Plan Review Stops For Permit 04100365 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2004-10-20 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-10-20 |
Time |
07:12 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2004-10-20 |
Time |
07:02 |
Sent To |
|
|
Notes |
2004-10-20 00:00:00 | PROVISO: | | REMOTE CONDENSER LOCATED ON THE ROOF, | | SHALL COMPLY WITH 2001 FBC 1511.7 FOR | | CLEARANCE BETWEEN THE ROOF SURFACE AND | | THE BOTTOM OF THE SUPPORT RAIL. | | | | WIDTH OF MECHMINIMUM CLEARANCE | | UNITABOVE THE ROOF | | (INCHES)SURFACE (INCHES) | | ---------------------------------------- | | < 2414 | | 24 < 36 18 | | 36 < 48 24 | | 48 < 60 30 | | > 60 48 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|