Plan Review Details - Permit 04100260
Plan Review Stops For Permit 04100260
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2004-12-20 Time 14:30 Rev Time 0.45
Received By prafter Date 2004-12-23 Time 08:33 Sent To M
Notes
2004-12-23 00:00:00PROVISO .PHK/ PROVISO NOTES MUST BE
 ADRESSED AND RFTURN AIR OUT OF MASTER
 BEDROOM .
  
 PAT RAFTER 12/23/04 .
2004-12-20 00:00:00SENT TO "M/AC" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-07 Cont ID  
Sent By csiegber Date 2004-10-07 Time 15:12 Rev Time 0.00
Received By csiegber Date 2004-10-07 Time 15:12 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By prafter Date 2004-12-23 Time 08:52 Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-10-19 Cont ID  
Sent By csiegber Date 2004-10-07 Time 15:12 Rev Time 0.35
Received By pkrauss Date 2004-10-19 Time 06:23 Sent To  
Notes
2004-10-19 00:00:00PROVISO:
 RETURN TRANSFER GRILLES ARE TO BE A
 MINIMUM OF 50 SQ INCHES OF FREE AREA TO
 100 CFM OF SUPPLY AIR IN ACCORDANCE WITH
 2001 FBC(M) 601.4 EXCEPTION #2.
 BEDROOM #3 SHALL BE A MINIMUM OF 10"X8"
 BEDROOM #2 SHALL BE A MINIMUM OF 10"X10"
  
 PLEASE NOTE TRANSFER GRILLE INDICATED
 IN THE MASTER BATHROOM SHOULD BE
 RELOCATED TO AC#2 CLOSET.AIR FROM THE
 BATHROOM AREA IS NOT TO BE RECIRCULATED.
 2001 FBC(M) 402.3.1.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.