFING AND STRAPS AND
 TIE-DOWNS.
 QUALITY ASSURANCE TESTING IS TO BE
 INCLUDED WITH THE FOLLOWING.
  
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8.SHOW SIZE OF BEDROOM WINDOWS AND
 TYPES SO THAT EMERGENCY ESCAPE OPENING
 SIZES CAN BE CALCULATED. FBC 1005.4.4
  
 9.SHOW SIZES OF BATHROOM DOORS. AT
 LEAST ONE DOOR SHALL MEET A CLEAR
 OPENING OF 29 INCHES.FBC11-11
  
 10.SUBMIT TWO COPIES OF A SITE PLAN
 SHOWING EXISTING BUIDINGS ON PROPERTY
 AND NEW ROOM ADDITION.
  
 11.SHOW METHOD OF TIE-IN FROM EXISTING
 SLAB TO NEW SLAB.
  
 12.SHOW ON PLANS EXISTING BUILDING AND
 SHOW NEW WORK SPECIFIED ON PLANS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-01 Cont ID  
Sent By btrobaug Date 2006-02-01 Time 16:33 Rev Time 0.33
Received By btrobaug Date 2006-02-01 Time 16:29 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2004-12-15 Cont ID  
Sent By dpalmer Date 2004-12-15 Time 12:42 Rev Time 0.25
Received By dpalmer Date 2004-12-15 Time 12:42 Sent To P
Notes
2004-12-15 00:00:00NO ELECTRICAL SUBMITTED FOR REVIEW.
  
 PLEASE SEE BLDG REVIEW NOTES, PLANS MAY
 NOT BE DONE ON PENCIL..
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-22 Cont ID  
Sent By dpalmer Date 2004-11-22 Time 17:00 Rev Time 0.25
Received By dpalmer Date 2004-11-22 Time 17:00 Sent To  
Notes
2004-11-22 00:00:00******* UNSAT ********
  
 1)NOTE: PLEASE SUBMIT ELECTRICAL PLANS
 SHOWING MIN REQUIRED FOR 2002 NEC
 COMPLIANCE FOR NEW WORK TO BE DONE.
  
 2)NOTE: PLEASE SEE FBC 104.2.1 FOR
 PERSON RESPONSIBLE FOR PLANS.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-10 Cont ID  
Sent By mjacobs Date 2005-01-10 Time 13:50 Rev Time 0.00
Received By mjacobs Date 2005-01-10 Time 13:50 Sent To AD
Notes
2005-01-10 00:00:00TO "AL" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 08:30 Rev Time 0.00
Received By mjacobs Date 2004-12-14 Time 08:30 Sent To E
Notes
2004-12-14 00:00:00SENT TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-08 Cont ID  
Sent By mjacobs Date 2004-12-08 Time 07:18 Rev Time 0.00
Received By mjacobs Date 2004-12-08 Time 07:17 Sent To Z
Notes
2004-12-08 00:00:00SENT TO "Z" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-08 Cont ID  
Sent By csiegber Date 2004-11-08 Time 11:22 Rev Time 0.00
Received By csiegber Date 2004-11-08 Time 11:21 Sent To B
Notes
2004-11-08 00:00:00TO RES BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 15:34 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 15:34 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-03-21 Cont ID  
Sent By hmoser Date 2005-03-21 Time 08:30 Rev Time 0.00
Received By hmoser Date 2005-03-21 Time 08:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-23 Cont ID  
Sent By kstevens Date 2004-12-23 Time 05:37 Rev Time 0.45
Received By kstevens Date 2004-12-23 Time 05:37 Sent To B1
Notes
2004-12-23 00:00:00PASSED/PROVISO - WATER HAMMER ARRESTORS
 REQUIRED PER SECTION 604.9

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-22 Cont ID  
Sent By kstevens Date 2004-11-22 Time 11:09 Rev Time 0.25
Received By kstevens Date 2004-11-22 Time 11:09 Sent To E
Notes
2004-11-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
  
 1) TWO OR MORE COPIES OF DRAWING SHALL
 ACCOMPANY THE APPLICATION FOR A PERMIT.
 ONLY ONE SET OF SANT. AND WATER RISER
 DIAGRAMS WERE SUBMITTED. SECTION
 104.2.1
 2) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SECTION 104.2.1
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-12-13 Cont ID  
Sent By mmclean Date 2004-12-13 Time 15:14 Rev Time 0.00
Received By mmclean Date 2004-12-13 Time 15:14 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-11-16 Cont ID  
Sent By csiegber Date 2004-11-06 Time 15:35 Rev Time 0.00
Received By mmclean Date 2004-11-06 Time 11:29 Sent To I
Notes
2004-11-06 00:00:00DENIED, NEED TO SHOW THE ADDITION ON
 SURVEY WITH SETBACKS.