Plan Review Details - Permit 04100422
Plan Review Stops For Permit 04100422
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-15 Cont ID  
Sent By rmcdouga Date 2004-11-15 Time 12:31 Rev Time 0.00
Received By rmcdouga Date 2004-11-15 Time 12:31 Sent To  
Notes
2004-11-15 00:00:00DENIED
  
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE TITLE BLOCK IS MISSING
 INFORMATION. THE LICENSE NUMBER OF THE
 FIRM, AS WELL AS, THE PRINTED NAME AND
 LICENSE NUMBER OF THE ARCHITECT SIGNING
 AND SEALING THE DOCUMENT IS REQUIRED.
 SEE FAC 61G1-16.004.
  
 4) SPECIFY THE ATTIC ACCESS AT THE GUEST
 SUITE. SPECIFY MINIMUM SIZE. SEE FBC
 2309.6.
  
 5) SPECIFY ON THE PLANS THAT THE DESIGN
 IS FOR A VENTLESS ATTIC. MUST COMPLY
 WITH BCAB REQUIREMENTS (SEE ATTACHMENT).
  
 SUBMIT AFFIDAVIT FROM THE ROOFING
 MATERIAL/SYSTEM MANUFACTURER CERTIFYING
 USE OF THEIR PRODUCT OVER AN UNVENTED
 ATTIC SYSTEM.
  
 6) SUBMIT CALCULATIONS FOR THE EAST
 ELEVATION WHICH SHOW THAT THE WALL
 OPENINGS DO NOT EXCEED THE 20% OF WALL
 AREA ALLOWED BY FBC TABLE 600 BASED ON A
 DISTANCE OF 10' TO THE PROPERTY LINE.
  
  
 7) 1007.8.1 WINDERS SHALL HAVE A MINIMUM
 TREAD DEPTH OF 6" AT THE NARROWEST EDGE
 & SHALL HAVE A MINIMUM TREAD DEPTH OF
 11" AT A POINT 12" FROM THE NARROW EDGE.
 WINDERS SHALL BE PERMITTEDTO BE USED
 AS A COMPONENT IN MEANS OF EGRESS WITHIN
 A DWELLING UNIT. SPECIFY ON PLANS.
  
 8) THE CONDITIONED AREA LISTED ON SHEET
 AO OF THE PLANS (4077 SQFT) CONFLICTS
 WITH THE 4321 SQFT LISTED ON THE ENERGY
 CALCULATION FORM. PLEASE CORRECT.
  
 9) PROVIDE A SECTION AND DETAILS FOR THE
 TWO STORY CHIMNEY AT THE FAMILY
 ROOM/NICHE. SPECIFY THE FOUNDATION AND
 FOUNDATION REINFORCEMENT REQUIREMENTS ON
 SHEET S1.
  
 10) SPECIFY THE WINDLOAD PRESSURES FOR
 THE OVERHEAD GARAGE DOOR ON A4.
  
 11) THE STRUCTURAL PLANS ON S2 DO NOT
 SHOW THE POURED CONC. TIE BEAM AT THE
 CEILING AS SPECIFIED ON DETAIL 2 ON A9.
 PLEASE CLARIFY.
  
 12) SPECIFY THE LOCATION AND MATERIAL
 FOR THE DRAFTSTOP AT THE FLOOR/CEILING
 ASSEMBLY DIVIDING IT INTO AREAS OF NO
 MORE THAN 500 SQFT PER FBC 2305.2.2.
  
 13) SPECIFY THE FIREBLOCKING AT THE TOP
 AND BOTTOM OF STAIR RUNS REQUIRED BY FBC
 2305.1.4.
  
 14) PROVIDE GARAGE DOOR BUCK FASTENING
 DETAILS ON THE STRUCTURAL SHEETS AS
 INDICATED BY THE NOTE ON A13.
  
 15) THE SECTIONS ON A6 ARE MISLABELED AS
 A5. PLEASE CORRECT.
  
 16) SPECIFY THE ROOFING MATERIAL FOR THE
 FLAT PORTION OF THE UPPER ROOF INDICATED
 ON SHEET S3. PROVIDE A DETAIL OF THE
 TRANSITION OF ROOF COVERINGS FROM FLAT
 TO SLOPED ROOFS.
  
 17) PLEASE CLARIFY THE "?" DETAIL ON
 SHEET S3.
  
 18) FBC 2804.2.4 REQUIRES CHIMNEYS TO
 EXTEND 3' ABOVE HIGHEST POINT THEY PASS
 THROUGH THE ROOF AND AT LEAST 2' HIGHER
 THAN ANY PART OF THE ROOF OR BUILDING
 WITHIN 10' HORIZONTALLY.
  
 19) PROVIDE THE LISTING IFORMATION AND
 SPECIFICATIONS FOR THE GAS BBQ.
  
 20) SPECIFY THE SPECIAL ROOF SHEATHING
 NAILING REQUIREMENTS AND ZONES AS
 REQUIRED BY REVISED TABLE 2306.1 OF THE
 CITY OF WPB AMENDMENTS TO THE 2001 FBC.
  
 21) THE ROOF HEIGHT IS INCORRECTLY
 LABELED AS THE SECOND FLOOR PLATE HEIGHT
 ON A4.
  
 22) PROVIDE STATE OR LOCAL PRODUCT
 APPROVAL FOR THE CONSTRUCTION GLASS
 INDUSTRIES CORP. PRODUCTS. SEE RULE
 9B-72.(SEE LOCAL PRODUCT APPLICATION
 FORM ATTACHED)
  
 23) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE MOUNT TYPE, FASTENERS & SPACING OF
 FASTENERS.
  
 24) SUBMIT PRODUCT APPROVAL FOR THE
 MAHOGANY DOOR WITH SIDELITES.
  
 25) PRODUCT APPROVAL WAS SUBMITTED FOR
 FIBERGLASS DOORS AND THE DOOR SCHEDULE
 CALLS FOR ALL EXTERIOR DOORS TO BE
 ALUMINUM CLAD OR MAHOGANY WOOD DOORS.
 PLEASE CLARIFY.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-28 Cont ID  
Sent By btrobaug Date 2004-10-28 Time 09:45 Rev Time 0.75
Received By btrobaug Date 2004-10-27 Time 12:54 Sent To M
Notes
2004-10-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF THE
 POOL PANEL ON THE PLAN AND INCLUDE SAME
 ON RISER PER 15.5.
  
 2} PLEASE NOTE THAT AHU'S #2 & 3 DO NOT
 COMPLY WITH ATRICLE 424.3(B), OCP AND
 BRANCH CIRCUIT WIRING @ 125%.
  
 3} PLEASE CLARIFY IF THE METER AND MAIN
 SHOWN ON THE RISER IS A COMBINATION UNIT
 AND SHOW LOCATION OF THE MAIN BREAKERS
 ON THE PLAN.
  
 4} A SMOKE DETECTOR IS REQUIRED IN CLOSE
 PROXIMITY TO THE STAIRWELL ON THE FIRST
 FLOOR LEVEL PER 905.2.2 FBC.
  
 5} PLEASE PROVIDE THE ARCHITECTURAL
 FIRMS LICENSE # IN THE TITLE BLOCK PER
 61G1-16.004 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-15 Cont ID  
Sent By mmclean Date 2004-10-26 Time 12:12 Rev Time 0.00
Received By rmcdouga Date 2004-10-13 Time 11:05 Sent To  
Notes
2004-10-27 00:00:00TO SFD RACK/E
2004-10-13 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By btrobaug Date 2004-10-28 Time 10:25 Rev Time 0.00
Received By pkrauss Date 2004-11-01 Time 14:13 Sent To  
Notes
2004-11-01 00:00:00PROVISO:
 1.PLAN SHEET M-2, BEDROOM 3 SUPPLY
 DUCT SHALL BE A MAXIMUM OF 7" FOR
 COMPLIANCE WITH 2001 FBC(M) 601.4
 EXCEPTION #1 & 3.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 3.PLEASE NOTE, SHOULD GAS DRYERS BE
 INSTALLED PROVIDE COMBUSTION AIR CALCS
 AND INDICATE FRESH AIR AS REQUIRED PER
 2001 FBC(M) CHAPTER 7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-04 Cont ID  
Sent By kstevens Date 2004-11-04 Time 18:33 Rev Time 0.75
Received By kstevens Date 2004-11-04 Time 18:33 Sent To B1
Notes
2004-11-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLAN.
 A) BAR SINK IN FAMILY ROOM NOT SHOWN ON
 THE RISER DIAGRAM. SECTION 104.2.1
 B) VENT REQUIRED FOR EACH WASH MACHINE.
 SECTION 901.2.1, AND THE WASH MACHINE
 SHALL HAVE A CLEANOUT 4 FT. ABOVE THE
 FLOOR FOR ACCESS. SECTION 708.10
 C) WASH MACHINE AND LAUNDRY SINK DO NOT
 REFLECT THE FLOOR PLAN. THE W/M SHALL BE
 ON THE RIGHT SIDE AND THE LAUNDRY SINK
 SHALL BE ON THE LEFT SIDE. SECTION
 104.2.1
 D) KITCHEN PREP SINK IS MISLABLED AS A
 BAR SINK. SECTION 104.2.1
 E) LAVS IN THE MASTER BATH TO BOTH FACE
 INTO THE BATHROOM. SECTION 104.2.1
 F) BATHROOM #2 ALL FIXTURES SHALL LOOK
 INTO THE SAME ROOM AS SHOWN ON THE FLOOR
 PLAN. SECTION 104.2.1
 2) INDICATE WHERE THE SHOWER ON THE
 FLOOR PLAN OUTSIDE THE CABANA BATH
 DRAINS TO. SECTION 104.2.1
 3) SHT P-1 GENERAL NOTES #8 AIR CHAMBERS
 ARE NOT APPROVED. DELETE FROM NOTES.
 SECTION 604.9
 4) 61G1-16.004(2) FIRM LICENSE NUMBER IS
 REQUIRED. (6) PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT REQUIRED. FS
 481.2055.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-10-26 Cont ID  
Sent By mmclean Date 2004-10-26 Time 12:12 Rev Time 0.00
Received By mmclean Date 2004-10-26 Time 12:12 Sent To I
Notes
***NONE***