Plan Review Details - Permit 04100413
Plan Review Stops For Permit 04100413
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-02-25 Cont ID  
Sent By rmcdouga Date 2005-02-25 Time 07:38 Rev Time 0.00
Received By rmcdouga Date 2005-02-25 Time 07:26 Sent To  
Notes
2005-02-25 00:00:00PROVISO
  
 1) A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE STORM PANELS. SUBMIT 2 COPIES OF
 STATE PRODUCT APPROVALS (INCLUDING
 INSTALLATION INSTRUCTIONS), KEY PLANS
 AND INSTALLATION SCHEDULE WITH FASTENERS
 AND SPACING LISTED.
  
 2) A SEPARATE PERMIT WILL ALSO BE
 REQUIRED FOR MECHANICAL AND REROOF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-01-31 Cont ID  
Sent By rmcdouga Date 2005-01-31 Time 10:06 Rev Time 0.00
Received By rmcdouga Date 2005-01-31 Time 10:06 Sent To  
Notes
2005-01-31 00:00:00DENIED
  
  
 1)PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. I HAVE
 ATTACHED THE COVER SHEET WITH THE FL#
 FOR THE TRACO WINDOWS, HOWEVER I DID NOT
 SEE ONE FOR THE POMA STORM PANELS.
 SUBMIT FLORIDA PRODUCT APPROVAL FOR
 STORM PANELS.
  
 2) SUBMIT TWO COPIES OF A KEY PLAN AND
 INSDTALLATION SCHEDULE FOR THE STORM
 PANELS. SPECIFY THE TYPE OF MOUNT, THE
 TYPE OF FASTENERS AND THE FASTENER
 SPACING.
  
 3) A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE MECHANICAL SYSTEMS. SUBMIT
 MECHANICAL PLANS, ENERGY CALCS. AND
 MANUAL J CALCS. WITH APPLICATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2004-12-22 Cont ID  
Sent By rmcdouga Date 2004-12-22 Time 14:09 Rev Time 0.00
Received By rmcdouga Date 2004-12-22 Time 14:08 Sent To  
Notes
2004-12-22 00:00:00REVISION DENIED
  
 1) INDICATE THE VALUE OF THE WORK
 INCLUDED IN THE REVISION SO THAT THE
 PERMIT VALUE CAN BE INCREASED TO INCLUDE
 THE ADDITIONAL SCOPE OF WORK.
  
 2)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 WWW.FLORIDABUILDING.ORG
  
 3) SUBMIT 2 COPIES OF STATE/LOCAL
 PRODUCT APPROVALS FOR THE NEW WINDOWS.
  
 4) SUBMIT PRODUCT APPROVALS, KEY PLAN
 AND INSTALLATION SCHEDULE FOR STORM
 PANELS OR PRODUCT APPROVALS FOR IMPACT
 RESISTANT WINDOWS.
  
 5) SUBMIT ELECTRICAL PLANS WITH RISER
 DIAGRAM AND CALCULATIONS, OR REMOVE
 ELECTRIC NOTE FROM SCOPE OF WORK ON A1
 AND APPLY UNDER A SEPARATE PERMIT.
  
 6) THE EXTENT OF STRUCTURAL REPAIRS IS
 TO BE EVALUATED BY THE FIELD INSPECTOR
 AND SIGNED AND SEALED DRAWINGS OF
 REPAIRS FROM AN ENGINEER OR ARCHITECT
 SUBMITTED IF NECESSARY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-10-20 Cont ID  
Sent By spalmer Date 2004-10-20 Time 08:28 Rev Time 0.25
Received By spalmer Date   Time   Sent To  
Notes
2004-10-20 00:00:00APPROVED PER STEVE NICOLOSI

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-18 Cont ID  
Sent By btrobaug Date 2005-02-18 Time 12:57 Rev Time 0.50
Received By btrobaug Date 2005-02-18 Time 12:31 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-26 Cont ID  
Sent By btrobaug Date 2005-01-26 Time 15:27 Rev Time 0.50
Received By btrobaug Date 2005-01-26 Time 07:36 Sent To B
Notes
2005-01-25 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1) LAUNDRY CIRCUIT LOAD. A LOAD OF NOT
 LESS THAN 1500 VOLT-AMPERES SHALL BE
 INCLUDED FOR EACH 2-WIRE LAUNDRY BRANCH
 CIRCUIT INSTALLED AS REQUIRED BY
 210.11(C)(2). THIS LOAD SHALL BE
 PERMITTED TO BE INCLUDED WITH THE
 GENERAL LIGHTING LOAD AND SUBJECTED TO
 THE DEMAND FACTORS PROVIDED IN TABLE
 220.11.
  
 2} 220.18 ELECTRIC CLOTHES DRYERS
 DWELLING UNIT(S).
 THE LOAD FOR HOUSEHOLD ELECTRIC CLOTHES
 DRYERS IN A DWELLING UNIT(S) SHALL BE
 5000 WATTS (VOLT-AMPERES) OR THE
 NAMEPLATE RATING, WHICHEVER IS LARGER,
 FOR EACH DRYER SERVED.
  
 3} 110.9 INTERRUPTING RATING.
 EQUIPMENT INTENDED TO INTERRUPT CURRENT
 AT FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING SUFFICIENT FOR THE
 NOMINAL CIRCUIT VOLTAGE AND THE CURRENT
 THAT IS AVAILABLE AT THE LINE TERMINALS
 OF THE EQUIPMENT.
  
 4} THE LOCATION OF THE ELECTRICAL
 SERVICE EQUIPMENT IS IN VIOLATION OF
 ARTICLE 110.26 WITH RELATIONSHIP TO THE
 STEPS.
  
 6} SEE ARTICLE 210.52(E) FOR OUTSIDE
 RECEPTACLE REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-11 Cont ID  
Sent By mjacobs Date 2005-02-11 Time 15:39 Rev Time 0.00
Received By mjacobs Date 2005-02-11 Time 15:39 Sent To E
Notes
2005-02-11 00:00:00TO "BT" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-19 Cont ID  
Sent By mjacobs Date 2005-01-19 Time 10:21 Rev Time 0.00
Received By mjacobs Date 2005-01-19 Time 10:21 Sent To E
Notes
2005-01-19 00:00:00TO "E" BOX./RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-13 Cont ID  
Sent By mjacobs Date 2004-12-13 Time 15:52 Rev Time 0.00
Received By mjacobs Date 2004-12-13 Time 15:52 Sent To B
Notes
2004-12-13 00:00:00SENT TO "B" TO RES BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-09 Cont ID  
Sent By mjacobs Date 2004-12-09 Time 10:28 Rev Time 0.00
Received By mjacobs Date 2004-12-09 Time 10:27 Sent To Z
Notes
2004-12-09 00:00:00SENT TO "Z" BOX.

Review Stop Z ZONING
Rev No 1 Status N Date 2004-12-22 Cont ID  
Sent By mmclean Date 2004-12-22 Time 13:18 Rev Time 0.00
Received By mmclean Date 2004-12-22 Time 13:18 Sent To B
Notes
2004-12-22 00:00:00GREEN CARD SHOWS APTS.OK FOR
 RENOVATION