Plan Review Details - Permit 04090812
Plan Review Stops For Permit 04090812
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-01-25 Cont ID  
Sent By kstevens Date 2005-01-25 Time 08:34 Rev Time 0.50
Received By kstevens Date 2005-01-25 Time 08:34 Sent To  
Notes
2005-01-25 00:00:00 
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
  
  
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By kstevens Date 2005-01-25 Time 08:32 Rev Time 0.50
Received By kstevens Date 2005-01-25 Time 08:32 Sent To  
Notes
2005-01-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
  
 1) SECTION 104.2.1. ALL DRAWINGS SHALL
 BE SIGNED AND NAME PRINTED BY PERSON
 RESPONSIBLE FOR THE DESIGN.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]