Plan Review Details - Permit 04090836
Plan Review Stops For Permit 04090836
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-02 Cont ID  
Sent By jwitmer Date 2004-12-02 Time 12:40 Rev Time 0.50
Received By jwitmer Date 2004-12-02 Time 12:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-22 Cont ID  
Sent By jwitmer Date 2004-10-22 Time 14:27 Rev Time 2.22
Received By jwitmer Date 2004-10-22 Time 14:20 Sent To  
Notes
2004-10-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090836
 ADD: 1400 CENTREPARK DR # 10TH FL
 CONT: PASS INTERNATIONAL
 TEL: (561)239-0125
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) PROVIDE THE SUITE NUMBER WHERE WORK
 WILL BE COMPLETED UNDER THIS PERMIT.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) PLANS INDICATE IN THE LEGOND SHEET 1,
 1 HR WALL AT STAIRWELL, TABLE 705.2.1.
 REQUIRES A 2HR WALL AT STAIRWAYS ( SHAFT
 CONSTRUCTION OVER 4 STORIES).
  
 5) PLANS DO NOT INDICATE THAT THIS BUILD
 ING IS FIRE SPRINKLERED,DOOR 1 AND 12
 DO NOT MEET THE REQUIREMENTS OF:
 1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
  
 6) SHEET 2 DETAIL 2 PROVIDE THE RATED
 WALL ASSEMBLY NUMBER FOR 1 HR RATING,
 EITHER UL, GYPSUM, ETC...
  
 7)DOOR SCHEDULE, DOOR# 1/12 ARE EXISTING
 RATED DOORS, BUT NOT NOTATION AS TO
 DOOR CLOSURE. 705.1.3.5 FIRE DOORS SHALL
 BE EQUIPPED WITH AN APPROVED CLOER.
  
 8) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-10-05 Cont ID  
Sent By jleahy Date 2004-10-05 Time 15:31 Rev Time 0.45
Received By jleahy Date 2004-10-05 Time 15:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-22 Cont ID  
Sent By nmccray Date 2004-12-22 Time 09:43 Rev Time 0.00
Received By nmccray Date 2004-12-22 Time 09:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-10-28 Cont ID  
Sent By mcarsill Date 2004-10-28 Time 16:03 Rev Time 0.00
Received By mcarsill Date 2004-10-28 Time 16:02 Sent To  
Notes
2004-10-28 00:00:001) THE STAIRWELL WALL SHOULD BE TWO
 HOUR RATED NOT ONE HOUR AS DEPICTED
 ON THE PLANS.
  
 2) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 3) EXISTING DOOR # 1 IS REQUIRED TO
 HAVE A DOOR CLOSER ON IT.
  
 4) COULD NOT LOCATE ANY EMERGENCY
 LIGHTING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-23 Cont ID  
Sent By mjacobs Date 2004-12-23 Time 14:13 Rev Time 0.00
Received By mjacobs Date 2004-11-22 Time 17:23 Sent To  
Notes
2004-11-22 00:00:00SENT TO COMM BD#22/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-23 Cont ID  
Sent By mjacobs Date 2004-12-23 Time 14:14 Rev Time 0.00
Received By mjacobs Date 2004-10-04 Time 13:14 Sent To  
Notes
2004-10-04 00:00:00TO COMM BD#44

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-12-06 Cont ID  
Sent By pkrauss Date 2004-12-06 Time 07:15 Rev Time 0.40
Received By pkrauss Date 2004-12-06 Time 07:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-10-08 Cont ID  
Sent By pkrauss Date 2004-10-08 Time 14:58 Rev Time 0.40
Received By pkrauss Date 2004-10-08 Time 14:58 Sent To  
Notes
2004-10-08 00:00:00DENIED:
 1.PLAN SHEET 7 OF 7 CONDENSING UNIT
 DETAIL, PLEASE PROVIDE THE FOLLOWING:
 - DETAIL OF THE ATTACHMENT TO THE ROOF.
 - INDICATE DEMENSION BEWTEEN THE ROOF
 SURFACE AND THE BOTTOM OF THE SUPPORT
 RAIL, REFERENCE 2001 FBC 1511.7.
  
 2.PLEASE CLARIFY OUTSIDE AIR
 CALCULATIONS.PLAN DOES NOT INDICATE
 OUTSIDE AIR INTAKE OR DUCTWORK.IS
 THIS EXISTING?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.