Plan Review Details - Permit 04081463
Plan Review Stops For Permit 04081463
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-11-18 Cont ID  
Sent By dpalmer Date 2004-11-18 Time 18:46 Rev Time 0.30
Received By dpalmer Date 2004-11-18 Time 18:46 Sent To  
Notes
2004-11-18 00:00:00REDLINED SD'S PER NFPA-72
 GFI PER 210.52E

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-15 Cont ID  
Sent By dpalmer Date 2004-11-15 Time 11:22 Rev Time 0.50
Received By dpalmer Date 2004-11-15 Time 11:22 Sent To  
Notes
2004-11-15 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE SOME OF THE COMMENTS
  
 FROM FIRST REVIEW STILL NEED TO BE
 ADDRESSED.
  
 2)NOTE: PLEASE INCLUDE CWP AS PART OF
 THE GROUNDING ELECTRODE SYSTEM. 250.50
  
 3)NOTE: PLEASE SEE NOT ALL SHEETS HAVE
 THE PRINTED NAME AND SIGNATURE OF PERSON
 RESPONSIBLE FOR PLAN, PLEASE ALSO SEE
 RISER DIAGRAM. FBC 104.2.1
  
 4)NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER 210.52D
 AND 210.11C3 20A/#12
  
  
 5 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED. 210.8A6
 PLEASE ALSO SEE SPACING PER 210.52C1,
 (ABOVE) WINE COOLER AND DW?
  
 7)NOTE: PLEASE SEE TWO DIFFERENT
 ELECTRICAL DRAWINGS FOR KITCHEN WAS
 SUBMITTED?
  
 8)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER 220.31B
 215.5
  
 8)NOTE: PLEASE SEE EACH ROOM IS SHOWN ON
 AN INDIVIDUAL SHEET. UNABLE TO CLEARLY
 SEE WHERE SD'S WOULD BE LOCATED OUTSIDE
 BEDRMS.
 NFPA-71 8-1.4.1.6.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.'
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 7)NOTE:

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-08-31 Time 15:52 Rev Time 0.33
Received By dpalmer Date 2004-09-14 Time 15:53 Sent To  
Notes
2004-09-14 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE APPLICATION MENTIONS
 RE-WIRE OF HOUSE. PLEASE SUBMIT PLAN
 SHOWING ALL ELECTRICAL DEVICE LOCATIONS
 PER 2002 NEC.
  
 2)NOTE: PLEASE SUBMIT A PANEL SCHEDULE
 SHOWING MIN CIRCUITS/OCP/AWG.
 215.5
 3)NOTE: PLEASE INCLUDE WIRING OF A/C
 SYSTEM IN ELECTRICAL RISER DIAGRAM.
  
 4)NOTE: PLEASE HAVE PRINTED NAME AND
 SIGNATURE OF PERSON RESPONSIBLE FOR PLAN
 (S). PER FBC 104.2.1
  
 5)NOTE: PLEASE CLARIFY IF COLD WATER
 WILL BE APART OF GROUNDING ELECTRODE
 SYSTEM.
 250.50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-17 Cont ID  
Sent By mjacobs Date 2004-11-17 Time 10:57 Rev Time 0.00
Received By dpalmer Date 2004-11-18 Time 18:45 Sent To B
Notes
2004-11-17 00:00:00SENT TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-01 Cont ID  
Sent By csiegber Date 2004-11-01 Time 14:04 Rev Time 0.00
Received By csiegber Date 2004-11-01 Time 14:04 Sent To  
Notes
2004-11-01 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-31 Cont ID  
Sent By csiegber Date 2004-08-31 Time 15:52 Rev Time 0.00
Received By csiegber Date 2004-08-31 Time 15:52 Sent To E
Notes
***NONE***