Plan Review Details - Permit 04090278
Plan Review Stops For Permit 04090278
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-10-20 Cont ID  
Sent By jwitmer Date 2004-10-20 Time 07:38 Rev Time 0.34
Received By jwitmer Date 2004-10-20 Time 07:38 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-09-22 Cont ID  
Sent By dpalmer Date 2004-09-22 Time 06:33 Rev Time 0.20
Received By dpalmer Date 2004-09-22 Time 06:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-10-01 Cont ID  
Sent By mcarsill Date 2004-10-01 Time 13:46 Rev Time 0.00
Received By mcarsill Date 2004-10-01 Time 13:46 Sent To  
Notes
2004-10-01 00:00:001) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-08 Cont ID  
Sent By csiegber Date 2004-11-08 Time 15:15 Rev Time 0.00
Received By csiegber Date 2004-11-08 Time 15:15 Sent To P
Notes
2004-11-08 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-27 Cont ID  
Sent By csiegber Date 2004-10-27 Time 14:58 Rev Time 0.00
Received By csiegber Date 2004-10-27 Time 14:58 Sent To P
Notes
2004-10-27 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-10-20 Cont ID  
Sent By jwitmer Date 2004-10-20 Time 07:44 Rev Time 0.00
Received By jwitmer Date 2004-09-16 Time 12:07 Sent To PC
Notes
2004-09-16 00:00:00TO COMM BD#9

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-10-13 Cont ID  
Sent By pkrauss Date 2004-10-13 Time 15:45 Rev Time 0.45
Received By pkrauss Date 2004-10-13 Time 15:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-24 Cont ID  
Sent By kstevens Date 2004-11-24 Time 05:27 Rev Time 0.50
Received By kstevens Date 2004-11-24 Time 05:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-03 Cont ID  
Sent By kstevens Date 2004-11-03 Time 16:46 Rev Time 0.50
Received By kstevens Date 2004-11-03 Time 16:46 Sent To  
Notes
2004-11-03 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
  
 1) SUBMIT A DETAIL FOR BREAK AREA SINK
 SHOWING KNEE CLEARANCE 11-4.24.3, SINK
 DEPTH 11-4.24.4, CLEAR FLOOR SPACE WHICH
 SHALL BE PROVIDED IN FRONT OF A SINT TO
 ALLOW FORWARD APPROACH 11-4,24,5 (SHEET
 4 SHOWS PARALLEL APPROACH), AND EXPOSED
 PIPES AND SURFACES 11-4.24.6
 2) SUBMIT MANUF. SPECIFICATIONS FOR
 PUMP. SECTION 104.2.1
 ****NEW COMMENT
 1B) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL, AND FS
 553.80(2)(B)
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-10-09 Cont ID  
Sent By csiegber Date 2004-10-27 Time 14:58 Rev Time 0.33
Received By kstevens Date 2004-10-09 Time 16:29 Sent To  
Notes
2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SUBMIT A DETAIL FOR BREAK AREA SINK
 SHOWING KNEE CLEARANCE 11-4.24.3, SINK
 DEPTH 11-4.24.4, CLEAR FLOOR SPACE WHICH
 SHALL BE PROVIDED IN FRONT OF A SINK TO
 ALLOW FORWARD APPROACH 11-4.24.5, & EX-
 POSED PIPES AND SURFACES 11-4.24.6
 2) SUBMIT MANUF. SPECIFICATIONS FOR PUMP
 SECTION 104.2.1
 3) SUBMIT A WATER RISER DIAGRAM SHOWING
 PIPE SIZES AND VALVE REQUIRED BY SECTION
 606.1(4). SECTION 104.3.1.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]