Plan Review Details - Permit 04090873
Plan Review Stops For Permit 04090873
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-01-25 Cont ID  
Sent By lsmith Date 2005-01-25 Time 16:10 Rev Time 0.75
Received By lsmith Date 2005-01-25 Time 16:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-22 Cont ID  
Sent By btrobaug Date 2005-02-22 Time 09:09 Rev Time 0.50
Received By btrobaug Date 2005-02-22 Time 09:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-03 Cont ID  
Sent By btrobaug Date 2005-02-03 Time 14:56 Rev Time 0.33
Received By btrobaug Date 2005-02-02 Time 16:45 Sent To  
Notes
2005-02-03 00:00:00 
 THE LOAD CALCULATIONS SUBMITTED MUST BE
 CORRECTED AS FOLLOWS.
  
 1} THE PLANS MUST CONTAIN THE PRINTED AN
 SIGNED NAME OF THE DESIGNER OF RECORD
 PER 104.2.1 FBC.
  
 2} THE GENERAL LIGHTING LOAD IS LISTED @
 6600 AND THEN A CALULATION OF 3 WATTS
 PER SQUARE FOOT IS SHOWN, WHICH WOULD BE
 THE GENERAL LIGHTING LOAD, @ 3000.
 PLEASE CORRELATE.
  
 3} THE SMALL APPLIANCE LOAD MUST COMPLY
 WITH 220.16, 2@ 1500=3000WATTS MINIMUM.
  
 4} THE WASHER IS INCORRECTLY CALCULATED
 AT 10000 WATTS, BUT MUST BE A MINIMUM OF
 1500 WATTS IF REFERRING TO THE LAUNDRY
 LOAD REQUIREMENT.
  
 5} A/C #1&2 ARE SHOWN AS 5000 EACH, AND
 SHOWN AGAIN AT 15000 AND 10000. PLEASE
 CORRELATE.
  
 6} THE RANGE MUST BE CALCULATED PER
 220.19.
  
 7} CLARIFY "HWIT" ON CALC.
  
 8} THE POOL PUMP AND HEATER MUST BE
 CALCULATED AT 125%. SEE ARTICLES 424 &
 430.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-01-19 Cont ID  
Sent By btrobaug Date 2005-01-19 Time 13:44 Rev Time 0.33
Received By btrobaug Date 2005-01-19 Time 13:28 Sent To P
Notes
2005-01-19 00:00:00 
  
 PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-16 Cont ID  
Sent By adarroug Date 2005-02-16 Time 11:38 Rev Time 0.00
Received By adarroug Date 2005-02-16 Time 11:38 Sent To B
Notes
2005-02-16 00:00:00TO BTROBAUG DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-02 Cont ID  
Sent By adarroug Date 2005-02-02 Time 16:22 Rev Time 0.00
Received By adarroug Date 2005-02-02 Time 16:22 Sent To E
Notes
2005-02-02 00:00:00TO "BT" DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-19 Cont ID  
Sent By mjacobs Date 2005-01-19 Time 08:44 Rev Time 0.00
Received By mjacobs Date 2005-01-19 Time 08:44 Sent To E
Notes
2005-01-19 00:00:00TO "E" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-12 Cont ID  
Sent By mjacobs Date 2005-01-12 Time 11:24 Rev Time 0.00
Received By mjacobs Date 2005-01-12 Time 11:24 Sent To Z
Notes
2005-01-12 00:00:00TO "Z" BOX/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 09:36 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 09:36 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-22 Cont ID  
Sent By jleech Date 2005-01-22 Time 10:09 Rev Time 0.50
Received By jleech Date 2005-01-22 Time 10:09 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-01-18 Cont ID  
Sent By mmclean Date 2005-01-18 Time 14:44 Rev Time 0.00
Received By mmclean Date 2005-01-18 Time 14:44 Sent To I
Notes
2005-01-18 00:00:00APPROVED ZBA CASE #3137 EDNASHA BOWERS,
 PLANNER 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-10-15 Cont ID  
Sent By csiegber Date 2004-10-04 Time 09:36 Rev Time 0.00
Received By mmclean Date 2004-10-15 Time 15:05 Sent To  
Notes
2004-10-15 00:00:00DENIED, NEED TO PROVIDE TWO COPY OF
 VARIANCE APPROVAL (IF APPLIED) OR POOL
 MUST BE BUILT BEYOND THE 25FT FRONT
 SETBACK MEETING ALL SETBACK GUIDELINES.
 CALLED LEFT MSG FOR SHAUN ON VOICE MAIL
 FILE P FOR P/U MM