Plan Review Details - Permit 04100101
Plan Review Stops For Permit 04100101
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-03-16 Cont ID  
Sent By nmccray Date 2005-03-16 Time 09:47 Rev Time 0.00
Received By nmccray Date 2005-03-16 Time 09:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-05 Time 11:14 Rev Time 0.00
Received By nmccray Date 2004-10-20 Time 12:33 Sent To  
Notes
2004-10-20 00:00:00**************DENIED********************
  
 1) WHEN THE FIRE ALARM CONTROL UNIT,
 INCLUDING THE DIALER-COMMUNICATOR, IS
 REPLACED IN AN EXISTING SYSTEM, IT WILL
 BE TREATED AS IF IT WERE A NEW SYSTEM.
  
 2) NEW FIRE ALARM SYSTEMS SHALL BE
 LISTED FOR CENTRAL STATION SERVICE.
  
 3) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENT
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL APPROVAL OF THE FIRE ALARM SYSTEM.
  
 4) THE FIRE ALARM SYSTEM SHALL BE
 CLASS "A" OR FULLY ADDRESSABLE.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 15:06 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 15:06 Sent To FIRE
Notes
2005-03-09 00:00:00TO "NMCRAY DESK/ RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 11:14 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 11:14 Sent To FIRE
Notes
***NONE***