Plan Review Details - Permit 04090793
Plan Review Stops For Permit 04090793
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-01-31 Cont ID  
Sent By jwitmer Date 2005-01-31 Time 16:23 Rev Time 0.33
Received By jwitmer Date 2005-01-31 Time 16:23 Sent To  
Notes
2005-01-31 00:00:0001-31-05 CONCRETE MIX DESIGNS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-01-26 Cont ID  
Sent By jwitmer Date 2005-01-26 Time 11:07 Rev Time 1.11
Received By jwitmer Date 2005-01-26 Time 11:07 Sent To  
Notes
2005-01-26 00:00:00PLANS APPROVED WITH BUILDING PROVISO,
 AN ACCESSIBLE PATH AROUND THE FOUNTAIN
 REQUIRED, INDICATE COMPLIANCE WITH
 DIFFERENCE WITH GRADE. 11-4.1.3(1)JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-01-18 Cont ID  
Sent By jwitmer Date 2005-01-18 Time 16:02 Rev Time 2.20
Received By jwitmer Date 2005-01-18 Time 16:02 Sent To  
Notes
2005-01-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090793
 ADD: 419 LAKEVIEW AVE
 CONT: THE WEITZ
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW/ DECK REVISION
 ACTION:DENIED
  
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 1A) SHEET S-6.0 INDICATES A SECTION# 2
 BUT PLAN DOES NOT SPECIFY WHAT THE
 RECESS IS FOR A FOUNTAIN OR WADING
 POOL?
 1B) NO INFORMATION IS PROVIDED HOW TO
 KEEP THE HANDICAPPED FROM WHEELING INTO
 THE DECK RECESS NOR THE HANDICAPPED
 TRAVEL FROM THE RAMP TO THE BUILDING
 ALSO ISN'T INDICATED, WHAT IS THE CLEAR
 WIDTH BETWEEN THE DECK RECESS AND
 GUARDRAIL?
  
 2) ORIGINAL PLANS DO NOT SHOW FOUNTAINS
 PROVIDE VALUE FOR PERMIT VALUE UPDATE?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-10 Cont ID  
Sent By jwitmer Date 2004-12-10 Time 08:12 Rev Time 3.50
Received By jwitmer Date 2004-12-10 Time 08:11 Sent To  
Notes
2004-12-10 00:00:00PLANS FOR DCA MANUFACTURED BLDG. PLUS
 17 ITEMS NOT INCLUDED UNDER DCA
 APPROVAL
 FOUNDATION AND DECK APPROVAL UNDER
 PERMIT # 04100051.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-20 Cont ID  
Sent By jwitmer Date 2004-10-20 Time 16:23 Rev Time 0.00
Received By mamini Date 2004-11-08 Time 10:32 Sent To  
Notes
2004-10-20 00:00:00BUILDING PLAN REVIEW
 PERMIT (36): 04100051- DCA MODULAR BLDG
 (32)04090793- SITE/RAMP/DECK/
 FACADE/ ROOF AND SKYLIGHT
 ADD: 419 LAKEVIEW
 CONT: THE WEITZ CO
 TEL: (561)686-5511
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN
 QUESTIONTHE BUILDING OFFICIAL MAY
 REQUIRE EXPLORATIONS, TEST OR OTHER
 ADEQUATE PROOF AS TO THE PERMISSIBLE
 SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) SALES TRAILER, PROVIDE DCA (DEPART-
 MENT OF COMMUNITY AFFAIRS) APPROVAL
 PACKAGE. THE DCA PACKAGE SUBMITTED
 STATES THESE REQUIREMENTS HAVE NOT BEEN
 COMPLETED BY THE BUILDING MANUFACTURER,
 AND ARE NOT CERTIFIED BY THE STATE MODU-
 LAR LABEL & OR CERTIFICATION. THE 17
 ITEMS NOT COVERED BY THE STATE WILL NEED
 TO BE REVIEWED & COMPLIED WITH THROUGH
 THE LOCAL DESIGN PROFESSIONALS.
 (1) COMPLETE FOUNDATION SYSTEM
 (2) RAMPS AND STAIRS
 (6) STRUCTURAL AND AESTHETIC INTER-
 CONNECTIONS BETWEEN MODULES
 (7) INSTALLATION OF INSULATION @
 FLOORS, CEILING & END WALLS AT
 MATING LINES
 (9) INSTALL FIRESTOPPING AT ALL MATE
 LINES FLOOR / CEILING.
 (10) STORM PROTECTION 1606.1.4. SEE
 BUILDING OFFICIAL INTERPRETATION
 (12) SKYLIGHT CONSTRUCTION
 (13) FLOOR FINISH MATERIALS
 (14) DOORS INDICATED ON FLOOR PLANS
 (17) GUTTERS AND DOWNSPOUTS
  
 THE EXEMPTION IN 553.10(8)(E) THAT THE
 LOCAL BUILDING DEPARTMENT DOES NOT
 INSPECT OR REVIEW MODULAR BUILDINGS IS
 ONLY WHEN NO RECONSTRUCTION OF THE UNIT
 IS TO OCCUR. THE FLOOR PLAN OF THE DCA
 UNIT VERSES THE FLOOR PLAN SUBMITTED BY
 BAP DEVELOPMENT INDICATES WORK BY ALL
 TRADES ALLOWING FOR LOCAL PLAN REVIEW
 COMMENTS AND INSPECTION.
  
 4) F102.1 NO TYPE VI CONSTRUCTION
 ALLOWED IN THE "FIRE DISTRICT". DECK,
 EXTERIOR WALLS OR RAMPS NOR THE MANUFACT
 URED BUILDINGS.
  
 5) ACCESSIBLE BUILDINGS: 11-4.1.3(8)(A)
 (III)ACCESIBLE ENTRANCES SHALL BE THE
 ENTRENCES USED BY THE MAJORITY OF
 PEOPLE VISITING OR WORKING IN THE BUILD-
 NG, NOT TO BE LOCATED IN THE BACK OF THE
 BUILDING.
  
 6) WITH AN ACCESSIBLE ENTRANCE PARKING
 FACILITIES SHALL BE LOCATED ON THE SHORT
 EST ACCESSIBLE ROUTE OF TRAVEL TO AN
 ACCESSIBLE PEDESTRIAN ENTRY INTO THE
 FACILITY. 11-4.6.2 LOCATION.
  
 7) A-4.0 PARKING STALL DETAIL TO COM-
 PLY WITH DOUBLE LINE STRIPING SEE ATTACH
 MENT.
  
 8)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE ELEVATIONS FOR HANDICAPPED PARK-
 ING AND ACCESS AISLE,CROSS SECTION SLOPE
  
 9) A-4.0 HANDRAIL DETAIL TO COMPLY WITH
 11-4.9.4(3) THE CLEAR SPACE BETWEEN HAND
 RAILS & WALL SHALL BE 1 1/2".
  
 10)A-4.0 SECTION AA INDICATES THE USE OF
 HAND/ GUARDRAILS, TO COMPLY WITH:
 1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 11) A-4.0 SAME SECTION AA INDICATES A
 SKYLIGHT BUT NO DETAILS,CURBS PRODUCT
 APPROVALS,ETC
  
 12)SHEET A-2.0 HAS NOTES THAT WORK WILL
 BE PREFORMED BY OTHERS,EXTERIOR DOORS,
 EXTERIOR WINDOWS, INTERIOR WALLS, DECK &
 SKYLIGHT. WHO WILL BE INSTALLING THESE
 ITEMS IF NOT THE GC? THE GENERAL CONTRAC
 TOR WILL ASSUME RESPONSIBLITY FOR THE
 PROJECT?
  
 13)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS, CURTAIN WALLS
 B) EXTERIOR DOORS
 C) SKYLIGHTS
 D) STORM SHUTTERS
 E) STRUCTURAL COMPONENTS,TRUSS ANCHORS
 F) ROOFING
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 14) SHEET A-6.0 INDICATES ELEVATIONS BUT
 NO FRAMING INFORMATION ON ELEVATIONS?
 NOR STOREFRONT, MULLIONS ETC
  
 15) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 16) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 17)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 18)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 19)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 20) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 21) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 22) S-1 INDICATES THE ANCHOR SCHEDULE
 BUT NO MANUFACTURER IS NOTED:
 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 23) CORRECT THE STREET NAME TO THE SOUTH
 OF THE PROPERTY, TO LAKEVIEW, NOT
 JASSMINE OR OKEECHOBEE.
  
 24)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-02-01 Cont ID  
Sent By dpalmer Date 2005-02-01 Time 11:56 Rev Time  
Received By dpalmer Date 2005-02-01 Time 11:56 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-01-10 Cont ID  
Sent By dpalmer Date 2005-01-10 Time 16:22 Rev Time 0.00
Received By dpalmer Date 2005-01-10 Time 15:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-12-08 Cont ID  
Sent By dpalmer Date 2004-12-08 Time 15:01 Rev Time 0.30
Received By dpalmer Date 2004-12-08 Time 15:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-10-06 Cont ID  
Sent By dpalmer Date 2004-10-06 Time 10:58 Rev Time 0.50
Received By dpalmer Date 2004-10-06 Time 10:58 Sent To  
Notes
2004-10-06 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASESEE NO ELECTRICAL PLANS
 WERE SUBMITTED FOR HOOK-UP OF TRAILERS.
 ARE THESE STATE APPROVED UNITS?
 ELECTRICAL LTS/PUMP ON LANDSCAPE PLANS
 NEEDS TO PROVIDE MORE INFORMATION ON
 HOOK-UP AND FROM WHERE? GFI PROTECTION
 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2004-12-06 Cont ID  
Sent By mamini Date 2004-12-06 Time 16:29 Rev Time 0.50
Received By mamini Date 2004-12-06 Time 16:28 Sent To  
Notes
2004-12-06 00:00:00PASSED:
  
 1. SEE PERMIT # 04110392 FOR
 UNDERGROUND UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2004-11-08 Cont ID  
Sent By mamini Date 2004-11-08 Time 10:32 Rev Time 0.00
Received By mamini Date 2004-11-08 Time 10:50 Sent To  
Notes
2004-11-08 00:00:00N:
  
 1. SEE PERMIT # 04110392 FOR UNDERGROUND
 UTILITIES AND SITE WORK. THE APPLICANT
 DECIDED TO APPLY SEPARATELY FOR
 UNDERGROUND UTILITIES AND SITE WORKS.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-10-07 Cont ID  
Sent By mamini Date 2004-10-07 Time 09:11 Rev Time 1.00
Received By mamini Date 2004-10-07 Time 09:11 Sent To  
Notes
2004-10-07 00:00:00PASSED WITH PROVISOS:
 1. PLEASE SUBMIT THE M.O.T PLANS AS
 REQUESTED ATT: WINDEL PALMER, PUBLIC
 UTILITIES 45TH AND TO FDOT IF REQUIRED
 PRIOR TO BEGINNING THE CONSTRUCTION.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-02-01 Cont ID  
Sent By nmccray Date 2005-02-01 Time 15:09 Rev Time 0.00
Received By nmccray Date 2005-02-01 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2005-01-20 Cont ID  
Sent By lmartine Date 2005-01-20 Time 15:57 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2005-01-20 00:00:00REVISION TO ADD FOUNTAINS, FIRE REVIEW
 NOT REQUIRED PER NATELM

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-12-13 Cont ID  
Sent By lmartine Date 2004-12-13 Time 11:10 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2004-12-13 00:00:00 
  
 APPPROVED PER MIKE CARSILLO ON
 12/9/04 SEE PLANS AND SUBMITTAL FORMS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-10-28 Cont ID  
Sent By nmccray Date 2004-10-28 Time 09:10 Rev Time 0.00
Received By nmccray Date 2004-10-27 Time 15:48 Sent To  
Notes
2004-10-28 00:00:00***********DENIED***********************
  
 1) PLANS INDICATE THAT THE SALES TRAILER
 IS OF TYPE VI CONSTRUCTION. THE TRAILER
 IS LOCATED IN THE CITY FIRE LIMITS AND
 CERTAIN RESTRICTIONS APPLY. TYPE VI
 CONSTRUCTION IS NOT ALLOWED IN THE CITY
 FIRE LIMITS. PLEASE SEE APPENDIX F, OF
 THE LOCAL AMENDMENTS OF THE FLORIDA
 BUILDING CODE.
  
 2) PLEASE INDICATE IN WRITING HOW LONG
 THE SALES TRAILER WILL BE ON SITE.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-01-28 Time 14:42 Rev Time 0.00
Received By mjacobs Date 2005-01-28 Time 14:42 Sent To E
Notes
2005-01-28 00:00:00TO "DP" DESK/AS BUILTS.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-27 Cont ID  
Sent By mjacobs Date 2005-01-27 Time 10:10 Rev Time 0.00
Received By mjacobs Date 2005-01-27 Time 10:10 Sent To B
Notes
2005-01-27 00:00:00TO "JW" DESK/SUBMITTALS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-26 Cont ID  
Sent By mjacobs Date 2005-01-26 Time 10:58 Rev Time 0.00
Received By mjacobs Date 2005-01-26 Time 10:58 Sent To P
Notes
2005-01-26 00:00:00TO "P" BOX/REV.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-25 Cont ID  
Sent By mjacobs Date 2005-01-25 Time 07:52 Rev Time 0.00
Received By mjacobs Date 2005-01-25 Time 07:52 Sent To B
Notes
2005-01-25 00:00:00TO "JW" DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-03 Cont ID  
Sent By mjacobs Date 2004-12-03 Time 16:55 Rev Time 0.00
Received By mjacobs Date 2004-12-03 Time 16:55 Sent To  
Notes
2004-12-03 00:00:00SENT TO COMM BD#57

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:01 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 11:15 Sent To  
Notes
2004-10-04 00:00:00TO COMM BD#32

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-12-09 Cont ID  
Sent By pkrauss Date 2004-12-09 Time 14:20 Rev Time 0.45
Received By pkrauss Date 2004-12-09 Time 14:10 Sent To  
Notes
2004-12-09 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED WITH NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS
 PER 2001 FBC(M)606.2.1 & 606.4.1
 EXCEPTION #2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-10-25 Cont ID  
Sent By pkrauss Date 2004-10-25 Time 07:35 Rev Time 0.20
Received By pkrauss Date 2004-10-25 Time 07:16 Sent To  
Notes
2004-10-25 00:00:00NO MECHANICAL PLANS SUBMITTED WITH THIS
 PERMIT APPLICATION.SEE PERMIT
 # 04100051

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-01-26 Cont ID  
Sent By kstevens Date 2005-01-26 Time 16:16 Rev Time 0.55
Received By kstevens Date 2005-01-26 Time 16:16 Sent To  
Notes
2005-01-26 00:00:00REVISION OK - SHTS P-1.0 & P-2

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-01-21 Cont ID  
Sent By jleech Date 2005-01-21 Time 15:57 Rev Time 0.50
Received By jleech Date 2005-01-21 Time 15:57 Sent To  
Notes
2005-01-21 00:00:00REVISION FOR ADDITION OF FOUNTAIN ONLY.

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-01-19 Cont ID  
Sent By jleech Date 2005-01-19 Time 14:18 Rev Time 3.00
Received By jleech Date 2005-01-19 Time 13:59 Sent To  
Notes
2005-01-19 00:00:00DENIED;
 1.FOUNTAIN SHOULD BE PERMITED
 SEPURATLY.
 2.SHOW DETAIL OF WATER HEATER. THERMAL
 EXPANSION CONTROL REQUIRED PER FBC
 PLUMBING SEC. 607.3.
 3.WATER ISOMETRIC, SHOCK ARRESTORS TO BE
 INSTALLED PER SEC.604.9. NOT NEEDED ON
 LAVS, SHR. AND TUBS.
 4.DETAIL FOR EMPLOYEE BATHROOM AND BREAK
 SINK SHOULD BE TRANSFURED FROM 8X11 SHT.
 AND 8X17 SHT.TO NEW PLUMBING PAGE.
 5.MODEL BATHROOM AND KITCHEN. SHOW
 COMPLIANCE TO THE FAIR HOUSING ACT.SHOW
 CLEAR FLOOR SPACE AND DETAILS FOR
 REQUIRED BACKING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-10 Cont ID  
Sent By kstevens Date 2004-12-10 Time 16:08 Rev Time 3.00
Received By kstevens Date 2004-12-10 Time 16:08 Sent To B
Notes
2004-12-10 00:00:00SANT. SEWER, WATER METER, AND BACKFLOW
 ARE SHOWN ON ATTACHED LETTER FROM WEITZ
 INDICATING LOCATIONS ON APPROVED PERMIT
 04110871 FOR PLUMBING WATER SERV. AND
 SEWER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-23 Cont ID  
Sent By kstevens Date 2004-10-23 Time 12:14 Rev Time 0.75
Received By kstevens Date 2004-10-23 Time 12:14 Sent To  
Notes
2004-10-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SUBMIT DETAILS FOR THE ACCESSIBLE
 FIXTURES. THE TOILET ROOM PER SECTIONS
 11-4.16, 11-4.19, & 11-4.22 AND ALL SUB-
 SECTIONS. THE DRINKING FOUNTAIN PER SEC-
 TION 11-4.15 AND ALL SUBSECTIONS. THE
 BREAK ROOM SINK PER SECTION 11-4.24 AND
 ALL SUBSECTIONS.
 2) SUBMIT A SITE PLAN SHOWING LOCATION
 OF THE SEWER CONNECTION, THE WATER METER
 AND THE RPZ BACKFLOW.
 3) FAC 61G15-23.002 ALL PLANS SHALL BE
 SIGNED AND SEALED BY THE ENGINEER, COP-
 IES ARE NOT ACCEPTABLE. ALSO ALL INFOR-
 MATION REQUIRED ON THE TITLE BLOCK SHALL
 BE SHOWN. FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-01-19 Cont ID  
Sent By mmclean Date 2005-01-19 Time 16:17 Rev Time 0.00
Received By mmclean Date 2005-01-19 Time 16:17 Sent To  
Notes
2005-01-19 00:00:00ANA APONTE APROVED TRAILER.

Review Stop Z ZONING
Rev No 2 Status P Date 2004-12-09 Cont ID  
Sent By mmclean Date 2004-12-09 Time 16:32 Rev Time 0.00
Received By mmclean Date 2004-12-09 Time 16:32 Sent To B
Notes
2004-12-09 00:00:00PROVISO: FENCE SHALL BE 5FT HT MAXIMUM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-10-20 Cont ID  
Sent By aaponte Date 2004-10-19 Time 16:42 Rev Time 0.00
Received By aaponte Date 2004-10-19 Time 16:43 Sent To  
Notes
2004-10-20 00:00:003. SIDEWALK SHALL BE A MINIMUM OF 8'
 IN CLEAR WIDTH.
2004-10-19 00:00:001. PLEASE PROVIDE SHADE TREES ALONG
 LAKEVIEW AVENUE.
 2. PLEASE PROVIDE WINDOWS ALONG THE EAST
 ELEVATION.