Plan Review Details - Permit 04090518
Plan Review Stops For Permit 04090518
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-10-20 Cont ID  
Sent By jwitmer Date 2004-10-20 Time 07:10 Rev Time 1.11
Received By jwitmer Date 2004-10-20 Time 07:10 Sent To  
Notes
2004-10-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04090518
 ADD: 580 VILLAGE BLVD #350&360
 CONT: GORGE RAY JR
 TEL: (561)714-3740
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 4) UNIT# 360 SEE 1020.1(4) BUSINESS
 SINGLE EXIT, MAXIMUM DISTANCE OF TRAVEL
 TO THE EXIT DOES NOT EXCEED 75 FT.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-10-05 Cont ID  
Sent By jleahy Date 2004-10-05 Time 10:47 Rev Time 0.00
Received By jleahy Date 2004-10-05 Time 10:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-10-01 Cont ID  
Sent By mcarsill Date 2004-10-01 Time 13:52 Rev Time 0.00
Received By mcarsill Date 2004-10-01 Time 13:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2004-09-22 Time 14:23 Sent To  
Notes
2004-09-22 00:00:00TO COMM BD#22

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-10-25 Cont ID  
Sent By jleahy Date 2004-10-05 Time 10:48 Rev Time 0.20
Received By pkrauss Date 2004-10-25 Time 10:10 Sent To  
Notes
2004-10-25 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED ON PERMIT APPLICATION.
 PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-25 Cont ID  
Sent By kstevens Date 2004-10-25 Time 17:13 Rev Time 0.50
Received By kstevens Date 2004-10-25 Time 17:13 Sent To  
Notes
2004-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SUBMIT A DETAIL FOR LOUNGE SINK PER
 SECTION 11-4.24. SHOW HEIGHT 4.24.2,
 KNEE CLEARANCE 4.24.3, DEPTH OF SINK 4.
 24.4, CLEAR FLOOR SPACE SHALL BE PROVID-
 ED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH AND SHALL EXTEND A MAXIMUM OF
 19" UNDERNEATH THE SINK, (SEE FIG. 32)
 4.24.5, EXPOSED PIPES AND SURFACES 4.24.
 6.
 2) FAC 61G1-16.004(6) PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT REQUIRED
 FS 481.2055. - THIS IS FOR ALL SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]