Plan Review Details - Permit 04090711
Plan Review Stops For Permit 04090711
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-01-03 Cont ID  
Sent By rmcdouga Date 2005-01-03 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2005-01-03 Time 07:40 Sent To  
Notes
2005-01-03 00:00:00BUILDING PROVISO
  
 1) SUBMIT TWO COPIES OF A KEY PLAN AND
 AN INSTALLATION SCHEDULE FOR THE STORM
 PANELS BEFORE THEY ARE INSTALLED.
  
 2) SUBMIT A RE-RECORDED COPY OF THE
 EXPIRED NOC BEFORE THE FIRST
 INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-11-05 Cont ID  
Sent By rmcdouga Date 2004-11-05 Time 15:13 Rev Time 0.00
Received By rmcdouga Date 2004-11-05 Time 15:13 Sent To  
Notes
2004-11-05 00:00:00DENIED
  
 1) THE SURVEY HAS THE WRONG STREET
 NAME.
 SUBMIT CORRECTED SURVEY SHOWING THE LOT
 ON FOX HOLLOW DRIVE.
  
 2) THE PRINTED NAME OF THE PERSON
 SEALING THE PLAN IS REQUIRED TO BE ON
 THE PLAN. SEE F.A.C.61G1-16.004.
  
 3) PLANS ARE REQUIRED TO BE PERSONALLY
 SIGNED BY THE RESPONSIBLE ARCHITECT PER
 F.A.C.61G1-16.003. IF THE SIGNATURE ON
 THE PLANS IS THE ARCHITECT'S LEGAL
 SIGNATURE, PLEASE SUBMIT A SIGNED AND
 SEALED LETTER STATING THIS FOR OUR
 FILES.
  
 4) ON SHEET A1 THE SECTION AT THE
 WINDOWS IN THE MASTER BEDROOM IS
 LABELED
 B ON A5 AND THERE IS NO SUCH SECTION ON
 A5. PLEASE CORRECT.
  
 5) ON SHEET A1 THE ID TAG FOR THE
 COLUMN
 IN THE LIVING ROOM IS IN THE WRONG
 LOCATION. PLEASE CORRECT.
  
 6) THE DOOR SCHEDULE ON A2 SPECIFIES
 (2)
 3'X 8' DOORS AT THE ENTRY AND THE FLOOR
 PLAN ON A1 SPECIFIES A SINGLE DOOR WITH
 A SIDELITE.
  
 7) THE WINDOWS (K) IN THE MASTER BATH
 AND BATH #2 ARE REQUIRED TO BE SAFEETY
 GLASS PER FBC 2405.2.
  
 8) THE GLASS BLOCK ON THE ZERO LOT LINE
 ARE REQUIRED TO BE ONE HOUR FIRE RATED.
 PLEASE SPECIFY THIS ON THE PLANS.
  
 9) THE GLASS BLOCK HAS THE WRONG ID TAG
 AND DOES NOT CORRESPOND TO THE
 SCHEDULE.
  
 10) ONE OF THE SECTIONS ON A2 IS
 MISLABELED. IT SHOULD BE A ON A5.
  
 11) ON SHEET S1 DETAIL MARKS (9) AT THE
 MASTER BATH, (10) AT THE LIVING ROOM
 AND
 (5) AT THE GARAGE ARE IN THE WRONG
 LOCATIONS. PLEASE CORRECT.
  
 12) ON SHEET A2 THE EXTERIOR WALL AT
 BEDROOM #4 IS INCORRECTLY IDENTIFIED AS
 WOOD FRAME BY NOTE #25 ON A1. PLEASE
 CORRECT.
  
 13) REVISE THE BUCK NOTES ON A6. FBC
 1707.4.4.2 REQUIRES WINDOW AND DOOR
 ASSEMBLIES TO BE ANCHORED THROUGH 1X
 BUCKS INTO THE SUBSTRATE.
  
 14) SPECIFY THE BOTTOM CORD LIVE LOAD
 FOR THE ROOF TRUSSES ON S3. FBC TABLE
 1604.1 REQUIRES A MINIMUM LIVE LOAD OF
 10PSF FOR ATTICS WITHOUT STORAGE.
  
 15) REVISE THE WIND SPEED ON SHEET S3.
 THE CITY OF WPB IS IN THE 140 MPH WIND
 ZONE.
  
 16) SPECIFY THE FLORIDA PRODUCT
 APPROVAL
 # (FL 599)FOR THE NUVUE CONNECTOR IN
 THE
 SCHEDULE ON S3.
  
 17) THE PLANS SHOW AN ELECTRIC WATER
 HEATER AND THE ENERGY CALC. FORM
 SPECIFIES A GAS WATER HEATER. PLEASE
 CORRECT.
  
 18) SPECIFY THE POSITIVE AND NEGATIVE
 WIND LOAD PRESSURES FOR THE TWO
 OVERHEAD
 GARAGE DOORS.
  
 19) SUBMIT A KEY PLAN AND AN
 INSTALLATION SCHEDULE INDICATING WHICH
 OPENINGS WILL BE SHUTTERED. SPECIFY THE
 TYPE OF MOUNTING, FASTENERS AND SPACING
 THAT WILL BE USED.
  
 20) SUBMIT THE INSTALLATION
 INSTRUCTIONS
 FROM MASONITE INTERNATIONAL FOR THE
 SINGLE OUTSWING EXTERIOR DOOR WITH ONE
 SIDELITE ENTRY DOOR AS SHOWN ON THE
 PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-12-24 Cont ID  
Sent By dpalmer Date 2005-12-24 Time 07:16 Rev Time 0.00
Received By dpalmer Date 2005-12-24 Time 07:04 Sent To  
Notes
2005-12-24 00:00:00REDLINED***
  
 PLEASE SEE MAX KVA ON A 20A 1-POLE
 BRANCH CIRCUIT IS 1920VA,
 PLEASE SEE POOL LT CIRCUIT SHOWS 2500VA
 VERIFY.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-24 Cont ID  
Sent By dpalmer Date 2005-11-21 Time 07:03 Rev Time 0.00
Received By dpalmer Date 2005-11-21 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-10-09 Cont ID  
Sent By dpalmer Date 2005-10-09 Time 18:53 Rev Time 0.80
Received By dpalmer Date 2005-10-09 Time 18:07 Sent To  
Notes
2005-10-09 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE REAR PORCH IS SHOWING
 A J-BOX FOR POSSIBLE FUTURE FAN/LT.
 PLEASE SEE 210.70 LS 1015.8 WHICH
 REQUIRES A LT FIXTURE OF SOME SORT FOR
 MEANS OF EGRESS.
  
 2)NOTE: PLEASE SEE LOAD CALCULATIONS FOR
 EACH PANEL ARE NOT COMPLETE AND ARE
 SHOWN WITH "0" LOAD ON EACH PANEL.
 PLEASE CORRECT, AND SHOW LOAD CALCS, AND
 LOAD ON EACH PANEL.
 215.5,220
  
 3)NOTE: PLEASE SEE PLANS FOR ALL
 LOCATIONS WHICH INDICATE A PRE-WIRE FOR
 "SD'S".
 PLEASE SEE THIS SEEMS TO BE A MISPRINT
 AS "SD" IS FOR THE SMOKE DETECTORS AND
 THIS SHOULD BE "SP" FOR SPEAKER
 PRE-WIRE, IF INDEED THIS IS WHAT IS
 MEANT.
  
 4)NOTE: PLEASE SEE SMOKE DETECTORS ARE
 BEING SHOWN CIRCUITED TO "A-20" , WHICH
 PANEL SCHEDULE SHOWS THIS AS THE SMALL
 APPLIANCE CIRCUIT.
 PLEASE SEE CIRCUIT A-20 IS ALSO BEING
 SHOWN ON PLANS FOR SMALL APPL.
 PLEASE SEE 210.52B1,210.11C1 WHICH DOES
 NOT PERMIT ANY OTHER DEVICES EXCEPT
 THOSE ALLOWED PER ABOVE.
 PLEASE ALSO SEE NOTES TO ELECTRICAL
 PLANS MENTIONS ONLY THOSE CIRCUITS
 LISTED TO BE "ARC-FAULT PROTECTED" ,
 HOWEVER UNDER THE 2002 NEC 210.12, "ALL
 OUTLETS" BRANCH CIRCUITS" FOR BEDRMS ARE
 REQUIRED TO BE PROTECTED.
 PLEASE SEE NUMEROUS CIRCUITS AS NOTED DO
 NOT CORRELATE WITH PLANS OR PANEL
 SCHEDULES/
 PLEASE SEE ARC FAULT PROTECTION LISTED
 FOR SM APPL, OVEN, A/C ETC,
 PLEASE CORRELATE ALL.
  
 5)NOTE: PLEASE SEE BATH RM SHOWING
 CIRCUIT B-10, WHICH IS FOR ENTRY. THE
 BATH RM CIRCUITING SHALL BE PER
 210.52D,210.11C3. IN EITHER CASE A
 RECEPT CIRCUIT MUST BE 20A AND #12.
  
 6)NOTE: PLEASE SEE PANEL "B" IS BEING
 SHOWN AT TWO LOCATIONS ON PLANS???
 PLEASE ADJUST.
  
 7)NOTE: PLEASE KNOW, ALL "OPTIONAL"
 ITEMS SHALL BE SHOWN AS INSTALLED OR NOT
 INSTALLED IF NOT REQUIRED.
 OPTIONS MAY BE SHOWN ON ORIGINAL PLANS
 FOR PERMITTING, HOWEVER ALL
 OPTIONS/REVISIONS ARE TO BE SUBMITTED
 FOR REVIEW BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 8)NOTE: PLEASE SEE NOTES PERTAINING TO
 AIC RATINGS OF MAINS TO BE USED.
 PLEASE CLARIFY NOTE, AS IT DOES NOT SEEM
 TO CONTAIN INFORMATION FOR LENGTHS
 BETWEEN 70-80 FT.???
 PLEASE ADJUST.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-10-15 Cont ID  
Sent By btrobaug Date 2004-10-15 Time 10:00 Rev Time 0.75
Received By btrobaug Date 2004-10-15 Time 07:34 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-19 Cont ID  
Sent By adarroug Date 2005-12-19 Time 14:17 Rev Time 0.00
Received By adarroug Date 2005-12-19 Time 14:17 Sent To E
Notes
2005-12-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 14:17 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 14:17 Sent To E
Notes
2005-11-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 09:43 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 09:43 Sent To E
Notes
2005-10-05 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 15:56 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 15:56 Sent To M
Notes
2005-05-24 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-27 Cont ID  
Sent By mjacobs Date 2004-12-27 Time 07:38 Rev Time 0.00
Received By mjacobs Date 2004-12-27 Time 07:38 Sent To B
Notes
2004-12-27 00:00:00TO "ROB MCD" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-08 Cont ID  
Sent By mmclean Date 2004-10-13 Time 17:53 Rev Time 0.00
Received By rmcdouga Date 2004-09-23 Time 14:16 Sent To  
Notes
2004-10-14 00:00:00TO SFD RACK/E
2004-09-23 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-31 Cont ID  
Sent By pkrauss Date 2005-05-31 Time 13:25 Rev Time 0.30
Received By pkrauss Date 2005-05-31 Time 13:14 Sent To  
Notes
2005-05-31 00:00:00REVISION

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-10-26 Cont ID  
Sent By btrobaug Date 2004-10-15 Time 10:00 Rev Time 0.50
Received By hmoser Date 2004-10-26 Time 15:18 Sent To P
Notes
2004-10-26 00:00:00PLEASE CHANGE RETURN AIR IN MASTER
 BEDROOM TO 14IN. PER SECTION 601.4 FBC M
 PLAN REVIEW BY HAROLD MOSER
 561(805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-03 Cont ID  
Sent By rmcdouga Date 2005-01-03 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2005-01-03 Time 07:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-08 Cont ID  
Sent By hmoser Date 2004-10-26 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2004-11-08 Time 09:41 Sent To  
Notes
2004-11-08 00:00:00DENIED
  
 1) RISER DIAGRAM DOES NOT MATCH THE
 PLANS. SUBMIT CORRECTED DIAGRAM.

Review Stop Z ZONING
Rev No 1 Status P Date 2004-10-13 Cont ID  
Sent By mmclean Date 2004-10-13 Time 17:53 Rev Time 0.00
Received By mmclean Date 2004-10-13 Time 17:53 Sent To I
Notes
***NONE***