Plan Review Details - Permit 04100592
Plan Review Stops For Permit 04100592
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-08 Cont ID  
Sent By jwitmer Date 2004-12-08 Time 07:52 Rev Time 0.55
Received By jwitmer Date 2004-12-08 Time 07:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-29 Cont ID  
Sent By jwitmer Date 2004-10-29 Time 08:49 Rev Time 1.11
Received By jwitmer Date 2004-10-29 Time 08:49 Sent To  
Notes
2004-10-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100592
 ADD: 1400 CENTREPARK# 300
 CONT: PASS INTERNATIONAL
 TEL: (561)706-7201
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) PERMIT APPLICATION THE DESCRIPTION OF
 WORK INDICATES THE PERMIT TO BE FOR THE
 UNIT# 300, WHILE THE PLANS INDICATE WORK
 ALSO ON THE (4TH) FLOOR. IF THE PERMIT
 IS TO INCLUDE THE WORK DESCRIBED IN THE
 PLANS FOR THE (4TH) FLOOR IT ALSO NEEDS
 TO BE REFLECTED ON THE PERMIT APPLICA-
 TION. IF THE (4TH) FLOOR ISN'T TO PART
 OF THIS PERMIT, PULL PAGES FROM THE
 PERMIT PACKAKE, ALSO IF THIS TO BE PART
 OF THE PERMIT PACKAGE DOES THE PERMIT
 FEES REFLECT THIS ADDITIONAL WORK?
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-24 Cont ID  
Sent By dpalmer Date 2004-11-24 Time 05:48 Rev Time 0.25
Received By dpalmer Date 2004-11-24 Time 05:48 Sent To  
Notes
2004-11-24 00:00:00******* PROVISO/REVISION **********
  
 1)NOTE: PLEASE NOTE ON PREVIOUS REVIEW.
 PLEASE PROVIDE ALL NEW CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 THIS IS REQUIRED TO BE SUBMITTED FOR
 REVIEW AND STAMPING BEFORE FINAL
 ELECTRICAL INSPECTION.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-23 Cont ID  
Sent By dpalmer Date 2004-10-23 Time 08:11 Rev Time 0.33
Received By dpalmer Date 2004-10-23 Time 08:11 Sent To  
Notes
2004-10-23 00:00:00****** UNSAT *********
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 AND PLANS INDICATE WORK TO BE IN SUITE
 #300, YET PLANS ALSO INDICATE ADDITIONAL
 WORK ON FORTH FLR?
 PLEASE INCLUDE IN PERMIT APPLICATION OR
 SEPARATE BY SUITES/FLRS.
  
 2)NOTE: PLEASE SEE FORTH FLR NOTE MENT-
 -IONS NO NEW LOADS, YET THERE APPEARS
 TO BE ADDITIONAL LOAD.
 PLEASE SHOW ALL CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE TO
 BE SUBMITTED BEFORE ROUGH.
 THIS NOTE IS GIVEN AT THIS TIME.
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-20 Cont ID  
Sent By mcarsill Date 2004-12-17 Time 07:40 Rev Time 0.00
Received By mcarsill Date 2004-12-17 Time 07:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-11-05 Cont ID  
Sent By mcarsill Date 2004-11-05 Time 14:41 Rev Time 0.00
Received By mcarsill Date 2004-12-17 Time 07:39 Sent To  
Notes
2004-11-05 00:00:001) IT APPEARS THAT ADDITIONAL EXIT
 SIGNS ARE NEEDED ON THE FOURTH
 FLOOR TENANT SPACE. EXIT SIGNS MUST
 DIRECT PERSONS TO THE EXITS. SIGNS
 DIRECTLY INFRONT OF EXITS DO NOT
 DIRECT PERSONS AROUND THE SPACE.
  
 2) THE SAME CONDITIONS APPEAR TO
 EXIST ON THE THIRD FLOOR TENANT
 SPACE, ESPECIALLY IN THE OPEN FLOOR
 PLAN AREAS.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-18 Cont ID  
Sent By csiegber Date 2004-11-05 Time 12:44 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 15:26 Sent To  
Notes
2004-10-18 00:00:00TO COMM BD#29

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-11-15 Cont ID  
Sent By pkrauss Date 2004-11-15 Time 13:45 Rev Time 0.45
Received By pkrauss Date 2004-11-15 Time 11:35 Sent To  
Notes
2004-11-15 00:00:00PROVISO:
 NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM AS PER
 2001 FBC(M) 602.2.1.
  
 SEE COMMENT#1 BY BUILDING PLANS EXAMINER
 JIM WITMER.PLANS ARE OTHERWISE CODE
 COMPIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-13 Cont ID  
Sent By kstevens Date 2004-12-13 Time 12:23 Rev Time 0.50
Received By kstevens Date 2004-12-13 Time 12:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-08 Cont ID  
Sent By kstevens Date 2004-11-08 Time 07:07 Rev Time 0.42
Received By kstevens Date 2004-11-08 Time 07:07 Sent To  
Notes
2004-11-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 1 CLEAR FLOOR SPACE FOR BREAK
 ROOM SINK SHALL BE FORWARD APPROACH NOT
 PARALLEL AS SHOWN. SECTION 11-4.24.5.
 2) SHT 2 SHOW CLEAR FLOOR SPACE FOR
 SINK. SECTION 11-4.24.5.
 3) SHT 7 IN THE INSTALLATION OR REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD
 ENDS SHALL BE PROHIBITED.
 4) SHT 8 (SEE COMMENT #3).
 5) SUBMIT A DETAIL FOR THE SINKS SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. SHOW:
 A) HEIGHT 11-4.24.2
 B) KNEE CLEARANCE 11-4.24.3
 C) DEPTH OF SINK 11-4.24.4
 D) CLEAR FLOOR SPACE - WHICH SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK.
 E) EXPOSED PIPES AND SURFACES
 11-4.24.6
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]