Plan Review Details - Permit 04100187
Plan Review Stops For Permit 04100187
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-22 Cont ID  
Sent By jwitmer Date 2004-12-22 Time 14:01 Rev Time 0.99
Received By jwitmer Date 2004-12-22 Time 14:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By jwitmer Date 2004-10-25 Time 07:28 Rev Time 1.11
Received By jwitmer Date 2004-10-25 Time 07:01 Sent To  
Notes
2004-10-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04100187
 ADD: 1400 ENTREPARK DRIVE# 400&500
 CONT: PASS INTERNATIONAL INC
 TEL: (561)239-0125
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) 4TH & 5TH FLOORS,SEE BREAK AREA SINK:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 4) 5TH FLOOR, THE HALLWAY DOOR NEXT TO
 RECEPTIONIST MISSING 18"CLEAR SPACE ON T
 HE PULL SIDE OF LATCHING MECHANISM:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS ARE UNCLEAR, 5TH FLOOR AT THE TOP
 OF THE PLAN, IT APPEARS THAT A OFFICE
 10'X12' MAY OR MAY NOT HAVE 4 WALLS, IF
 IT ONLY HAS THREE WALLS THE CORRIDOR
 LESADS DIRRECTLY INTO THE OFFICE. IF
 THERE IS TO BE A WALL THE OFFICE ABOVE
 IS OVER THE 75' COMMON PATH OF TRAVEL.
 1004.1.3. COMMON PATH OF TRAVEL SHALL
 NOT EXCEED 75'.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-29 Cont ID  
Sent By dpalmer Date 2004-11-29 Time 07:10 Rev Time 0.25
Received By dpalmer Date 2004-11-29 Time 07:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-15 Cont ID  
Sent By mjacobs Date 2004-11-22 Time 15:48 Rev Time 0.33
Received By dpalmer Date 2004-10-15 Time 16:18 Sent To  
Notes
2004-10-15 00:00:00********* UNSAT *************
  
 1)NOTE: PLEASE SEE NOTEON PLANS MENT-
 -IONS ONLY GEN PURPOSE RECEPTS BEING
 REMOVED/RELOCATED.
 PLANS SHOW NEW APPLICANCE/ FRIG RECETPS
 ALSO.
 PLEASE INCLUDE CIRCUITING FOR THIS, TO
 CORRELATE WITH PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE SEVERAL LOCATIONS
 WHICH MENTION "TO VERIFY IF EXISTING"
 FOR EXT/EM LTS ETC. IF THESE ITEMS ARE
 REQUIRED BY CODE?, OR GOING TO BE
 INSTALLED, THEN THESE ARE REQUIRED TO
 BE SHOWN ON PLANS AT THIS TIME.
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF THESE.
  
 PLEASE SEE POSSIBLE COMMENTS FROM FIRE
 PLAN REVIEW AND ANY OTHER REVIEW(S)
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEET FROM
 SETS AND ONLY INSERT NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-22 Cont ID  
Sent By nmccray Date 2004-12-22 Time 10:42 Rev Time 0.00
Received By nmccray Date 2004-12-22 Time 10:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-10-20 Cont ID  
Sent By mcarsill Date 2004-10-20 Time 16:29 Rev Time 0.00
Received By mcarsill Date 2004-10-20 Time 16:29 Sent To  
Notes
2004-10-20 00:00:001) PLEASE INDICATE INTERIOR FINISH
 THAT WILL BE USED ON NEW WALLS.
  
 2) THE 5TH FLOOR SHOWS ONLY ONE
 FIRE EXTINGUISHER. TRAVEL DISTANCE
 TO REACH A FIRE EXTINGUISHER SHALL
 NOT EXCEED 75 FEET.
  
 3) PLEASE SUBMIT SHOP DRAWINGS FOR
 FIRE SPRINKLER REMODEL.
  
 4) PLEASE SUBMIT SHOP DRAWINGS FOR
 FIRE ALARM REMODEL.
  
 5) ARE THERE ANY UL DOOR CLOSERS AND
 HARDWARE ON THE RATED FIRE DOORS.
  
 MIKE WENNERGREN, LIEUTENANT
 835-2950

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-29 Cont ID  
Sent By mjacobs Date 2004-11-22 Time 07:30 Rev Time 0.00
Received By mjacobs Date 2004-11-22 Time 07:33 Sent To  
Notes
2004-11-22 00:00:00SENT TO THE COMM BD#46/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-25 Cont ID  
Sent By dpalmer Date 2004-10-25 Time 06:55 Rev Time 0.00
Received By dpalmer Date 2004-10-07 Time 07:08 Sent To  
Notes
2004-10-06 00:00:00TO COMM BD#4

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-13 Cont ID  
Sent By kstevens Date 2004-12-13 Time 13:16 Rev Time 0.50
Received By kstevens Date 2004-12-13 Time 13:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-01 Cont ID  
Sent By kstevens Date 2004-11-01 Time 11:48 Rev Time 1.00
Received By kstevens Date 2004-11-01 Time 11:38 Sent To  
Notes
2004-11-01 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 1) A CLEAR FLOOR SPACE AT LEAST 30"X48"
 COMPLYING WITH 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19"
 UNDERNEATH
 THE SINK. SEE FIG. 32 SECTION 11-4.24.5
 2) SHOW KNEE CLEARANCE 11-4.24.3
 3) SHOW DEPTH OF SINK 11-4.24.4
 4) SHOW EXPOSED PIPES & SURFACES
 11-4.24.6
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]